ECB violations
Hickman Park, Brooklyn • Block 03768 • Lot 0001
51 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 24, 2026 | 35722548H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.PROVIDE REQUIREDCORRIDOR WIDTH PER BC 1008.1;27-371(J).SECURITY... | $625 | $0 | Apr 27, 2026 |
| Jul 11, 2025 | 35720940N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT EXIT 5, ONE SMOKE DOOR DO NOT CLOSE PROPERLY. REMEDY... | $1,250 | $0 | Aug 15, 2025 |
| Mar 30, 2021 | 35546512X | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTED: AT STAIR BY 426,STAIR D BY 400,SMOKE AT EXIT 5 BY 125,AUDITORIUM LEFT STAGE,& RIGH... | $625 | $0 | Aug 25, 2021 |
| Mar 30, 2021 | 35546514J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN COMPLIANT MANNER ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006.1;... | $625 | $0 | Aug 25, 2021 |
| Mar 30, 2021 | 35546511Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT ROOMS 409406,205 & 106 ARE NOT WORKING PROPERLY.(THE DOO... | $625 | $0 | Aug 25, 2021 |
| Mar 30, 2021 | 35546513H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NO FIRE STOPPING PERBC 712.3;27-345. NOTED: AT THE CELLAR LEVEL ELE... | $1,250 | $0 | Aug 25, 2021 |
| Mar 23, 2020 | 35486680N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 10... | $625 | $0 | Sep 9, 2020 |
| Mar 23, 2020 | 35486679X | RESOLVE | CLASS - 2 | SEC. 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),FGC APPENDIX E(E4)(2014 CODE)AT ... | $1,250 | $0 | Sep 9, 2020 |
| Mar 23, 2020 | 35486681P | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING PROPERLY,AT 4TH FL & 3RD FL AT STAIR"BZ7E"EACH FLOOR 1 DOOR & 4RH FL AT STAIR"A"1 DOOR NOT... | $625 | $0 | Sep 9, 2020 |
| Jan 22, 2018 | 35297717P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. AT 1ST FLOOR VESTIBULE OF EXIT 5, DOOR SADDLE AND CONCRETE FLOOR B... | $0 | $0 | Apr 23, 2018 |
| Jan 22, 2018 | 35297716N | RESOLVE | CLASS - 2 | REISSUE: #35177326L GLASS BLOCKS AT STAIRWAY B BETWEEN 1ST AND 2ND FLOOR ARE CRACKED. RMDY: COMPLY WITH SUMMONS. | $0 | $0 | Apr 23, 2018 |
| Mar 18, 2016 | 35177326L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE: AT TIME OF INSPECTION NEAR STAIRWAY B AT 1ND FLOOR EXTERIOR ... | $0 | $0 | Jun 13, 2016 |
| Mar 17, 2016 | 35177325J | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNERNTO PROVIDE 1/4"THICKWIRED GLASS VISION PANEL WHERE REQUIRED AS PER ... | $0 | $0 | Jun 13, 2016 |
| Sep 5, 2015 | 35146662Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. FAILURE TO PROVIDE WIRED GLASS VISION PANELS PER 27-3716 AT THE FO... | $0 | $0 | Oct 26, 2015 |
| Jun 5, 2015 | 35129081X | RESOLVE | CLASS - 2 | 27-371.RE-ISSUE 35102076L THE FOLLOWING DOOR HAVE PLEXIGLASS OR ARE MISSING REQUIRED GLASS PANELS:ROOMS 108,105,106,1... | $0 | $0 | Aug 3, 2015 |
| Jul 22, 2014 | 35102078P | RESOLVE | CLASS - 2 | RE-ISSUE 35016947R.EXIT DOORS NOT SELF CLOSING.THE FOLLOWING DOOR ARE RACKED OR DO NOT CLOSE PROPERLY:STAIR DOOR"D" @... | $0 | $0 | Sep 29, 2014 |
| Jul 22, 2014 | 35102077N | RESOLVE | CLASS - 2 | RE-ISSUE 35016948Z.GROUT MISSING IN TILE WALL OF STAIR D 1ST FL LEVEL.REM:MAKE REPAIRS. | $0 | $0 | Sep 29, 2014 |
