ECB violations
2117-2127 Beekman Place, Brooklyn • Block 05026 • Lot 0070
55 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 18, 2026 | 39188957R | RESOLVE | CLASS - 2 | 1) PROVIDE ACCESS TO THE MOTOR-ROOM (8.11.2.1.2). 2) THE CAT-5 TAG IS EXPIRED (JUNE/2014) (8.11.1.6) 3) COMPLY WITH (... | $625 | $625 | Jul 22, 2026 |
| Aug 1, 2025 | 39155778K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING CODE COMPLIANT. NOTED: IN APARTMENT 6-H, THE BATHROOM DOOR KNOB IS LOOSE AND BROKEN ALLO... | $0 | $0 | Oct 8, 2025 |
| Apr 28, 2025 | 39146281K | RESOLVE | CLASS - 2 | INOPERATIVE PHONE. MISALIGNED CAB MIRROR. ADJUST FLOOR STOPS. UNGUARDED PLANK SWITCH. PROVIDE UP TO DATE CONTACT INFO... | $0 | $0 | May 6, 2026 |
| Apr 4, 2024 | 39110773M | ACTIVE | CLASS - 2 | MISALIGNED CAB MIRROR. UNGUARDED PLANK SWITCH. LABEL HOISTWAY DOORS WHERE NEEDED. ADJSUT FLOOR STOPS. CLEAN PIT. MISS... | $625 | $625 | Dec 2, 2024 |
| Mar 22, 2024 | 39109636H | ACTIVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT LIFTING CORRECTLY CAUSING ENTRAPMENTS. REPAIR RESTRICTOR. C/U. | $1,250 | $1,250 | Jun 5, 2024 |
| Nov 29, 2023 | 39100360P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NO RECENT CATEGORY 1 TESTS FILED WITH NYC DOB. IN CAR COMMUNIC... | $0 | $0 | Dec 23, 2024 |
| Jun 13, 2023 | 39088452N | RESOLVE | CLASS - 2 | CLASS 2: CAR FLOOR NOT LEVEL TO LANDING SILL CREATING SAFETY HAZZARD. ADJUST CAR TO LEVEL AT EVERY FLOOR. CAR BUTTON ... | $312 | $312 | Feb 27, 2024 |
| Jan 13, 2023 | 39077740Y | RESOLVE | CLASS - 1 | CEASE USE ITEM: INOPERATIVE ALARM AND PHONE. CLASS 2 ITEMS: UNGUARDED PLANK SWITCH. CLEAN CAR TOP. FLOOR STOPS NOT LE... | $1,250 | $1,250 | Aug 7, 2023 |
| Oct 19, 2022 | 39072324M | RESOLVE | CLASS - 1 | RIGHT SIDE BRAKE IS NOT LIFTING. C/U. REPAIR. CAR IS OFF LEVEL AT BASEMENT AND 1ST FLOOR. C/U. ADJUST. DLM IS NOT WOR... | $0 | $0 | May 22, 2023 |
| Sep 27, 2022 | 39070946H | RESOLVE | CLASS - 1 | THE ONLY ELEVATOR IN BUILDING OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE CREATING A HA... | $1,250 | $1,250 | Jun 5, 2023 |
| Sep 2, 2022 | 39069402L | RESOLVE | CLASS - 1 | THE ONLY ELEVATOR IN BUILDING) OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE. REMEDY: RES... | $1,250 | $1,250 | Jan 4, 2023 |
| Jul 27, 2022 | 39066838Z | RESOLVE | CLASS - 1 | PROVIDE KEYS TO ACCESS BASEMENT., PROVIDE KEYS TO ACCESS MOTOR-ROOM., PROVIDE KEYS TO ACCESS PIT., CLEAN PIT., REPAIR... | $6,250 | $6,250 | Dec 7, 2022 |
