ECB violations
526-534 Pennsylvania Avenue, Brooklyn • Block 03822 • Lot 0031
41 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 23, 2026 | 39185840J | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN MAIN LOBBY OF BUILDING ONE HUNG ELECTRICAL HEATER INSTALLED WITH DISCON... | $1,250 | $0 | Jul 1, 2026 |
| Nov 25, 2025 | 39168317K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT. OF BUILDINGS FOR V... | $1,250 | $1,250 | Aug 17, 2026 |
| Apr 4, 2024 | 39110797R | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS STATED IN ECB #39068965K STILL IN EFFECT AT THE TIME OF MY INSPECTION. THE UNPERM... | $1,250 | $0 | Feb 24, 2025 |
| Apr 4, 2024 | 39110798Z | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDER AS STATED IN ECB # 39068965K AND THE VIOLATING CONDITIONS ... | $1,250 | $0 | Feb 24, 2025 |
| Apr 4, 2024 | 39110799K | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONERS ORDER AS STATED IN ECB #39068963R AND CORRECT THE BONDING OF THE ... | $1,250 | $0 | Feb 24, 2025 |
| Apr 4, 2024 | 39110800Z | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT ELECTRICAL ROOM THE SERVICE SWITCH BONDED BEYOND THE LOAD SIDE. THE BONDING OF THE SERVICE... | $3,750 | $0 | Feb 24, 2025 |
| Aug 29, 2022 | 39068965K | RESOLVE | CLASS - 2 | I OBSERVED IN THE PASSAGEWAY AT EXPOSURE #4 THE USE OF EMT CONDUIT OUTDOORS. THIS HAS LEAD TO THE CORROSION OF THE CO... | $1,250 | $1,250 | Jan 4, 2023 |
| Aug 29, 2022 | 39068962P | RESOLVE | CLASS - 2 | I OBSERVED ON THE SECOND FLOOR LANDING A LIGHT FIXTURE NOT SECURED PROPERLY WITH EXPOSED AND ENERGIZED WIRES. PHOTOS ... | $0 | $0 | Jan 4, 2023 |
| Aug 29, 2022 | 39068966M | RESOLVE | CLASS - 1 | AT CELLAR LEVEL, BACK SIDE, ELECTRICAL RM/ STORAGE ROOM, SECOND EGRESS/EXIT DOOR WAS REMOVED AND BLOCKED WITH CONCRET... | $6,250 | $6,250 | Jan 4, 2023 |
| Aug 29, 2022 | 39068955R | RESOLVE | CLASS - 2 | REAR ACCESS DOOR OF BOILER MISSING BOLTS AND CLAMPS. CORRECT VIOLATING CONDITION & SUBMIT A CERTIFICATE OF CORRECTION. | $0 | $0 | Jan 4, 2023 |
| Aug 29, 2022 | 39068963R | RESOLVE | CLASS - 2 | I OBSERVED IN THE ELECTRICAL EQUIPMENT ROOM THE IMPROPER BONDING OF THE LOAD SIDE OF THE MAIN ELECTRICAL SERVICE SWIT... | $3,750 | $3,650 | Jan 4, 2023 |
| Dec 22, 2020 | 39033812J | RESOLVE | CLASS - 2 | MANUAL RESET LOW WATER CUT NEEDED. C.O. DETECTOR INTERLOCK WITH BOILER | $625 | $0 | Apr 28, 2021 |
| Feb 6, 2019 | 32093182Y | RESOLVE | CLASS - 2 | B254,36, FOUND FEDERAL MODEL #FST-50 2100000 BTU'S STEAM BOILER; 26-NOT REGISTERED. REGISTER BOILER AND CORRECT ALL V... | $0 | $0 | Jun 3, 2019 |
| Dec 7, 2018 | 35392368L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35361481L ISSUED ON 9/25/18 AND TO FILE ... | $0 | $0 | Mar 11, 2019 |
| Sep 25, 2018 | 35389187P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35321981L ISSUED ON 03-05-18 & TO FILE A C OF C PURSUAN... | $3,125 | $0 | Mar 11, 2019 |
| Sep 25, 2018 | 35361481L | RESOLVE | CLASS - 1 | FILED A CERT OF CORRECTION OR OTHER RELATED MATERIALS CONTAINING MATERIAL FALSE STATEMENTS. REMEDY: CORRECT CONDITION... | $0 | $0 | Feb 4, 2019 |
| Sep 25, 2018 | 35361480J | RESOLVE | CLASS - 2 | SEC. 110.2A MISC VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARS: OBSERVED IN BOILER RM & GAS ROOM/METER ROOM,MC ... | $4,000 | $0 | Feb 4, 2019 |
| Aug 2, 2018 | 35347377K | RESOLVE | CLASS - 2 | EC590.4.TEMPORARY LIGHTS AND RECEPTACLES ON SAME CIRCUIT.OBSERVED IN WATER METER ROOM LOCATED IN THE CELLAR.TEMPORARY... | $830 | $0 | Oct 29, 2018 |
| Apr 2, 2018 | 32096405X | RESOLVE | CLASS - 2 | 4A,36,50. FOUND FEDERAL BOILER MODEL FST50 2,100,000 BTU'S UNREGISTERED AND OPERATING WITH VIOLATING CONDITIONS; 4A-M... | $625 | $0 | Jun 4, 2018 |
| Mar 5, 2018 | 35321982N | RESOLVE | CLASS - 2 | UNAPPROVED, UNSAFE, UNSUITABLE ELECTRICAL EQUIPMENT, MATERIALS DEVICE, APPARATUS, APPLIANCE OR WIRING IN USE. OBSERVE... | $800 | $0 | Oct 3, 2018 |
