ECB violations
268-284 East 96 Street, Brooklyn • Block 04650 • Lot 0015
56 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 13, 2026 | 35731618Z | ACTIVE | CLASS - 2 | RE-ISSUE 35691745H. AT THE TIME OF INSPECTION, THE FOLLOWING EMERGENCYLIGHTS WERE INOPERABLE:-#1 AND #3(CAFETERIA), #... | $3,125 | $0 | May 27, 2026 |
| Apr 13, 2026 | 35731619K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, STAIRWELL DOWN TO GRADE @ EXIT #7 H... | $1,250 | $0 | May 27, 2026 |
| Apr 13, 2026 | 35731620H | ACTIVE | CLASS - 2 | 28-301.1. RE-ISSUE 35691744X. AT THE TIME OF INSPECTION, GAS METER ROOM DID NOT HAVE VENTILATION. REMEDY: COMPLY WITH... | $3,125 | $0 | May 27, 2026 |
| Apr 13, 2026 | 35731617R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, THE FOLLOWING DOORS WERE NOT SELF-C... | $1,250 | $0 | May 27, 2026 |
| Apr 23, 2025 | 35485999K | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O AND/OR THE DEPARTMENT OF BUILDINGS RECORDS. PARTITION ERECTED CREATING A... | $6,250 | $6,250 | Nov 5, 2025 |
| Apr 11, 2025 | 35691745H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS P... | $1,250 | $0 | Nov 7, 2025 |
| Apr 11, 2025 | 35691744X | ACTIVE | CLASS - 2 | 28-301.1. RE-ISSUE #35678800P. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE), FGC APPENDI E(... | $3,125 | $0 | Nov 7, 2025 |
| Mar 14, 2024 | 35678800P | ACTIVE | CLASS - 2 | 28-301.1 REISSUE#35672509M FAILURE TO PROVIDE VENTILATION TO GAS METERROOM PER P115.6 L1968 CODED.FG6 APPENDIX E(C4)(... | $3,125 | $0 | May 3, 2024 |
| Mar 9, 2023 | 35672509M | ACTIVE | CLASS - 2 | 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER RM PER P115-6(1968 CODE),FGC APPENDIX E (E4) (2014 CODE).NOTED:A... | $1,250 | $0 | Jun 21, 2023 |
| Mar 9, 2023 | 35672510J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED:AT ROOF AIRPOCKETS ARE PRESENT THROUGHOUT CAUSING THE LEAK... | $0 | $0 | Jan 10, 2024 |
| May 11, 2022 | 35654732X | ACTIVE | CLASS - 2 | 28-301.1 RE-ISSUED #35578186X FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115-6(1968),FGC APPENDIX E(E4)(20... | $3,125 | $0 | Oct 26, 2022 |
| Jun 7, 2021 | 35578184M | RESOLVE | CLASS - 2 | REISSUE35442710K FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES&PUBLIC CORRI... | $1,562 | $0 | Nov 10, 2021 |
| Jun 7, 2021 | 35578185Y | RESOLVE | CLASS - 2 | REISSUE35442711M FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NO FIRESTOPPING@GAS METER RM.COMPLY W/CODE. | $3,125 | $0 | Nov 10, 2021 |
| Jun 7, 2021 | 35578186X | ACTIVE | CLASS - 2 | REISSUE35442712Y FAILURE TO PROVIDE VENTILATION TO GAS METER RM PER P115.6(1968 CODE)FGC APPENDIXE (E4)(2014 CODE) NO... | $3,125 | $0 | Nov 10, 2021 |
| Jul 30, 2019 | 35442707J | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTED: THE FOLLOWING ARE NOT WORKING PROPERLY; SMOKE DOORS BY 101, 205, 211 & 213B, REM:R... | $0 | $0 | Jan 8, 2020 |
| Jul 30, 2019 | 35442712Y | ACTIVE | CLASS - 2 | 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE) FGC APENDIX E(E4)(2014 CODE).NOTED: @... | $0 | $0 | Jan 8, 2020 |
| Jul 30, 2019 | 35442709N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THE CEILING TILES BT THE MAINENTRNACE AND BY ROOM 102 A... | $0 | $0 | Jan 8, 2020 |
