| Dec 1, 2025 | 39168880J | ACTIVE | CLASS - 1 | AS PER NATGRID MECHANIC RIVERA#71014025 ON SITE. 2" GAS LINE WAS SHUT & LOCKED ON 11/19. THE LOCK WAS CUT & GAS HAS B... | $25,000 | $25,000 | Mar 20, 2026 |
| Apr 6, 2022 | 38274216Y | RESOLVE | CLASS - 1 | CEASE USE;97R05:97-R-05 WORK W/O PERMIT. CONVEYOR WAS INSTALLED W/O PERMIT BEING OBTAINED AND APPLICATION BEING FILED... | $2,500 | $0 | Oct 3, 2022 |
| Apr 6, 2022 | 38274217X | RESOLVE | CLASS - 1 | CEASE USE;97R05:97-R-05 WORK W/O PERMIT. CONVEYOR WAS INSTALLED W/O PERMIT BEING OBTAINED AND APPLICATION BEING FILED... | $2,500 | $0 | Oct 3, 2022 |
| Oct 17, 2018 | 35358669X | RESOLVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSUITABLE ELECTRUCAL EQUIPEMNT APPARATUS,MATERIAL,DEVICES,APPLIANCES& WIRING IN USE.OBSERVED:UNAPP... | $1,600 | $0 | Jan 7, 2019 |
| Oct 17, 2018 | 35358668Y | ACTIVE | CLASS - 1 | ELECTRICAL WORK WITHOUT PERMIT.OBSERVED THAT WIRING AND INSTALLED OF LIFT WAS DONE WITHOUT PERMIT,INCLUDING BRANCH CI... | $800 | $0 | Jan 7, 2019 |
| Aug 31, 2016 | 32076536H | RESOLVE | CLASS - 2 | B265 AS PER DOB RECORDS AS PER CLASS 2 (B265) 28.303.7 FAILURE TO COMPLETE BOILER INSPECTION REPORT. AS PER DOB RECOR... | $1,250 | $0 | Oct 24, 2016 |
| Aug 31, 2016 | 32076537J | RESOLVE | CLASS - 2 | B265 AS PER CLASS (B265) 28-303.7 FAILURE TO FILE A COMPLETE BOILER INSPECTION REPORT AS PER DOB RECORDS AND SUBMIT A... | $500 | $0 | Apr 26, 2017 |
| Aug 17, 2009 | 32066646J | RESOLVE | CLASS - 2 | 2 B254 50A.50B 50A PRESSURE CONTROLS MUST BE ON SEPERATE 1/4" TAPPINGSCAN'T BE ONE 1/4" TAPPINGS 50B FRESH AIR BLOWER... | $0 | $0 | Oct 5, 2009 |
| Apr 23, 2008 | 32056404H | RESOLVE | Non-Hazardous | 6A50A50B. COLUMBIA FTSH HP STEAM BOILER. 6A CONTINUOUS STEAM LEAKAGE AT THE SAFETY VALVE REPLACE DEFECTIVE SAFETY VAL... | $0 | $0 | Jun 16, 2008 |
| Jul 18, 2006 | 32051669K | RESOLVE | Non-Hazardous | 50A,50B/COLUMBIA FISH BOILER HP STEAM OIL FIRED/50A-BLOCKED AIR INTAKEFOR BOILER ROOM VENTILATION HIGHH AMBIENT TEMPE... | $0 | $0 | Aug 28, 2006 |
| Jan 22, 2005 | 32047034P | RESOLVE | Non-Hazardous | 38/50A/50B COLUM RTSM BLR 38 NO FIXED FRESH AIR VENTILATION FOR ENCLOSED BOILER 50A-NO DISCHARGE PIPE ON THE SAFTEY V... | $180 | $0 | Mar 15, 2005 |
| May 28, 1999 | 34194357M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BLDG INTEERIOR DEFECT CEILING AND WALLS FORMING STAIRWELL IS NOTE FIRE RATED IN AREA WHERE PLYWOO... | $0 | $0 | Nov 15, 1999 |
| Jan 8, 1999 | 34184484X | RESOLVE | Non-Hazardous | NO EQUIPMENT USE PERMIT FOR A/C UNIT ON ROOF-YORK 5 TON. REMEDY: OBTAIN A VALID EQUIPMENT USE PERMIT. | $0 | $0 | Mar 29, 1999 |
| Aug 22, 1998 | 32016215M | RESOLVE | Non-Hazardous | 18A,18B,49, LOW WATER MANUAL RESET SWITCH DISCONNECTED | $180 | $0 | Nov 23, 1998 |
| Mar 21, 1997 | 34151991J | RESOLVE | Hazardous | FAILURE TO MAINTAIN. HAZARDOUS. AT INETERIOR CELLAR STAIR AT 1887 & 1895 NOSTRAND AVENUE NO FIRE RATED INTERIOR BULKH... | $800 | $0 | Nov 24, 1997 |
| Mar 21, 1997 | 34151989K | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT. DEMISHING PARTTIONS BETWEEN 1893 & 1895 NOSTRAND HAVE BEEN REMOVED MAKING A GREAT SPACE APPROC... | $800 | $0 | Nov 24, 1997 |
| Mar 21, 1997 | 34151990H | RESOLVE | Hazardous | RETAIL SPACE APPROACHING 8000 SQUARE FEET REQIRES A SPRINKLER SYSTEM AT 1ST FLOOR. REMEDY; PROVIDE SPRINKLER SYSTEM F... | $400 | $0 | Nov 24, 1997 |
| Jun 13, 1994 | 34108911R | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. DEFECT IS: THE PARAPET WALL AT THE NORTH SIDE OF PREMISES IS OUT OF PLUMB... | $1,000 | $0 | Sep 19, 1994 |
| Jun 2, 1993 | 32010158H | RESOLVE | Hazardous | 6A BOILER DESIBN PRESSURE IS 100 PSL. NEW SAFETY VALVE MUST HAVE SETT-ING MAXIMUM UP TO 100 PSI. THIS SUPERCEDES VIOL... | $250 | $0 | Jun 28, 1993 |
| Apr 12, 1993 | 34068644H | RESOLVE | Non-Hazardous | SPRINKLER INSTALLATION NOT IN ACCORDANCE WITH RS17-2.ALL SPRINKLER HE-ADS PAINTED.REMEDY-CONFORM TO RS17-2 REMEDY:ENG... | $500 | $0 | Dec 6, 1993 |
| Dec 9, 1992 | 32009752M | RESOLVE | Non-Hazardous | 32, BOILER DESIGN PRESSURE IS 100PS1 EXISTING SAFETY VALVE IS SET FOR 125 PS1. THE LATER TO REPLACE BY NEW ONE SET MA... | $0 | $0 | Feb 8, 1993 |