| Jul 22, 2014 | 35102076L | RESOLVE | CLASS - 2 | 27-371(B),RE-ISSUE:35016949K VISION PANELS.EXTENSIVE USE OF PLEXIGLASSVISION PANELS THROUGHOUT ALL FLS.PLEXIGLASS & T... | $0 | $0 | Sep 29, 2014 |
| Jul 22, 2014 | 35102080Y | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE PROPER CORRIDOR WIDTH & UNOBSTRUCTED EXIT PASSAGEWAY.@ KINDERGARTEN ROOMS 11 & 113 & 105 & 107 EXI... | $0 | $0 | Sep 29, 2014 |
| Jul 22, 2014 | 35102079R | RESOLVE | CLASS - 2 | USE OF PROHIBITED DOOR HARDWARE.@ 1ST FL EXIT DOORS:PINS USED TO LOCK DOORS.HOLES DRILLED THORUGH FRAME & ADJACENT DO... | $0 | $0 | Sep 29, 2014 |
| Apr 30, 2013 | 35016949K | RESOLVE | CLASS - 2 | 27-371(B) PLEXI VISSION PANELS INSTALLED ON DOROS TO ROOMS 103,104,106,105,108,202,204,203,205,207,208,209,211,214,21... | $0 | $0 | Jun 17, 2013 |
| Apr 30, 2013 | 35016947R | RESOLVE | CLASS - 2 | REISSUE 34933310L CORRIDOR DOOR AT 3RD FLR ADJACENT TO ROOM 306 IS RACKED AND SEPARATING FROM HINGE. CORRIDOR DOORS A... | $0 | $0 | Jun 17, 2013 |
| Apr 30, 2013 | 35016948Z | RESOLVE | CLASS - 2 | REISSUE 34933311N CRACKS IN TILE WALL OF STAIR D @FIRST FLOOR LEVEL. REMEDY: MAKE NECESSARY REPAIRS. | $0 | $0 | Jun 17, 2013 |
| Feb 10, 2012 | 34933312P | RESOLVE | CLASS - 2 | REISSUE: 34895356M. EXCESSIVE AMOUNT OF COMBUSTIBLE MATERIAL IS BEING HUNG ON WALLS AND LIGHTING FIXTURES LOCATED ON ... | $0 | $0 | May 21, 2012 |
| Feb 10, 2012 | 34933311N | RESOLVE | CLASS - 2 | THE GLAZED WALL TILES HAS SEPARATED BETWEEN THE MORTAR CREATING A 1" WIDE CRACK. LOCATED AT THE 1ST FLR LEVEL AT STAI... | $0 | $0 | May 21, 2012 |
| Feb 10, 2012 | 34933310L | RESOLVE | CLASS - 2 | THE CORRIDOR SMOKE DOOR IS DRAGGING ON THE FLR CAUSING DOORS NOT TO BESELF-CLOSING LOCATED ON EVERY FLR LEVEL. REMEDY... | $0 | $0 | May 21, 2012 |
| Mar 1, 2011 | 34900525H | RESOLVE | CLASS - 2 | AT 1ST FLR AUDITORIUM, GYMNASIUM & CAFETERIA. EMERGENCY LIGHTING IS DEFECTIVE, BROKEN THROUGHOUT. REMEDY: REPAIR/REPL... | $0 | $0 | May 2, 2011 |
| Mar 1, 2011 | 34900526J | RESOLVE | CLASS - 2 | AT 1ST FLR CORRIDOR CEILING BY RM 122 & 123 TILES ARE LOOSE, BROKEN ASWELL AS SUB CEILING PLYWOOD DETERIORATING, LOOS... | $0 | $0 | May 2, 2011 |
| Mar 1, 2011 | 34895356M | RESOLVE | CLASS - 2 | EXCESSIVE COMBUSTIBLE MATERIAL THROUGHOUT ENTIRE BLDG CORRIDOR & CLASSROOM WALLS & LIGHTING. CONSISTING OF ART WORK, ... | $0 | $0 | May 2, 2011 |
| Apr 14, 2009 | 34770794N | RESOLVE | CLASS - 2 | 1ST FLR ROOF LEVEL HAS BECOME POROUS & ALLOWING RAIN WATER INTO BUILDING CORRIDOR BY EXIT "E". REMEDY: WATER PROOF EX... | $0 | $0 | Jul 6, 2009 |
| May 28, 2008 | 34646026M | RESOLVE | Non-Hazardous | 27-127 VERTICAL CRACK IN LUNCHROOM APPROX 12' LONG IN BLOCK WALL ON BOTH SIDES REM: REPAIR CRACK | $0 | $0 | Jul 21, 2008 |
| May 28, 2008 | 34646025K | RESOLVE | Non-Hazardous | 27-127 VERTIVAL CRACK ON EXTERIOR BRICK NEXT TO WINDOW @ BLAKE AV CRACK APPROX ENTIRE LENGTH REM: (REPAIR)/REPLACE BRICK | $0 | $0 | Jul 21, 2008 |
| Mar 10, 2006 | 34513186M | RESOLVE | Hazardous | REISSUE: 34474407H. WATER PENETRATION THROUGH INTERIOR WALLS AT 1ST FLOOR GYM OFFICE AND EQUIPMENT STORAGE ROOMS, ROO... | $0 | $0 | May 1, 2006 |
| Mar 10, 2006 | 34513187Y | RESOLVE | Hazardous | REISSUE: 34474408J DEFECTIVE//SPALLING PLASTER, CERAMIC TILE WALLS IN ROOMS 130,132, GYM OFFICE, STORAGE ROOM. REMEDY... | $0 | $0 | May 1, 2006 |