| Jul 30, 2019 | 35442705X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:AT EXPOSURES#1&2 OF THE FACADE HAS SPALLING PAINT IN VAR... | $1,250 | $1,250 | Mar 20, 2020 |
| Jul 30, 2019 | 35442706H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED:PANELS INSTALLED ON THE STEPS AT THE MAIN ENTRANCE TO TH... | $625 | $625 | Mar 20, 2020 |
| Jul 30, 2019 | 35442710K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER; ILLUMINATION FOR EXITS EXIT DISCHARGES & PUBLIC CORRIDORS PER ... | $0 | $0 | Jan 8, 2020 |
| Jul 30, 2019 | 35442711M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING CODE-COMPLAINT MANNER: NO FIRES STOPPINGPER BC 712.3; 27-345. NOTED: @THE GAS METER ROOM... | $0 | $0 | Jan 8, 2020 |
| Jun 4, 2018 | 35332047X | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING.IN CAFETERIA(NEAR BOYS BATH)EXIT DOORS IS NOT SELF CLOSING WHEN TESTED AT THE TIME OF INSP... | $0 | $0 | Sep 17, 2018 |
| Aug 5, 2014 | 35107711Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) AND/OR APPURTENANCES FOUNDATION WALLSALLOWS WATER TO PENETRATE IN SLOP SINK ROOM AND... | $1,250 | $0 | Sep 29, 2014 |
| Aug 5, 2014 | 35107146K | RESOLVE | CLASS - 2 | INTERIOR FOUNDATION WALLS @FIRST FL IN SLOPSINK RM & PAINTROOM,WALLS SPALLING DUE TO WATER PENETRATION.REM:REPAIR WAL... | $0 | $0 | Oct 27, 2014 |
| Feb 17, 2012 | 34941197Z | RESOLVE | CLASS - 2 | REISSUE # 34871347Y. WATER PENETRATING ROOF AT: 2ND FLOOR ABOVE MAIN ENTRY. REMEDY: MAINTAIN WATER PROOF INTEGRITY OF... | $0 | $0 | Apr 30, 2012 |
| Feb 17, 2012 | 34941198K | RESOLVE | CLASS - 2 | DOORS NOT CLOSING AT: 2ND STORY EXIT 9 INTERIOR VESTIBULE DOOR, 1ST STORY EXIT 7,10 & 11 EXIT DISCHARGE DOORS (DOOR J... | $0 | $0 | Apr 30, 2012 |
| Jul 28, 2011 | 34918199R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG. NOTED WATER PENETRATING ROOMS 200,201,216,212, MAIN ENTRANCE ALSO UNLEVELED PAVEMENT IN ALL... | $2,500 | $0 | Sep 19, 2011 |
| Aug 4, 2010 | 34871346M | RESOLVE | CLASS - 2 | REISSUE: 34779672X EXTERIOR CONCRETE BLOCK RETAINING WALL IS MISSING MORTAR CREATING A STEP CRACK ALONG THE WALL LOCA... | $0 | $0 | Sep 13, 2010 |
| Aug 4, 2010 | 34871349H | RESOLVE | CLASS - 2 | EXTERIOR METAL PLATFORM LEADING TO THE ALLEY WAY IS RUSTED LEAVING HOLES ON THE 1ST FLOOR LEVEL. REM:REPAIR/REPLACE M... | $0 | $0 | Sep 13, 2010 |
| Aug 4, 2010 | 34871703L | RESOLVE | CLASS - 2 | INTERIOR PLASTER ON THE WALL IS CRACKED & SPALLING LOCATED IN THE BOYS BATHROOM @ THE BASEMENT LEVEL.REM:REPAIR AND/O... | $0 | $0 | Sep 13, 2010 |
| Aug 4, 2010 | 34871348X | RESOLVE | CLASS - 1 | EXTERIOR CONCRETE WALL IS CRACKED & BULGING LOCATED @ THE ALLEYWAY ON THE 1ST FL LEVEL LEADING TO THE PUBLIC STREET. ... | $0 | $0 | Sep 13, 2010 |
| Aug 4, 2010 | 34871705P | RESOLVE | CLASS - 2 | GLASS ABOVE THE MAIN ENTRANCE ON THE 1ST FL LEVEL IS CRACKED & HELD IN PLACE BY TAPE. REM:REPLACE BROKEN GLASS. | $0 | $0 | Sep 13, 2010 |
| Aug 4, 2010 | 34871347Y | RESOLVE | CLASS - 2 | EXTERIOR WINDOW LINTELS ARE ROTTEN RUSTED LOCATED @ THE REAR OF THE SCHOOL ON THE 2ND FL LEVEL. REM:REPLACE ROTTEN & ... | $0 | $0 | Sep 13, 2010 |
| Aug 4, 2010 | 34871704N | RESOLVE | CLASS - 2 | EXTERIOR ROOF HAS BECOME POROUS AND ALLOWING RAIN INTO THE BUILDING CAUSING INTERIOR DAMAGES BY THE MAIN ENTRANCE 1ST... | $0 | $0 | Sep 13, 2010 |
