ECB violations
49-59 Riverdale Avenue, Brooklyn • Block 03583 • Lot 0006
49 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 24, 2026 | 39193563K | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSEWRVED HOLE PENETRATIONS THROUGHOUT BASEMENT. POTENTIAL HAZ... | $2,500 | $0 | Jul 9, 2026 |
| Jun 24, 2026 | 39193564M | ACTIVE | CLASS - 2 | FAILURE TO POST AND DISTRIBUTE NOTICE TO OCCUPANTS OF TPP. OBSERVED NO TTP ON FILE AND NO TPP POSTED., POST/DISTR. NO... | $1,250 | $0 | Jul 9, 2026 |
| Jun 24, 2026 | 39193570Z | ACTIVE | CLASS - 2 | FOUND AO SMITH HW-520 HOT WATER BOILER NOT REGISTERED AND LEAKING PRESSURE RELIEF VALVE ON HEATING BOILER., MAINTAIN ... | $1,250 | $0 | Jul 9, 2026 |
| Jul 2, 2025 | 39152646P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Jul 8, 2025 |
| Jul 2, 2025 | 39152648Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 C... | $2,500 | $0 | Jul 8, 2025 |
| Jul 2, 2025 | 39152647R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED CRACKS ON PARAPET WALLS. LOCATED AT EXPOSURE 1,2,AND ... | $2,500 | $0 | Jul 8, 2025 |
| Jul 2, 2025 | 39152690M | RESOLVE | CLASS - 3 | CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTION | $500 | $0 | Jul 8, 2025 |
| Oct 30, 2023 | 39098303Z | RESOLVE | CLASS - 2 | MULTIPLE SMALL CRACKS ON PARAPET AND FACADE TO EXTERIOR ROOF LEVER AND THROUGHOUT BUILDING., REPAIR AND/OR REPLACE | $625 | $0 | Nov 14, 2023 |
| Oct 30, 2023 | 39098304K | RESOLVE | CLASS - 2 | HOLE PENETRATIONS IN CEILING AND WALLS AT CELLAR LEVEL., REPAIR AND/OR REPLACE | $625 | $0 | Nov 14, 2023 |
| Oct 30, 2023 | 39098256P | ACTIVE | CLASS - 2 | OBSERVED NO FRESH AIR VENTILATION IN THE BOILER ROOM. AS PER FGC 304.4.2 PROVISIONS MUST BE MADE FOR PROPER AIR BALAN... | $625 | $0 | Nov 15, 2023 |
| Oct 30, 2023 | 39098305M | ACTIVE | CLASS - 2 | MAJOR SIGNS OF WATER PENETRATION IN BOTH (A & B) BULKHEADS AND THROUGHOUT BUILDING., REPAIR AND/OR REPLACE | $625 | $0 | Nov 14, 2023 |
| Oct 30, 2023 | 39098257R | RESOLVE | CLASS - 2 | OBSERVED IN THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR NO VENTILATION. AS PER E 3 AND E 4 OF THE FUEL GAS CODE... | $625 | $0 | Nov 14, 2023 |
| Mar 15, 2022 | 35650600X | RESOLVE | CLASS - 2 | 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),FGC APPENDIX E(E4)(2014 CODE)OBSERVED... | $1,250 | $0 | Aug 17, 2022 |
| Mar 15, 2022 | 39058208Y | ACTIVE | CLASS - 2 | I DID NOT OBSERVE A FRESH AIR INTAKE VENT IN THE BOILER ROOM ALSO I DID NOT OBSERVE AND FRESH ARE VENTILATION THE THE... | $625 | $0 | Mar 29, 2022 |
| Mar 15, 2022 | 35651048X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED AT ROOFLEVEL PARAPET WALL CHIMNEY,SEVERAL CRACKS THROU... | $625 | $0 | Aug 17, 2022 |
| Mar 15, 2022 | 35651047Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:NO FIRE STOPPINGPER BC712.3;27-345.OBSERVED AT CELLAR LEVEL UTI... | $1,250 | $0 | Aug 17, 2022 |
| Mar 15, 2022 | 35651049H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED AT CELLAR LEVEL STAIRCASE HAVE BECOME POROUS ALLOWING ... | $625 | $0 | Aug 17, 2022 |
