ECB violations
41 Lott Avenue, Brooklyn • Block 03610 • Lot 0009
39 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 3, 2021 | 39040893X | RESOLVE | CLASS - 2 | BOILER SAFETY VALVE DISCHARGE NOT PIPED TO A SAFE LOCATION MC1006.6 MISSING REMOTE EMERGENCY SWITCH OUTSIDE BOILER RO... | $1,250 | $0 | Jul 18, 2022 |
| Feb 10, 2021 | 35547755P | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT OBSERVED AT 1145AM BOILERS INSTALLED IN APARTMENTS 2B,3C,AND 4B.NO ELECTRICAL APPLIC... | $0 | $0 | Jul 26, 2021 |
| Feb 10, 2021 | 35547754N | RESOLVE | CLASS - 1 | UNSAFE UNSUITABLE UNAPPROVED ELECTRICAL EQUIPMENT DEVICES APPARATUS APPLIANCES MATERIALS OR WIRING UN USE.EXPOSED ELE... | $400 | $0 | Jun 6, 2022 |
| Feb 3, 2021 | 39035782R | RESOLVE | CLASS - 2 | I OBSERVED ON OUTSIDE OF BUILDING SEVERAL VENT PIPES FOR COMBO TANKLESS BOILER AND HOT WATER UNITS IN APARTMENTS AND ... | $0 | $0 | Jun 9, 2021 |
| Feb 3, 2021 | 35547757Z | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT PERMIT.OBSERVED AT 3:15PM 5 DISCONNECT SWITCHES INSTALLED ON OUTSIDE WALL IN BASEMENT FOR BOI... | $0 | $0 | Jun 30, 2021 |
| Feb 3, 2021 | 35547752J | RESOLVE | CLASS - 2 | FAIL TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS ENCLOSURES CABLE ARMOR.SERVICE GROUND RACEWAY NOT ... | $600 | $0 | Dec 8, 2021 |
| Jun 12, 2018 | 35335531L | RESOLVE | CLASS - 2 | ELECTRICA; WORK W/OUT A PERMIT.OBSERVED IN FLS 1-4 OF BLDG. THE INSTALLATION OF EMERGENCY LIGHTING HARD WIRED SMOKE D... | $0 | $0 | Dec 5, 2018 |
| Jun 12, 2018 | 35335452N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT EXP 3 ROOF LEVEL CRACKS IN WALL IN 2 SPOTS OF THE WALL... | $0 | $0 | Aug 13, 2018 |
| Jun 12, 2018 | 35335530J | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE ADEQUATE GROUNDINGS OF (ELECTRICAL) SYSTEMS.OBSERVED @WATER MAIN LOCATED IN THE CELLAR.MAIN GROUND... | $500 | $0 | Dec 5, 2018 |
| May 1, 2018 | 35337783R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35321884J ISSUED ON 02-06-18 & TO FILE A C OF C PURSUAN... | $625 | $0 | Jul 2, 2018 |
| Mar 12, 2018 | 37009421J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #32088927N ISSUED ON 06/16/2017 AND TO FILE... | $0 | $0 | Jun 18, 2018 |
| Mar 12, 2018 | 37009422L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VILATION #32088928P ISSUED ON 06/16/2017 AND TO F... | $0 | $0 | Jun 18, 2018 |
| Feb 6, 2018 | 35321884J | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED: @ EXP#2 GATE DESIGNATED EGRESS FOR FIRE ESCAPE @ EXP#4 IS CHA... | $1,000 | $0 | May 7, 2018 |
| Dec 4, 2017 | 32092205N | RESOLVE | CLASS - 2 | 50. VIOLATING CONDITION (B254) (50)NO AIR GAP ON PRESSURE REDUCING VALVE ON BAXI BOILER IN APARTMENT 2D. | $250 | $0 | Apr 23, 2018 |
| Aug 16, 2017 | 35233181N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUM/VIO#35071045K ISSUED ON 08/02/11 & TO FILE A C OF C PURSUANT TO... | $2,000 | $0 | Dec 4, 2017 |
| Aug 16, 2017 | 35233180L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUM/VIO#35075433K ISSUED ON 07/11/17 & TO FILE A C OF C PURSUANT TO... | $2,000 | $0 | Dec 4, 2017 |
| Jun 16, 2017 | 32088928P | RESOLVE | CLASS - 2 | 24B,36,50,50A,50B,50C,50D,50E. 50-SAFETY VALVE DISCHARGE PIPES NOT SEPARATE INTO DRAIN WITH AIR GAP; 50A-BOILER SAFET... | $500 | $0 | Aug 14, 2017 |
| Jun 16, 2017 | 32088927N | RESOLVE | CLASS - 2 | 50,50A,15,34B,36. WEIL MCLAIN IN CELLAR BOILER ROOM, 52,000 BTU; 50-LOUVER TO BOILER ROOM FRESH AIR IS DEFECTIVE AND ... | $500 | $0 | Aug 14, 2017 |
