Skip to content

ECB violations

1026-1036 Sheffield Avenue, Brooklyn • Block 04411 • Lot 0024

43 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jun 9, 2026 39191850Y ACTIVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT. OF BUILDINGS FOR V... $1,250 $1,250 Aug 19, 2026
Jun 9, 2026 39191851X RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION FOR VIOLATION #39185426Y, FILE A ... $1,250 $1,250 Aug 19, 2026
Apr 21, 2026 39185425M ACTIVE CLASS - 1 ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE MAIN ELECTRIC RM ONE NEW PANEL INSTALLED WITH NEW CONDUITS ALSO NEW... $2,530 $0 Jul 1, 2026
Feb 17, 2026 39177506Y RESOLVE CLASS - 1 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO OBTAIN WORK PERMITS FOR VIOLATION #39132555L. NO PERMIT ON FILE TO... $2,500 $0 May 6, 2026
Feb 17, 2026 39177507X RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT. OF BUILDINGS FOR V... $3,125 $3,125 May 6, 2026
Dec 10, 2024 39132557P RESOLVE CLASS - 1 OBSERVED GAS LEAK ON THE 1 INCH ELBOW TO THE WATER HEATER LOCATED ON THE MAIN FLOOR. AS PER 102.3 OF THE PLUMBING COD... $1,250 $0 Jan 15, 2026
Dec 10, 2024 39132560X RESOLVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS AT ALL UTILITY/ MECHANICAL ROOMS LOCATED ON THROUGHOUT FI... $0 $0 Feb 19, 2025
Dec 10, 2024 39132556N RESOLVE CLASS - 2 OBSERVED PEX PIPING ( RED & BLUE) INSTALLED TO SLOP SINK. PEX PIPING IS NOT ALLOWED FOR DOMESTIC USE. PEX CAN ONLY BE... $3,125 -$3,125 Feb 19, 2025
Dec 10, 2024 39132555L RESOLVE CLASS - 1 WORK WITHOUT A PERMIT. OBSERVED NEW GAS PIPING TO 2 GAS FIRED WATER HEATERS AND ALSO TO COMMERCIAL LAUNDRY EQUIPMENT ... $2,500 $0 Jan 15, 2026
Dec 10, 2024 39132561H RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $2,500 $0 Jan 15, 2026
Dec 10, 2024 39132559Z RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED WALL AT EXPOSURE 1 INSIDE THE PARKING LOT AREA. WALL ... $1,250 $0 Jan 15, 2026
Dec 9, 2024 39132368X RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 2 ITEMS: 1) EXCESSIVE OIL IN THE PIT, SEAL THE OIL LEAK ... $0 $0 Feb 12, 2025
Jun 17, 2024 39117126H RESOLVE CLASS - 1 I OBSERVED IN THE FOURTH FLOOR KITCHEN THE INSTALLATION OF AN OUTLET, JUNCTION BOX AND EMT RACEWAY IN THE HALLWAY FRO... $4,000 $0 Jan 9, 2025
Jun 17, 2024 39117124Y RESOLVE CLASS - 1 I NOTED IN DOB RECORDS THE FAILURE TO OBTAIN A PERMIT FOR VIOLATIONS STATED IN ECB# 39099397N AS PURSUANT TO 28-201.1... $6,280 $0 Aug 21, 2024