| Nov 17, 2021 | 39051395R | RESOLVE | CLASS - 2 | NOTED: OBSERVED CRACKS AT PARAPET WALL LEVEL, SPALLING AND MISSING CEMENT STUCCO THROUGHOUT EXTERIOR WALLS, MISSING A... | $3,125 | $0 | Dec 13, 2021 |
| Nov 17, 2021 | 39051396Z | RESOLVE | CLASS - 2 | NOTED: OBSERVED THROUGHOUT ROOF AT VARIOUS LOCATIONS, LOOSE AND DETACHED ALUMINUM FLASHING., REPAIR AND/OR REPLACE | $625 | $0 | Dec 13, 2021 |
| Nov 17, 2021 | 39051496X | ACTIVE | CLASS - 2 | I OBSERVED NO VENTILATION IN THE GAS METER ROOM ALSO I DID NOT OBSERVE THE FRESH AIR IN TAKE FOR THE BOILER ROOM., RE... | $625 | $0 | Dec 13, 2021 |
| Nov 17, 2021 | 39051397K | ACTIVE | CLASS - 2 | NOTED: SPALLING PLASTER AT BOTH EAST AND WEST BULKHEADS, WEST BULKHEAD HAS LOOSE WALL TILES ON THE VERGE OF DETACHING... | $625 | $0 | Dec 14, 2021 |
| Apr 29, 2021 | 39040412X | RESOLVE | CLASS - 2 | STUCCO LAYER HAS CRACKS AND IN SOME AREAS THE STUCCO HAS FALLEN ON TO THE FIRE ESCAPE ON EXPOSURE 2 AND 3 , EXPOSURE ... | $1,250 | $0 | May 10, 2021 |
| Feb 20, 2020 | 39018198N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR OF THE BUILDING CRACKS THUR OUT, ON ROOF SOME PARTS FALLING., MAINTAIN EXTERIOR BUILDING... | $1,250 | $0 | Mar 16, 2020 |
| Jan 22, 2019 | 35379803K | RESOLVE | CLASS - 2 | ALTERED/CHANGED BUILDING OCCUPIED W/O A VALID C OF O AS PER 28-118.3.1-28-118.3.2 BUILDING ALTERED UNDER JOB APPLICAT... | $0 | $0 | May 6, 2019 |
| Jan 22, 2019 | 35372668P | RESOLVE | CLASS - 2 | ELECTRICAL WORK WITHOUT A PERMIT.I OBSERVED NEW RAB LIGHTS THROUGHOUT STAIRWELL AND ROOF INSTALLED WITHOUT A PERMIT C... | $0 | $0 | May 16, 2019 |
| Jan 22, 2019 | 35379802Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:OBSERVED ON ROOF-CRACKS THROUGHOUT PARAPET WALL AT ALL E... | $0 | $0 | May 6, 2019 |
| Oct 19, 2018 | 35361471H | RESOLVE | CLASS - 2 | ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPPANCY AS PER 28-118.3.1-28-118.3.2.NOTED:BUILDI... | $0 | $0 | Jan 28, 2019 |
| Aug 15, 2018 | 32096032M | RESOLVE | CLASS - 2 | 34A,50,50A,50B,50C,50D,50E-FOUND 1)HYDROTHERM MR1200B BOILER. 50)BACKFLOW LEAKING. 50A)CIRCULATING PUMPS LEAKING. 50B... | $0 | $0 | Nov 26, 2018 |
| Aug 1, 2018 | 35347076R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED ON 8/1/2018 AT ABOVE ADDRESS NO VENTILATION IN GAS MET... | $0 | $0 | Oct 29, 2018 |
| Aug 1, 2018 | 35341623J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES.ROOF LEVEL CRACKS IN WALLS PARTS FALLING OFF ON TO ROOF AND PAR... | $3,125 | $3,125 | Oct 29, 2018 |
| Apr 18, 2018 | 32096507R | RESOLVE | CLASS - 2 | B254,22A,325A. AS PER CLASS 2 (B254) 28-301.1 HYDROTHERM BOILER, MODEL MR 1200B HAS VIOLATING CONDITIONS; 22A-PUMP LE... | $0 | $0 | Jul 16, 2018 |
| Apr 18, 2018 | 32096508Z | RESOLVE | CLASS - 2 | B254,50. AS PER CLASS 2 (B254) 28-301.1; 50-BOILER INOPERATIVE. | $0 | $0 | Jul 16, 2018 |
| Feb 6, 2018 | 35311734P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED IN CELLAR NUMEROUS JIM CAPS INSTALLED ON THE SANITARY... | $0 | $0 | May 21, 2018 |