| May 19, 2022 | 39062494X | ACTIVE | CLASS - 1 | DLM IMPROPERLY INSTALLED ON THIS DEVICE. NO FIREMANS' SERVICE PRESENT IN CONTROLLER. INSTALL FIREMANS' SERVIDE SO DLM... | $25,000 | $25,000 | Sep 21, 2022 |
| Apr 27, 2022 | 39061179L | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $0 | $0 | Apr 24, 2023 |
| Mar 3, 2022 | 39057385K | ACTIVE | CLASS - 1 | 1) NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS... | $25,000 | $25,000 | Jul 6, 2022 |
| Sep 29, 2021 | 39048423H | ACTIVE | CLASS - 1 | 1) THIS DEVICE WILL NOT STOP ON THE 4TH FLOOR (AS PREVIOUSLY STATED IN SUMMONS 39035055K ON 1/19/21). THIS CREATES A ... | $3,125 | $3,125 | Feb 2, 2022 |
| Apr 2, 2021 | 39038774K | ACTIVE | CLASS - 2 | PROVIDE KEYS TO ACCESS BASEMENT., PROVIDE KEYS TO ACCESS PIT., PROVIDE KEYS TO ACCESS ROOF., PROVIDE KEYS TO ACCESS E... | $3,125 | $3,125 | Sep 8, 2021 |
| Jan 19, 2021 | 39035055K | RESOLVE | CLASS - 2 | PROPERLY SECURE CAR DOOR OPERATOR., CLEAN TOP OF CAR., RESTORE SERVICE TO 4TH FLOOR., REPAIR 4TH FLOOR DOOR., PROVIDE... | $625 | $625 | May 26, 2021 |
| Jan 5, 2021 | 39034280M | RESOLVE | CLASS - 1 | CEASE USE ITEMS: 1) CAR STOPS BETWEEN 4TH AND 5TH FLOOR WITH NO CALL ENTERED. 2) INOPERATIVE DOOR LOCK MONITOR 3) LEF... | $0 | $0 | Oct 4, 2021 |
| Sep 3, 2020 | 39028084Y | RESOLVE | CLASS - 1 | CAR STOPS BETWEEN 4TH AND 5TH FLOOR, AND DOOR OPENS (CEASE USE). CAR DOOR SLAMS SHUT, NEEDS ADJUSTMENT. 4TH FLOOR STR... | $1,250 | $1,250 | Mar 8, 2021 |
| Jan 22, 2020 | 38271838P | ACTIVE | CLASS - 1 | 97X10: 97-X-10 DEVICE #3P1122 REMAIN UNDER CEASE USE TO RETURN THIS DEVICE INTO SERVICE FOR A PROPER INSPECTION. REME... | $3,125 | $3,125 | Sep 3, 2021 |
| Jan 17, 2020 | 38273052M | ACTIVE | CLASS - 1 | (C/U 42M07);(C/U 76N10);(C/U 8V01);(C/U 59H11);42M07,02X10,39M07,39M07,21M07,30D06,29D06,44Y02,56Y13,56Y02,59BB07,37X... | $1,250 | $1,250 | Sep 3, 2021 |
| Nov 26, 2019 | 38271771J | ACTIVE | CLASS - 1 | 97X17: 97X, RESTORE ELEVATOR TO SERVICE & CALL D.O.B FOR REINSPECTION | $1,250 | $1,250 | Jul 22, 2021 |
| Jul 2, 2019 | 39004913X | RESOLVE | CLASS - 1 | IN EXIT PASSAGEWAY HOUSEHOLD DEBRIS, GLASS PANELS AND SHOPPING CART OBSTRUCT EXIT PASSAGEWAY, REMOVE OBSTRUCTION | $1,250 | $0 | Aug 19, 2019 |
| Oct 15, 2018 | 35362070L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S)OR APPURTENANCES.NOTED:AT EXP #4 BLDG RIGHT CORNER ROOF LEVEL APPROX 3FT LONG CONCRET... | $0 | $0 | Sep 18, 2019 |
