1-11 Junius Street, Brooklyn • Block 03679 • Lot 0030
48 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 26, 2026 | 39178402Y | ACTIVE | CLASS - 1 | OBSERVED GAS FUTURES ON ROOF, SPRINKLER HEADS OBSTRUCTED THROUGHOUT BUILDING, WASHER AND DRYERS NOT PIPED IN PROPERLY... | $2,500 | $2,500 | Dec 4, 2026 |
| Feb 25, 2026 | 39178247N | RESOLVE | CLASS - 2 | CLASS 2: CAT1 TEST TAG EXPIRED, PROVIDE A NEW TAG. BRAKE MAINTENANCE TAG EXPIRED, PROVIDE SERVICE AND UPDATE THE TAG.... | $0 | $0 | May 6, 2026 |
| Feb 25, 2026 | 39178246L | RESOLVE | CLASS - 2 | CLASS 2: CAT1 TEST TAG EXPIRED, PROVIDE A NEW TAG. BRAKE MAINTENANCE TAG EXPIRED, PROVIDE SERVICE AND UPDATE THE TAG.... | $0 | $0 | May 6, 2026 |
| Feb 25, 2026 | 39178248P | RESOLVE | CLASS - 2 | CLASS 2: CAT1 TEST TAG EXPIRED, PROVIDE A NEW TAG. BRAKE MAINTENANCE TAG EXPIRED, PROVIDE SERVICE AND UPDATE THE TAG.... | $0 | $0 | May 6, 2026 |
| Nov 3, 2025 | 39165754P | RESOLVE | CLASS - 2 | CLASS 2: CATEGORY 1 TEST TAGS EXPIRED, REMOVE OUTDATED TAGS AND PROVIDE A NEW ONE. BRAKE MAINTENANCE TAG EXPIRED, PRO... | $625 | $0 | Jan 14, 2026 |
| Nov 3, 2025 | 39165753N | RESOLVE | CLASS - 2 | CLASS 2: CATEGORY 1 TEST TAGS EXPIRED, REMOVE OUTDATED TAGS AND PROVIDE A NEW ONE. BRAKE MAINTENANCE TAG EXPIRED, PRO... | $625 | $0 | Jan 14, 2026 |
| Nov 3, 2025 | 39165783Y | RESOLVE | CLASS - 2 | OBSERVED ON ROOF FUTURES ON GAS LINES. IN THE BUILDING EXHAUSTED VENTS TO GAS DRYERS IS BACK PITCHED AND NOT CONNECTE... | $0 | $0 | Aug 10, 2026 |
| Dec 30, 2024 | 39134107R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Sep 8, 2025 |
| Dec 30, 2024 | 39134108Z | RESOLVE | CLASS - 2 | NON SELF CLOSING DOORS. OBSERVED NON SELF CLOSING DOORS AT BASEBMENT AND CELLAR LEVELS IN BOILER AND MACHINAL ROOMS. ... | $0 | $0 | Mar 12, 2025 |
| Nov 2, 2023 | 39098699Y | RESOLVE | CLASS - 2 | EMERGENCY EXIT DOOR DOES NOT FUNCTION CORRECTLY, B SIDE, GROUND LEVEL., REPAIR AND/OR REPLACE | $625 | $0 | Feb 28, 2024 |
| Feb 28, 2023 | 39080449X | RESOLVE | CLASS - 2 | 1 JUNIUS AOSMITH BOILERS=#2 MODULE POOR FLAMEÝSOOT¨/SAFETY DISCHARGE PIPES ON BOILER+HWH+HW STORAGE TANKS INCORRECT/W... | $625 | $0 | Jun 28, 2023 |
| Feb 28, 2023 | 39080448Y | RESOLVE | CLASS - 3 | 1 JUNIUS WEILMCLAIN BOILER=OUTSIDE COMBUSTION AIR INLET 1/2 CLOGGED;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF C... | $500 | $0 | Jun 28, 2023 |
| Feb 28, 2023 | 39080450N | ACTIVE | CLASS - 2 | 25 JUNUIS AOSMITH BOILERS=SAFETY DISCHARGE PIPES INCORRECT/BOTH HOT WATER STORAGE TANKS CORRODED AND LEAKING/COMBUSTI... | $625 | $0 | Jun 28, 2023 |
| Mar 28, 2022 | 35650601H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NO FIRESTOPPING PER BC712.3;27-345.OBSERVED:@CELLAR LEVEL&ROOF LEVEL... | $0 | $0 | Aug 17, 2022 |
| Mar 28, 2022 | 39059025X | RESOLVE | CLASS - 2 | AT THE TIME OF MY INSPECTION IN THE BASEMENT/ CELLAR I DID NOT OBSERVE VENTILATION IN THE ROOM WITH THE 3 GAS FIRED W... | $625 | $0 | Aug 3, 2022 |
| Mar 28, 2022 | 39059036L | RESOLVE | CLASS - 2 | AT THE TIME OF MY INSPECTION IN THE BASEMENT/ CELLAR I DID NOT OBSERVE VENTILATION IN THE BOILER ROOM, VENTILATION WA... | $0 | $0 | Aug 3, 2022 |