| Feb 6, 2018 | 35298040R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE-STOPPING PER BC 712.3; 27;345. NOTED: OBSERVED THERE A... | $0 | $0 | May 21, 2018 |
| Feb 6, 2018 | 35298039J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: OBSERVED AT ROOF, PARAPET WALL HAS VERTICAL CRACKS, SPI... | $0 | $0 | May 21, 2018 |
| Jul 26, 2017 | 35287059N | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE (GFCI) GROUND FAULT CIRCUIT INTERRUPTER PROTECTION AS REQUIRED.OBSERVED LAUNDRY ROOM RECEPTACLE OU... | $0 | $0 | Oct 16, 2017 |
| Jul 26, 2017 | 35272340N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTED. OBSERVED ON ROOF,LOOSE AND DETACHEC FLASHING THROUGHOUT ROO... | $0 | $0 | Oct 16, 2017 |
| Jul 26, 2017 | 35287060K | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE ADEQUATE GROUNDING OF ELECTRICAL SYSTEMS. OBSERVED CORRODED AND DETERIORATING CONDUIT AND CONDUCTO... | $0 | $0 | Oct 16, 2017 |
| Feb 1, 2017 | 35226457J | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER; RE: INSTALLATION/MAINTENANCE OF PLUMBING MATERAILS/EQUIPMENT PER PC 1... | $0 | $0 | Apr 3, 2017 |
| Feb 1, 2017 | 35226458L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 2/1/17 IN BOILER ROOM EXPOSED WIRES ON THE CONTROL PAN... | $0 | $0 | Apr 3, 2017 |
| Feb 1, 2017 | 35226456H | RESOLVE | CLASS - 1 | MISC VIOL. OBSERVED ON 2/1/17 IN BASEMENT FUTURE GAS CONNECTIONS EXISTPHOTOS TAKEN. RMDY:COMPLY WITH SUMMONS. | $0 | $0 | Apr 3, 2017 |
| Oct 12, 2016 | 35214324H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: FAILURE TO COMPLY W/ LAW FOR DRAINAGE SYSTEM PER PC702.1;27-911. @... | $0 | $0 | Nov 14, 2016 |
| Oct 12, 2016 | 35216150X | RESOLVE | CLASS - 2 | ALTERED/CHANGED BLDG OCCUPIED W/OUT A VALID C OF O AS PER 28-118.3.1-28-118.3.2. NOTE: PREMISES OCCUPIED UNDER TEMPOR... | $0 | $0 | Nov 14, 2016 |
| Oct 12, 2016 | 35216165Z | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE: BULKHEAD DOORS FOR EAST & WEST SIDE NOT SELF CLOSING AFTER U... | $0 | $0 | Nov 14, 2016 |
| Oct 12, 2016 | 35214526X | RESOLVE | CLASS - 1 | SEC: FGC 411.1. RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. @ TIME OF INSP 11:40AM ON 10/12/16 @ ABOVE ADRESS ... | $0 | $0 | Nov 14, 2016 |
| Oct 12, 2016 | 35216164R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTE: PARAPET WALL & CHIMNEY @ ROOF LEVEL HAS CRACKS & MISSING COP... | $0 | $0 | Nov 14, 2016 |
| Oct 12, 2016 | 35214525Y | RESOLVE | CLASS - 1 | SEC: FGC408.2. FUTURE CONNECTIONS EXIST DOWN STREAM OF APPLIANCE. @ TIME OF INSP 11:40AM ON 10/12/16 @ ABOVE ADDRESS ... | $0 | $0 | Nov 14, 2016 |
| Jun 3, 2016 | 35195206X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 7123; 27-345. NOTED: AT CELLAR, GS METER R... | $0 | $0 | Sep 12, 2016 |
| Jun 3, 2016 | 35195207H | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: BULKHEADDOORS FOR EAST AND WEST SIDE NOT SELF CLOSING A... | $0 | $0 | Sep 12, 2016 |