Issued Violation Status Severity Description Penalty Balance due Hearing
Jun 5, 2020 39023520Z RESOLVE CLASS - 2 NATCO BOILER; THERE IS STORAGE AT THE GAS METERS; CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION $1,562 $0 Oct 7, 2020
Jun 5, 2020 39023521K RESOLVE CLASS - 2 PEERLESS BOILER; THE AUTOMATIC FLUE DAMPER IS DEFECTIVE-THE CHIMNEY BASE DOOR HAS BEEN BRICKED UP-THE HIGH LIMIT AQUA... $1,562 $0 Oct 7, 2020
Jun 5, 2020 39023522M RESOLVE CLASS - 2 WEILMCLAIN BOILER HEATING SECOND APT; THE LWCO IS NOT INSTALLED IN THE HEAT SUPPLY PIPE AS CLOSE AS PRACTICAL TO THE ... $1,562 $0 Oct 7, 2020
Jun 5, 2020 39023523Y RESOLVE CLASS - 2 WEILMCLAIN BOILER HEATING FIRST APT; SWITCH COVER IS MISSING-HIGH LIMIT AQUASTAT IS NOT INSTALLED IN HEAT SUPPLY PIPE... $1,562 $0 Oct 7, 2020
Sep 27, 2004 32045539L RESOLVE Hazardous 4A/50/19B 50-FEEDWATER PRESSURE LINE DOES NOT ENTER INTO THE PIPING SYSTEM $400 $0 Nov 15, 2004
Sep 27, 2004 32045540Z RESOLVE Hazardous 4A/50/19B/ 50-FEEDWATER PRESSURE LINE ENTERS INTO THE CAST IRON BOILERNOT THE PIPING SYSTEM 4A-HAZARDOUS $400 $0 Nov 15, 2004