| Mar 28, 2022 | 35650602J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NO ARE STOPPING PER BC712.3;27-345.OBSERVED:@CELLAR LEVEL&ROOF LEVEL... | $0 | $0 | Aug 17, 2022 |
| Nov 4, 2021 | 39050564Y | RESOLVE | CLASS - 1 | ELECTRICAL BREAK MONITORING SWITCH NOT WORKING(CU). | $3,125 | $0 | Mar 9, 2022 |
| Nov 4, 2021 | 39050565X | RESOLVE | CLASS - 1 | ELECTRICAL BREAK MONITORING SWITCH NOT WORKING(CU). IN CAR PHONE NOT WORKING(CU). ALARM BELL NO BUZZER(CU). EMERGENCY... | $3,125 | $0 | Mar 9, 2022 |
| Nov 3, 2021 | 35577326Y | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. I OBSERVED THROUGHOUT BLDG RESIDENTIAL GAS FLEX USED ON COMMERCIAL... | $312 | $0 | Apr 6, 2022 |
| Nov 3, 2021 | 35592074M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. I OBSERVED IN REAR BOILER ROOM,NO FRESH AIR VENTILATION FORTHE GAS... | $625 | $0 | May 11, 2022 |
| Oct 1, 2021 | 39066375L | RESOLVE | CLASS - 1 | (2) UNREGISTERED AOS HYDRONIC BOILERS. | $625 | $0 | Feb 10, 2023 |
| Sep 28, 2021 | 39048353L | RESOLVE | CLASS - 1 | EMERGENCY STOP SWITCH NO BUZZER(CU). ALARM BELL NO BUZZER(CU) IN CAR PHONE NOT WORKING(CU). ELECTRICAL BREAK MONITORI... | $3,125 | $0 | Feb 2, 2022 |
| Sep 28, 2021 | 39048352J | RESOLVE | CLASS - 1 | UPON INSPECTION THE DEVICE WAS FOUND OUT OF SERVICE. RESTORE TO SERVICE IMMEDIATELY. YOU CAN CONTACT NYCDOB AT EIR@BU... | $3,125 | $0 | Feb 2, 2022 |
| May 26, 2021 | 35577110P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER BC 712.3;27-345.NOTED:OBSERVED AT STAIR "A... | $0 | $0 | Oct 6, 2021 |
| Feb 27, 2020 | 39018462N | RESOLVE | CLASS - 2 | EMERGENCY LIGHTING ON THE STAIRCASE THRU OUT NOT WORKING, SOME MISSING BULBS AND OTHERS NOT WORKING WHEN TESTED, REPA... | $1,250 | $0 | Jul 1, 2020 |
| Feb 11, 2020 | 37017529L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#38268373R ISSUED ON 03/05/19 & TO FILE A CERT OF CORREC... | $1,250 | $0 | Jul 8, 2020 |
| Jan 14, 2020 | 37017369L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#38267732P ISSUED ON 1/29/19,AND TO FILE A CE... | $1,250 | -$94 | Jun 3, 2020 |
| Jan 14, 2020 | 37017368J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#38267731N ISSUED ON 1/29/19,AND TO FILE A CE... | $1,250 | -$94 | Jun 3, 2020 |
| Mar 5, 2019 | 38268373R | RESOLVE | CLASS - 2 | 1B10,5B10,70O2,78B14. 1B10-EMERGENCY ALARM BELL INSUFFICIENT NEEDS TO BE REPAIRED; 5B10-CAR GATE OFF THE TRACK NEEDS ... | $625 | $0 | Jun 17, 2019 |
| Jan 29, 2019 | 38267732P | RESOLVE | CLASS - 2 | 2X10,59X10,100M3. 2X-REPAIR PHONE SYSTEM IN THE CAR; 59X-REPAIR BRAKEMONITORING; 100M-PROVIDE COVER FOR ELECTRIC EYE ... | $625 | $0 | May 6, 2019 |
| Jan 29, 2019 | 38267731N | RESOLVE | CLASS - 2 | 2X10,42Q3,59X10,71X10. 2X REPAIR PHONE SYSTEM IN THE CAR; 42Q-INSTALLGROUND ON REGISTERS ON THE SIDE OF THE CONTROLLE... | $625 | -$25 | May 6, 2019 |
| Dec 13, 2018 | 38266892J | RESOLVE | CLASS - 1 | (97,X,10)UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE.RESTORE TO SERVICE IMMEDIATELY AND CONTACT DOB NYC.THAT THE ... | $1,250 | $0 | Mar 20, 2019 |