| Mar 10, 2006 | 34513184Z | RESOLVE | Hazardous | MISSING STAIR RAILINGS AT STAIR B (EXIT 3) 3RD FLOOR. REMEDY: REPLACE/REPAIR RAILINGS. | $0 | $0 | May 1, 2006 |
| Mar 10, 2006 | 34513185K | RESOLVE | Hazardous | 1) DEFECTIVE HINGE ROD AT CORRIDOR DOOR ADJACENT TO ROOM 206,413 CAUSING DOOR TO RACK 2) MISSING CORRIDOR DOOR ADJACE... | $0 | $0 | May 1, 2006 |
| Mar 23, 2005 | 34474407H | RESOLVE | Non-Hazardous | WATER PENETRATION THROUGH WALLS (INTERIOR) AT 1ST FLOOR GYM OFFICE AND EQUIPMENT STORAGE ROOM AND RM #130 & 132.REMED... | $0 | $0 | Aug 1, 2005 |
| Mar 23, 2005 | 34474408J | RESOLVE | Non-Hazardous | PLASTER SPALLING FROM WALLS IN ROOM #130 & 132 AND PLASTER CEILING IN GYM OFFICE BATHROOM IS MISSING AND CRACKED AND ... | $0 | $0 | Aug 1, 2005 |
| May 28, 2004 | 34436877P | RESOLVE | Non-Hazardous | "REISSUE" (34391262M) FAILURE TO MAINTAIN.DEFECTS ARE FIRST FLOOR CORRIDOR 12"X12" CEILING TILES ARE MISSING AND LOOS... | $0 | $0 | Aug 2, 2004 |
| Jan 16, 2004 | 34421063Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BLDG-DEFECT IS:CRACKS AT CAFETERIA AND GYM WALLS REMEDY:MAINTAIN BLDG MAKE ALL NECESSARY REPAIR A... | $0 | $0 | Mar 15, 2004 |
| Jan 16, 2004 | 34421062M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN.DEFECTS ARE WINDOWS DEFECTIVE THROUGHOUT SCHOOL INOPERABLE SHSHES AIR AND WATER INFILRATION PAINT... | $0 | $0 | Mar 15, 2004 |
| Mar 10, 2003 | 34391262M | RESOLVE | Hazardous | FAILURE TO MAINTAIN. DEFECTS ARE FIRST FLOOR CORRIDOR 12"X12" CEILING TILIES ARE MISSING, LOOSE AND BULDING AT VARIOU... | $0 | $0 | Jun 9, 2003 |
| Mar 10, 2003 | 34391261K | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. DEFECT IS 4TH FLOOR BOYS BATHROOM PARTITIONS LOOSE AND SAGGING. REPAIR BATHROOM PARTITONS. | $0 | $0 | Jun 9, 2003 |
| Mar 10, 2003 | 34391263Y | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT. NOTE CONCRETE YARD APPROX 38'X155' (5,890SF) BETWEEN AUDITORIUM AND KINDERGARTEN CLASS ROOMS I... | $0 | $0 | Jun 9, 2003 |
| Jan 25, 2002 | 34312658K | RESOLVE | Non-Hazardous | FAILURE TO MAINTIAN BUILDING. NOTED DEFECTS. HOLE IN FENCE BETWEEN SCHOOL + PLAYYARD WROUGHT IRON GATES HAS BROKEN HI... | $0 | $0 | Mar 25, 2002 |
| May 10, 2001 | 34295005L | RESOLVE | Hazardous | FAILURE TO MAINTAIN. DEFECT IS; LONG VERTICAL CRACKS AT WALLS, BELOW STEEL GIRDERS GYMNASIUM AND CAFETERIA WALLS FOUN... | $0 | $0 | Nov 5, 2001 |
| May 10, 2001 | 34295004J | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. DEFECT IS: AT INNER COUTYARD ACCUMULATION OF WATER NO DRAINS PROVIDED. WATER PENETRATED INTO ARE... | $0 | $0 | Nov 5, 2001 |
| Mar 19, 2001 | 34280000K | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE EMERGENCY LIGHT FIXTURE WITHIN CORRIDOR & VESTIBULE ADJOINING AUDITORIUM,GYM & LUNCHROOM ALSO CORR... | $0 | $0 | May 7, 2001 |
| May 11, 2000 | 34241249Y | RESOLVE | Non-Hazardous | FAILURE TO MIANTAIN DEFECTS ARE:WINDOWS DEFECTIVE THROUGHOUT SCHOOL-INOPERABLE SASHES,AIR AND WATER INFILTRTION,PAINT... | $0 | $0 | Jul 31, 2000 |
| May 25, 1999 | 34212495R | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING. DEFECT IS CONCRETE PAVEMENT BROKEN SINKING CREATING TWO INCH CRACK ON WILLIAMS STREET E... | $0 | $0 | Aug 30, 1999 |