| May 22, 2009 | 34779670M | RESOLVE | CLASS - 2 | REISSUE: 34698620J. THE CONCRETE CEILING IS CRACKED AT THE CAFETERIA EXIT LEADING TO THE PLAYGROUND. REMEDY: REPAIR C... | $0 | $0 | Jul 6, 2009 |
| May 22, 2009 | 34779350N | RESOLVE | CLASS - 2 | THE PLASTER IS SPALLING OFF THE CEILING LOCATED IN ROOM 212 ON THE 2ND FLR LEVEL. REMEDY: REPAIR/REPLACE PLASTER ON C... | $0 | $0 | Jul 6, 2009 |
| May 22, 2009 | 34779674J | RESOLVE | CLASS - 2 | THE ELECTRICAL RM IS BEING USED AS A STORAGE RM CONSISTING OF SHELVES W/FILLED BOOKS AT BASEMENT LEVEL. REMEDY: REMOV... | $0 | $0 | Jul 6, 2009 |
| May 22, 2009 | 34779672X | RESOLVE | CLASS - 2 | EXTERIOR CONCRETE BLOCK WALL APPROX 10' IN THE CHILDREN'S PLAYGROUND IS MISSING MORTAR BETWEEN THE BLOCS. REMEDY: REP... | $0 | $0 | Jul 6, 2009 |
| May 22, 2009 | 34779671Y | RESOLVE | CLASS - 2 | EXIT DOOR #8 LEADING TO THE CHILDREN'S PLAYGROUND IS DEFECTIVE. NOTED:DOOR IS HITTING DOOR FRAME CAUSING DOOR TO OPEN... | $0 | $0 | Jul 6, 2009 |
| May 22, 2009 | 34779673H | RESOLVE | CLASS - 2 | THE PLASTER BY EXIT #11 AT BASEMENT LEVEL IS CRACKED & MISSING BY THE FLR BASE. REMEDY: REPAIR/REPLACE PLASTER. | $0 | $0 | Jul 6, 2009 |
| Oct 10, 2008 | 34698621L | RESOLVE | CLASS - 2 | NO FIRE-STOPPING PROVIDED IN THE GAS METER ROOM @ CELLAR LEVEL LOCATED@ PIPE - PENETRATIONS GOING THROUGH THE WALL. R... | $0 | $0 | Dec 15, 2008 |
| Oct 10, 2008 | 34698619M | RESOLVE | CLASS - 2 | WINDOW LINTELS ARE ROTTEN LOCATED OUTSIDE OF CLASS ROOM 214 @ THE 2ND FLOOR. REMEDY: REPAIR / REPLACE WINDOW LINTELS | $0 | $0 | Dec 15, 2008 |
| Oct 10, 2008 | 34698620J | RESOLVE | CLASS - 2 | CONCRETE CEILING IS CRACKED ALONG THE STAIR WAY LEVING THE CAFETERIA EXIT LEADING TO THE PLAYGROUND @ THE BASEMENT LE... | $0 | $0 | Dec 15, 2008 |
| Feb 2, 2007 | 34556312Y | RESOLVE | Non-Hazardous | RE-ISSUE:34513389M. FAILURE TO MAINTAIN BLDG. NOTED: MISSING 4 SMOKE DOORS AT EXIT 'C' ADJACENT TO BOYS BATHROOM AT B... | $0 | $0 | Apr 16, 2007 |
| Mar 14, 2006 | 34513389M | RESOLVE | Hazardous | REISSUE #34474397N. MISSING 4 FIRE SMOKE STOP DOORS IN BASEMENT BY EXIT "C". REMEDY: PROVIDE MISSING DOORS. | $0 | $0 | May 1, 2006 |
| Mar 14, 2006 | 34513390J | RESOLVE | Hazardous | ELECTRICAL ROOM IN BASEMENT (RM 101) USE AS A STORAGE ROOM REMEDY: REMOVE STORAGE MAINTAIN EL. ROOM CLEAR. | $0 | $0 | May 1, 2006 |
| Mar 24, 2005 | 34474397N | RESOLVE | Non-Hazardous | 4 FIRE SMOKE STOP DOORS MISSING AT BASEMENT BY EXIT C NOTED 2 DOOR FRAMES ARE ROTTEN NEXT TO BATHROOMS.REMEDY:PROVIDE... | $0 | $0 | Aug 1, 2005 |
| May 4, 2004 | 34434591K | RESOLVE | Non-Hazardous | REISSUE FAILURE TO MAINTAIN DEFECTS ARE ROTTEN LOOSE AND SAGGING METALDOORS AND FRAMED LOCATIONS ARE CELLAR STORAGE R... | $0 | $0 | Aug 2, 2004 |
| Feb 4, 2003 | 34386890R | RESOLVE | Hazardous | FAILURE TO MAINTIAN DEFECTS ARE IN CELLAR GIRLS AND BOYS BATHROOMS METAL STALL DEVIDERS ARE LOOSE, SAGGING AND ROTTEN... | $0 | $0 | Apr 14, 2003 |
| Feb 4, 2003 | 34386893M | RESOLVE | Hazardous | " REISSUE " FAILURE TO MAINTIAN DEFECT IS. AT EXTERIOR REAR NORTH LARGE OPENING AND UN PORTECTED PIT APPROX 8'L X 6'W... | $0 | $0 | Apr 14, 2003 |