ECB violations
599 Utica Avenue, Brooklyn • Block 04604 • Lot 0052
23 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 30, 2026 | 39194321M | ACTIVE | CLASS - 1 | CLASS 1 C/U: DOOR ZONE RESTRICTOR INOPERATIVE AS PER ASME A17.1/CSA B44. THIS CONDITION COMPROMISES DOOR SAFETY AND C... | $1,250 | $1,250 | Sep 9, 2026 |
| Jul 24, 2024 | 39119748L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 2 ITEMS: MAINTENANCE LOG MISSING IN THE MACHINE ROOM, PE... | $312 | $0 | Oct 28, 2024 |
| Sep 15, 2021 | 39047577X | RESOLVE | CLASS - 2 | HOT WATER HEATER #3 IS DEFECTIVE/HOT WATER HEATER#3 IS MISSING WEATHER CAP AT TOP OF FLUE/HOT WATER HEATER#6 IS DEFEC... | $625 | $0 | Jan 19, 2022 |
| Jul 14, 2021 | 39044379L | RESOLVE | CLASS - 2 | PROVIDE A CODE COMPLIANT SHACKLE FOR THE HOIST ROPES AND THE GOVERNOR CABLE. FILE FOR A TEST (CODE: 2.20.9.5 WEDGE RO... | $310 | $0 | Nov 17, 2021 |
| Dec 22, 2020 | 39033803H | RESOLVE | CLASS - 1 | CLASS 1 : NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCB... | $1,250 | $0 | Apr 28, 2021 |
| Oct 18, 2018 | 38265989L | RESOLVE | CLASS - 2 | 52K2 HOIST CABLES RUSTED CLEAN AND MONITOR CONDITION. | $655 | $0 | May 1, 2019 |
| Aug 14, 2018 | 35341827L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. IN CELLAR LEVEL MECHANICAL ROOM DOOR NO SELF CLOSING, DOOR TO ELEC... | $1,250 | $0 | Jan 14, 2019 |
| Aug 14, 2018 | 35347086K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 08/14/18 AT ABOVE ADDRESS SPRINKLER HEAD ON THE 2ND... | $625 | $0 | Nov 27, 2018 |
| Dec 19, 2017 | 35297740N | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE W/ SECTION. OBSERVED THE GROUNDING ELECTRODE CONNECTED... | $4,800 | $0 | Feb 12, 2018 |
| Oct 25, 2017 | 35275752N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35287056H ISSUED 07/26/17 AND TO FILE... | $800 | $0 | Dec 11, 2017 |
| Aug 30, 2017 | 35277110K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUM/VIO#35287056H ISSUED ON 07/26/17 & TO FILE A C OF C PURSUANT TO... | $800 | $0 | Jan 3, 2018 |
| Jul 26, 2017 | 35287058L | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT.OBSERVED EXPOSED ENERGIZED WIRES ON ROOFTOP WHICH WERE PREVIOUSLY CONNECTED TO SIGNS... | $1,600 | $0 | Feb 21, 2018 |
| Jul 26, 2017 | 35272339X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRE STOPPINGPER BC 712.3;27-345.NOTED:OBSERVED AT CELLAR LE... | $530 | $0 | Nov 20, 2017 |
| Jul 26, 2017 | 35287056H | RESOLVE | CLASS - 1 | 250.4 FAILURE TO INSTALL GROUNDING ELECTRICAL CONDUCTOR IN ACCORDANCE WITH SECTION.OBSERVED THE GROUNDING ELECTRICAL ... | $8,000 | $0 | Sep 18, 2017 |
| Jul 26, 2017 | 35287057J | RESOLVE | CLASS - 1 | 250.68 BUILDING GROUND CLAMP INACCESSIBLE. OBSERVED GROUNDING CONDUCTOR AND CONDUIT IN AREA OF WATER SERVICE PIPE UNA... | $8,000 | $0 | Sep 18, 2017 |
| Feb 3, 2017 | 35225637M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC COR... | $250 | $0 | Mar 20, 2017 |
| Feb 3, 2017 | 35226465J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.OBSERVED ON 2/3/17 NO BOILER RECORDS ON FILE AT THE DOB.REM:REPAIR ... | $500 | $0 | Mar 20, 2017 |
| Feb 3, 2017 | 35226464H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.OBSERVED ON 2/3/17 NO INPSECTORS TEST GAUGE ON UPPER MOST FLR.REM:R... | $500 | $0 | Mar 20, 2017 |
| Jun 1, 2016 | 38243221R | RESOLVE | CLASS - 2 | 31J01,52K11,61B07,70O02,39O02,05X10. 05X10-FRONT DOOR RESTRICTOR NEED A NEW LATCH PLATE; 31J01-LEVELING SLIGHTLY OFF ... | $0 | $0 | Jul 18, 2016 |
| Dec 1, 2010 | 38214220M | RESOLVE | CLASS - 2 | 40R09,17D06,10D06,17M07,41B07,70Y02,08V01,08J01,46Q03,37Q03,14M07,05X10. 40R- REMOVE NON ELEVATOR MATERIAL. 17/10D- S... | $0 | $0 | Jan 24, 2011 |
| Jun 26, 2009 | 38204286X | RESOLVE | CLASS - 2 | 70Y10,70Y02,77X10 77X-UNDERCAR LIGHT | $250 | $0 | Nov 9, 2009 |
| Feb 20, 2008 | 38182207Y | RESOLVE | Hazardous | 41N09.12Q03.39R09.66Y02.17H11.17D06.10H11.71X10.08V01.09I10. 41N BY PASSED FUSE 12Q UNGUARDED CAB LIGHTS 39R REMOVE N... | $180 | $0 | Apr 21, 2008 |
| Jul 2, 2004 | 34438119P | RESOLVE | Non-Hazardous | QUESTIONABLE CONSTRUCTION IN BASEMENT, STEEL IS TO BE SUPPORTED BLOCK/CONCRETE WALL (ANCHOR ON PRESSURE PLATE) HOWEVE... | $400 | $0 | Aug 16, 2004 |