| Mar 5, 2018 | 35317565K | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPARTMENT RECORDS. NOTED: OBSERVED 1S... | $1,200 | $0 | Apr 30, 2018 |
| Mar 5, 2018 | 35321981L | RESOLVE | CLASS - 2 | EC 320.30 ARMORED CABLES ARE NOT PROPERLY SECURED. OBSERVED IN BOILER ROOM AND GAS METER ROOM, MC CABLES ARE NOT SECU... | $800 | $0 | Oct 3, 2018 |
| Mar 5, 2018 | 35321983P | RESOLVE | CLASS - 2 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN BASEMENT AREA INSTALLATION OF POWER FOR DATA EQUIPMENT AND INSTALLATION... | $2,000 | $0 | Apr 30, 2018 |
| Nov 1, 2017 | 35279154L | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35286947R ISSUED ON 07/25/17 & TO FILE A C OF C PURSUAN... | $0 | $0 | Dec 12, 2017 |
| Jul 25, 2017 | 35286949K | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED (PLUMBING) SYSTEM TESTED,INSTALL 3/4 & 1/2 GAVE LINE FOR BOILER PILOT LINE & UTILITY S... | $1,000 | $0 | Sep 15, 2017 |
| Jul 25, 2017 | 35286948Z | RESOLVE | CLASS - 1 | FGC 408.2 MISC VIO-OBSERVED FUTURE TEE'S THRU OUT BSMT ON HOUSE GAS LINES,TEES'S & PLUGS INSTALLED REQ'S NIPPLE & CAP... | $800 | $0 | Sep 15, 2017 |
| Jul 25, 2017 | 35287025P | RESOLVE | CLASS - 1 | FGC 406.6.2.1 MISC VIO-OBSERVED GAS LINE INSTALLED FOR BOILER(PILOT)LINE IN BSMT,NO CERTIFIED/UNAUTHORIZED FOR USE-BY... | $1,600 | $0 | Sep 11, 2017 |
| Jul 25, 2017 | 35272557Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 27-345: @ CELLAR LEVE, FIRE STOP MIS... | $500 | $0 | Sep 15, 2017 |
| Jul 25, 2017 | 35286947R | RESOLVE | CLASS - 1 | WORK NO PERMIT.INSTALL GAS LINE 1/2 & 3/4 FOR BOILER PILOT LINE,WITH GAS (IMONS) IN BSMT NO PERMIT FOR THIS INSTALLAT... | $0 | $0 | Nov 21, 2017 |
| Feb 13, 2017 | 35229195M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLG IN CODE-COMPLIANT MANNER. OBSERVED ON 02/13/17IN BASEMENT RUSTED GAS PIPES IN GAS METER ROOM ... | $500 | $0 | Apr 12, 2017 |
| Oct 6, 2016 | 35214307X | RESOLVE | CLASS - 1 | 408.2 FUTURE CONNECTIONS EXIST ON GAS PIPING DOWN STREAM OF APPLIANCES.@THE TIME OF MY INSPECTION 2PM ON 10/6/16 @THE... | $800 | $0 | Mar 22, 2017 |
| Oct 6, 2016 | 35214309J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER:LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS OR ALTERNATIVE HAND WIRED ... | $0 | $0 | Mar 22, 2017 |
| Oct 6, 2016 | 35214306Y | RESOLVE | CLASS - 1 | 401.5 GAS PIPING NOT LABELLED.@THE TIME OF MY INSPECTION 2PM ON 10/6/16 @THE ABOVE PLACE OF OCCURENCE ADDRESS I OBSER... | $0 | $0 | Mar 22, 2017 |
| Mar 1, 2012 | 34941154Z | RESOLVE | CLASS - 2 | WORK W/O A PERMIT - BASEMENT INSTALL BEAMS IN THE CEILING ABOVE APTS -FLOOR OF APT 1D FIVE 2"X 10" FLOOR OF APT 1F FO... | $0 | $0 | May 14, 2012 |
| Mar 1, 2012 | 34941155K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER-ROOF CRACKED/BROKEN CHIMNEYS. ROOF-CAMEL BACKS MISSING &/OR BRO... | $0 | $0 | May 16, 2012 |
| Mar 1, 2012 | 34941156M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER. 1-WIRING NOT SECURED AT ROOF. 2-HANGING WIRING IN PUBLIC CORRI... | $0 | $0 | May 16, 2012 |
| Mar 1, 2012 | 34941157Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION SECTION. 1-GAS METER ROOM - BLUE PLASTIC BAGS. 2-BOILER ROOM BL... | $0 | $0 | May 16, 2012 |
| Sep 20, 2008 | 32060786Y | RESOLVE | CLASS - 3 | B354,40,50A,B,C,D,E.50A-HOLES IN BOILER ROOM WALLS.50B-PEEP HOLES GLASS BROKEN.50C-FLUE PIPE NOT PROPERLY SEALED TO C... | $200 | $0 | Oct 29, 2009 |
| Dec 6, 2007 | 34612169Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BLDG AT TIME OF INSPECT.NOTED:MAIN STAIRWAY 1 STEPON THIRD FL MISSNG REST OF THE PANELS SHEIRING ... | $2,500 | $0 | Jan 28, 2008 |
| Jan 31, 1995 | 34122307L | RESOLVE | Non-Hazardous | ALTERED BUILDING WITHOUT A VALID CERTIFICATE OF OCCUPANCY: ALT#2028/1987. REMEDY: OBTAIN A VALID CERTIFICATE OF OCCUP... | $0 | $0 | Apr 24, 1995 |
| Jan 25, 1989 | 34017847H | RESOLVE | Non-Hazardous | ALTERED BUILDING OCCUPIED WITHOUT A VALID C OF O. REMEDY: OBTAIN A VALID C OF O. | $250 | $0 | Mar 13, 1989 |