| Apr 28, 2017 | 35293852J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER,LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES PER BC 1006.1;... | $1,250 | $0 | Nov 27, 2017 |
| Jul 11, 2015 | 32075432Z | RESOLVE | CLASS - 1 | B154,36,24B,50A,50B,50C. 50A-NO FLOOR DRAIN; 50B-PIPE BACKFLOW PREVENTER DISCHARGE DOWN; 50C-EXHAUST VENTING IS TO CL... | $2,500 | $0 | Aug 31, 2015 |
| Jul 11, 2015 | 32075433K | RESOLVE | CLASS - 1 | B101,50A. NO WORK PERMIT FILED WITH D.O.B. FOR THE GAS FIRED BAXI BOILER. | $4,000 | $0 | Aug 31, 2015 |
| Jul 11, 2015 | 32075434M | RESOLVE | CLASS - 1 | B154,36,24,32A,15. 50A-NO FLOOR DRAIN; 50B-EXHAUST VENTING IS TOO CLOSE TO THE WINDOW. | $2,500 | $0 | Aug 31, 2015 |
| Oct 8, 2014 | 32074705K | RESOLVE | CLASS - 1 | B101, 50A. 50A-NO WORK PERMIT FILED WITH DOB FOR THE HOT WATER BOILER. | $0 | $0 | May 4, 2015 |
| Oct 8, 2014 | 32074702P | RESOLVE | CLASS - 2 | B254,36,15,32A,50A. 50A-PIPE BACK FLOW PREVENTOR DISCHARGE DOWN TO THREADED END. | $500 | $0 | Dec 15, 2014 |
| Oct 8, 2014 | 32074704Z | RESOLVE | CLASS - 2 | B254,36,15,32A | $500 | $0 | Dec 15, 2014 |
| Oct 8, 2014 | 32074701N | RESOLVE | CLASS - 2 | B254,36,15,32A,50A. 50A-PIPE BACK FLOW PREVENTOR DISCHARGE DOWN. () END. | $500 | $0 | Dec 15, 2014 |
| Oct 8, 2014 | 32074703R | RESOLVE | CLASS - 2 | B254,36,15,32A,50A. 50A-PIPE BACK FLOW DISCHARGE DOWN. | $500 | $0 | Dec 15, 2014 |
| Aug 2, 2011 | 32071041N | RESOLVE | CLASS - 2 | B254,4A,19B,36,32A,15,16,32A,50A,B,24B. 50A- PIPE BACK FLOW DOWN. 50B-PIPE SAFETY VALVE DOWN NO THREADED END. | $500 | $0 | Jun 27, 2012 |
| Aug 2, 2011 | 32071042P | RESOLVE | CLASS - 2 | B254,36,4A,19B,15,16,32A,38,50A,B,C,24B. 50A- PIPE BACK FLOW DOWN. 50B- PIPE SAFETY VALID DISCHARGE DOWN NO THREADED ... | $500 | $0 | Jun 27, 2012 |
| Aug 2, 2011 | 32071044Z | RESOLVE | CLASS - 2 | B254,36,4A,19B,15,16,50A,B,C,D,32A. 50A- NO CHECK VALVE ON FEED WATER LINE. 50B- SPILL SWITCH JUMPS OUT. 50C- (MANUEL... | $500 | $0 | Jun 27, 2012 |
| Aug 2, 2011 | 32071048X | RESOLVE | CLASS - 2 | B254,4A,19B,36. | $500 | $0 | Jun 27, 2012 |
| Aug 2, 2011 | 32071039Y | RESOLVE | CLASS - 2 | B254,38,15,16,22A,19B,4A,36. 50A- BOILER ROOM NOT A STORAGE ROOM. 50B-BOILER ROOM FIRE DOOR DOES NOT OPEN TO EGRESS. ... | $500 | $0 | Dec 5, 2011 |
| Aug 2, 2011 | 32071040L | RESOLVE | CLASS - 2 | B254,4A,19B,15,16,32A,38,36,50A. 50A- NO EMERGENCE FUEL CUT OFF SWITCHOUTSIDE OF BOILER ROOM DOOR. 50B- PIPE SAFETY V... | $500 | $0 | Dec 5, 2011 |
| Aug 2, 2011 | 32071043R | RESOLVE | CLASS - 2 | B254,4A,19B,36,15,16,34B,24B,38,32A,50A,B. 50A- PIPE SAFETY VALVE DOWN50B- PIPE BACK FLOW PREVENTOR DISCHARGE DOWN. 5... | $500 | $0 | Jun 27, 2012 |
| Aug 2, 2011 | 32071047Y | RESOLVE | CLASS - 3 | B354,15,16,32A,50A,B,19B,36. 50A- BACK FLOW MISSING. 50B- NO CHECK VALVE ON FEED WATER LINE. | $200 | $0 | Jun 29, 2012 |
| Aug 2, 2011 | 32071046M | RESOLVE | CLASS - 3 | B354,15,16,32A,36,24B,50A,B. 50A- BOILER ROOM FIRE DOOR DEFECTIVE. 50B- PIPE SAFETY OR RELIEF VALVE DISCHARGE DOWN NO... | $200 | $0 | Jun 29, 2012 |
| Aug 2, 2011 | 32071045K | RESOLVE | CLASS - 1 | B101,50A,B. 50A- WORK W/O A PERMIT. 28-105.1. 50B- NO WORK PERMIT FILED W/DOB FOR THE INSTALLATION OF THE GAS BOILER. | $1,600 | $0 | Jun 29, 2012 |
| Apr 30, 2009 | 34744070Z | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH COMM-ORDER TO OBTAIN A PERMIT PER VIOLATION 34707519R FOR INSTALLING GAS HEATER ETC W/I THE PR... | $1,600 | $0 | Jun 3, 2010 |
| Oct 29, 2008 | 34707519R | RESOLVE | CLASS - 1 | WORK W/O A PERMIT WORK NOTED AT 2ND FL 5 SPTS 3RD FL 5 APTS 4FL 5 APTS INSTALLED GAS HEATER SYSTEMS AT LIVINGROOMS OR... | $1,600 | $0 | Feb 24, 2010 |