Jun 17, 2024 39117125X RESOLVE CLASS - 1 I OBSERVED THE COMPLETION OF THE BRANCH CIRCUIT WIRING FROM THE GROUND FLOOR ELECTRICAL ROOM TO THE 4TH KITCHEN TO SU... $5,000 $0 Jan 9, 2025
Nov 15, 2023 39099394H RESOLVE CLASS - 1 I OBSERVED IN THE FRONT ENTRANCE THE INSTALLATION AND SECURED EXTENSION CORD PASSING THROUGH THE DROP CEILING TO SUPP... $1,600 $0 Jan 24, 2024
Nov 14, 2023 39099397N RESOLVE CLASS - 1 I OBSERVED THE INSTALLATION ON BRANCH CIRCUIT WIRING FROM THE GARAGE AREA TO THE THIRD FLOOR PASSAGEWAY EN-ROUTE TO T... $800 $0 Jan 24, 2024
Nov 14, 2023 39099396L RESOLVE CLASS - 1 I OBSERVED RAVINDER SINGH A MAINTENANCE WORKER IN THE MIDST OF INSTALLING BX CABLING FROM THE GARAGE AREA TO THE FOUR... $4,800 $0 Jan 24, 2024
Nov 14, 2023 39099395J RESOLVE CLASS - 1 I OBSERVED MR. RAVINDER SINGH IN THE PROCESS OF INSTALLING BX CABLING FROM THE THE GARAGE AREA TO THE 4TH FLOOR KITCH... $4,800 $0 Jan 24, 2024
Oct 16, 2023 39097125K RESOLVE CLASS - 2 ILLEGAL HARDWARE, (SLIDING LOCK LATCHES) INSTALLED ON EXIT DOORS THROUGHOUT BUILDING., PROVIDE LEGAL HARDWARE $0 $0 Dec 20, 2023
Oct 16, 2023 39097124Z RESOLVE CLASS - 2 EXCESSIVE FOAM IN SPRINKLER ROOM GROUND LEVEL., REPAIR AND/OR REPLACE $0 $0 Dec 20, 2023
Oct 16, 2023 39097126M RESOLVE CLASS - 2 OBSERVED IN THE LAUNDRY AREA LOCATED ON GROUND FLOOR GAS PIPING NOT BEING SUPPORTED PROPERLY. THE GAS PIPING WAS BEIN... $0 $0 Dec 20, 2023
Oct 16, 2023 39097123R RESOLVE CLASS - 2 HOLE PENETRATION FOUND IN ELEVATOR AND BOILER MECHANICAL ROOMS, GROUND LEVEL., MAINTAIN EXTERIOR BUILDING WALL $0 $0 Dec 20, 2023
Jan 24, 2023 39078301R RESOLVE CLASS - 2 I OBSERVED IN THE LAUNDRY/ BOILER ROOM FAILURE TO MAINTAIN ACCESS / WORKSPACE IN FRONT OF THE ELECTRICAL PANEL AT THE... $0 $0 Apr 5, 2023
Jan 24, 2023 39078300P RESOLVE CLASS - 2 I OBSERVED IN THE LAUNDRY/ BOILER ROOM THE INSTALLATION OF A BLACK FLEXIBLE RUBBER CORD SUPPLYING POWER TO THE PARKIN... $0 $0 Apr 5, 2023
Jan 24, 2023 39078299R RESOLVE CLASS - 2 I OBSERVED THE INSTALLATION WALL MOUNTED LED LIGHTS IN THE PARKING LOT, THERE ISNO ELECTRICAL PERMIT IN DOB RECORDS T... $0 $0 Apr 5, 2023
Jan 24, 2023 39078302Z RESOLVE CLASS - 2 I OBSERVED IN THE FRONT OF THE PREMISES A RECEPTACLE NOT OF THE GFCI TYPE NOR GFCI PROTECTED,, ALSO NOTED IN THE REAR... $1,000 $0 Sep 18, 2023
Sep 28, 2021 39048306Z RESOLVE CLASS - 2 #2 HOT WATER HEATER SAFETY VALVE INLET AND OUTLET PIPING IS INCORRECT+IT IS NOT125PSI/#1 HWH DRAFTSTAT DEFECT/HW TEMP... $655 $0 Feb 2, 2022
Aug 27, 2021 35586810K RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED AT FIRST FLOOR EXP #2 AND #3 PERIMETER WALLS OR ENCLOS... $0 $0 Jan 5, 2022