| Dec 13, 2018 | 38266891H | RESOLVE | CLASS - 1 | 97-X-10=UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE.RESTORE TO SERVICE IMMEDISTELY AND CONTACT DOB NYC .TAHT THE ... | $1,250 | $0 | Mar 18, 2019 |
| Dec 5, 2017 | 38259141N | RESOLVE | CLASS - 1 | CEASE USE. 21L10,12R9,39Q3,71X10. (21L)B1 HOISTWAY DOOR INTERLOCK IS GETTING STUCK (ELECTRICAL CONTACT) IN CLOSED POS... | $1,000 | $0 | Apr 16, 2018 |
| Jul 24, 2017 | 35286756Y | RESOLVE | CLASS - 1 | SEC. 403.8 MISC VIOLATIONS: UNPAINTED GAS PIPING NOT PROTECTED FROM THE ELEMENTS. OBSERVED ON LOWER ROOF UNPAINTED GA... | $800 | $0 | Sep 25, 2017 |
| Jul 24, 2017 | 35286710Z | RESOLVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,DEVICES,MATERIALS,APPLIANCES OR WIRING IN USE.OBSERVED ON... | $8,000 | $0 | Sep 11, 2017 |
| Jul 24, 2017 | 35272109K | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTED: @ 1ST STORY 'A' BLDG, EXIT DOOR LEADING TO JUNIUS STREET NOT SELF CLOSING. REM: RE... | $250 | $0 | Sep 22, 2017 |
| Feb 17, 2017 | 35229110Y | RESOLVE | CLASS - 1 | SEC: FGC-408.2, E.3.1. MISCELLANEOUS VIOLATIONS: FUTURES EXIST ON GAS PIPING & EXCESSIVE STORAGE IN GAS METER ROOM. @... | $8,000 | $0 | Apr 17, 2017 |
| Feb 10, 2017 | 35229191P | RESOLVE | CLASS - 1 | FGC401.1. MISC. VIO. GAS PIPING NOT LABELED. OBSERVED ON 2/10/17 GAS PIPING IN WATER METER ROOM NOT LABELED. PHOTOS T... | $800 | $0 | Jul 19, 2017 |
| Feb 10, 2017 | 35229189X | RESOLVE | CLASS - 1 | FGC408.2. MISC. VIO. DRIPS. FUTURE CONNECTIONS EXIST DOWN STREAM OF APPLIANCE. OBSERVED ON 2/10/17 FUTURE GAS CONNECT... | $4,000 | $0 | Mar 27, 2017 |
| Feb 10, 2017 | 35229190N | RESOLVE | CLASS - 1 | FGC411.1. MISC. VIO. RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENTOBSERVED ON 2/10/17. RESIDENTIAL GAS FLEX USED ... | $800 | $0 | Aug 2, 2017 |
| Jul 27, 2016 | 35187130Z | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35171218R ISSUED ON 02/24/16 & TO FILE A C OF C PURSUANT TO 28... | $0 | $0 | Aug 17, 2016 |
| Apr 9, 2016 | 35184740M | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35171218R ISSUED ON 2/24/16 & TO FILE A C OF C PURSUANT TO 28-... | $0 | $0 | Jul 20, 2016 |
| Feb 26, 2016 | 35171218R | RESOLVE | CLASS - 1 | WORK W/O PERMIT.NOTE:INSTALLED GAS WASHER AND DRYER LAUNDRY ROOMS ON EVERY FLOOR FROM 1 - 6.CERT OF OCCUPANCY #301356... | $0 | $0 | Jul 20, 2016 |
| Jan 20, 2016 | 38240156X | RESOLVE | CLASS - 2 | 97X10,100R07. 97X-RESTORE TO SERVICE FOR PROPER DOB INSPECTIONS; 10R- PROVIDE ACCIDENT REPORT TO DOB FOR INVESTIGATIO... | $500 | $0 | Jul 11, 2016 |
| Jun 16, 2015 | 38236782L | RESOLVE | CLASS - 2 | 56Y13,69B07,42G11,69B11,12Q03,05M07,70O02,10M07,17M11,17D06,16T07,16B11,70O02,71X10,77X10,10H11. 56Y-SEAL LEAK; 69B-W... | $500 | $0 | Oct 26, 2015 |
| Jun 16, 2015 | 38236780H | RESOLVE | CLASS - 2 | 12Q03,12X10,12M07,16B11,17H11,17D06,10H11,10M07,61R11,42G11,69B11,68B07,60X10,56Y13,40I10,03I10,70X02,71X10. 16B-PROV... | $500 | $0 | Oct 26, 2015 |