Aug 27, 2021 35586811M RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOT FIRE STOPPING PER BC 712.3;27-345.OBSERVED AT FIRST FLOOR M... $0 $0 Jan 5, 2022
Oct 31, 2019 38272094X RESOLVE CLASS - 1 14M7, (C/U 42G11); 67X10: (14,M,7) IN CAR MIRROR MISSING PROVIDE. (42,G,11) IMPROPER FUSES ON THE CONTROLLER FOUR FUS... $1,250 $0 Mar 4, 2020
Aug 28, 2019 39008651N RESOLVE CLASS - 2 I OBSERVED IN THE GROUND FLOOR LAUNDRY AREA THE INSTALLATION OF CONVENIENCE RECEPTACLE OUTLETS NOT OF THE GFCI TYPE N... $1,200 $0 Oct 21, 2019
Aug 28, 2019 39008650L RESOLVE CLASS - 1 I OBSERVED ON THE GROUND FLOOR LAUNDRY AREA THE IMPROPER WIRING OF AN EQUIPMENT DISCONNECT FOR A GAS DRYER. I OBSERVE... $0 $0 Oct 21, 2019
Mar 11, 2019 35386424X RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: AT ROOF,CABLE TRAY COVERS ARE LOOSE FROM TRAYS & IN DANGER OF... $2,500 $0 Jun 24, 2019
Mar 11, 2019 35401905J RESOLVE CLASS - 2 EXIT DOOR NOT SELF CLOSING. NOTED: AT BULKHEAD,DOOR TO ROOF NOT SELF CLOSING. ALSO,AT 1ST STY IN LAUNDRY EM,EXIT DOOR... $0 $0 Jun 24, 2019
Mar 11, 2019 35401908P RESOLVE CLASS - 1 FAILURE TO PROTECT AGAINST DETERIORATING AGENTS. OBSERVED IN ELECTRICAL EQUIPMENT ROOM LOCATED IN PARKING LOT AREA, A... $1,600 $0 Jun 24, 2019
Mar 11, 2019 35401906L RESOLVE CLASS - 1 ELECTRICAL WORK W/O A PERMIT. OBSERVED ON 1ST FLOOR, LAUNDRY AREA. THEINSTALLATION OF BRANCH CKT WIRING, EQUIPMENT DI... $800 $0 Jun 24, 2019
Mar 11, 2019 35401904H RESOLVE CLASS - 1 FAILURE TO MAINTIAN BLDG IN CODE COMPLIANT MANNER. NOTED: IN ELECTRICAL PANEL ROOM,WATER PENETRATING CEILING. WATER P... $1,250 $0 Jun 24, 2019
Mar 11, 2019 35401907N RESOLVE CLASS - 2 FAILURE TO PROPERTY CONNECT CNDUCTORS TO TERMINALS. OBSERVED IN THE LAUNDRY AREA, THE INSTALLATION OF EQUIPMENT DISCO... $0 $0 Jun 24, 2019
Dec 11, 2018 39000938Y RESOLVE CLASS - 2 ILLEGAL STORAGE OF NON-ELEVATOR ITEMS IN MACHINE ROOM, MAINTENANCE LOG MISSING DETAILED INFO, MISSING CONTROLLER PRIN... $0 $0 Jan 28, 2019
Oct 31, 2017 38258840H RESOLVE CLASS - 1 CEASE USE. 70Y2,81Y13,38I11. (70Y)PIT HAS EXCESSIVE OIL,CLEAN. (81Y)PISTON IS LEAKING,SEAL. (38I)TRAVELING CABLE NEAR... $1,000 $0 Dec 18, 2017
Oct 21, 2010 34874096M RESOLVE CLASS - 1 RESIDENCE ALTERED FOR OCCUPANCY AS A DWELLING FOR MORE THAN THE LEGALLY APPROVED # OF FAMILIES.DOB RECORD INDICATES P... $0 $0 Nov 14, 2011
Sep 18, 2009 38206275J RESOLVE CLASS - 2 40B09,40R09,60Q03,48BB05,69M07,70O02,77Q03,34O02,70M07,17O06,10H11,100D06,34B03,67X10,97X10.40BR ACCESS BLOCKED & NON... $500 $0 Nov 9, 2009