| Sep 18, 2018 | 35351896Y | RESOLVE | CLASS - 2 | PROJECT INFORMATION PANEL/SIDEWALK SHED PARAPET PANEL/CONSTRUCTION SIGN NOT PROVIDED OR NOT IN COMPLIANCE WITH SECTIO... | $0 | $0 | Dec 12, 2018 |
| Sep 18, 2018 | 35351897X | RESOLVE | CLASS - 2 | WORK WITHOUT A PERMIT.UPON INSPECTION OF COMPLIANT #3666998 I NOTICED THERE WASNT ANY PERMIT FOR THE SIDEWALK SHED ON... | $0 | $0 | Dec 10, 2018 |
| Sep 4, 2018 | 35323086Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN IN A CODE COMPLIANT MANNER. THE CONCRETE COPING ONTHE PARAPET IS MISSING,BROKEN & DEFECTIVE AT TH... | $0 | $0 | Feb 27, 2019 |
| Jun 15, 2018 | 38263689K | RESOLVE | CLASS - 2 | 8V1,5J1,16J10,29J1,59M7,56Y2,56Y13,68M7,67L10,70O2. 8V1-CAR FLOOR TO LANDING SILL NOT LEVEL ADJUST; 5J1-CAR DOOR MISA... | $0 | $0 | Nov 5, 2018 |
| May 25, 2018 | 38263408P | RESOLVE | CLASS - 2 | 8V1.59BB7.56YZ.56Y13.70O2.56M7.42N11.68M7.29J1.5J1.16J10.8VQ CARFLOOR TO LADING SILL NOT LEVEL ADJUST 59BB7 MACHINEBR... | $625 | $0 | Jul 23, 2018 |
| Apr 25, 2017 | 38254762N | RESOLVE | CLASS - 1 | CEASE USE. 2M7,1L10,40M7,40P16. (2M)OUTSIDE COMM MISSING PROVIDE. (1L)EMERGENCY STOP SWITCH SELL DOES NOT WORK. (40M)... | $1,000 | $0 | Jun 12, 2017 |
| Feb 6, 2017 | 38253179L | RESOLVE | CLASS - 2 | 8V1,5J1,10H11,29J1,15M7,16J10,40P16. 8V1-CAR FLOOR TO LANDING SILL NOTLEVEL ADJUST; 5J1-CAR DOOR MISALIGNED ADJUST; 1... | $1,250 | $0 | Mar 27, 2017 |
| Dec 19, 2016 | 38251888P | RESOLVE | CLASS - 1 | 15M7,5M7,2M7,2B10,40M7,52H11,21D6,70M7,70O2,39O2,39M7,32H10,32H11.5M7 PROVIDE ZONE RESTRICTOR;2M7 PROVIDE EM.PHONE;2B... | $2,500 | $0 | Mar 27, 2017 |
| Jan 25, 2016 | 38240828J | RESOLVE | CLASS - 1 | 05M07,15M07,34B07,52H11,56O02,59U15,67M07,40P16,40O02,70O02. 05M07-PROIDE DOOR ZONE RESTRICTOR; 15M07; 34B07:PROVIDE ... | $1,000 | $0 | Apr 18, 2016 |
| Sep 17, 2014 | 38233046J | RESOLVE | CLASS - 1 | *77M07 / 08V01,08J01,14J01,29J01,67M07,39D06,76Q03,52V02,16H11,16J11,100M07,97L10,71Q03,70M07,60Q03,57Y13,40V02,69M07... | $1,000 | $0 | Feb 9, 2015 |
| Jun 13, 2014 | 38231779H | RESOLVE | CLASS - 2 | 05B01/ 56Y13/ 69M07/ 68B07/ 70O02/ 67M07/ 21Q03/ 39O02/ 39Q03/ 77Q03/ 52M07/ 59D06/ 60Q03/ 100M07/ 05-B-01- GAP ON UP... | $2,500 | $0 | Jul 28, 2014 |
| Apr 18, 2014 | 38230874L | RESOLVE | CLASS - 2 | 61R05:MAIN LINE DISCONNECT INSTALLED WITHOUT PERMIT | $800 | $0 | Sep 8, 2014 |
| Dec 10, 2013 | 38229392K | RESOLVE | CLASS - 1 | *08V01*77M07*42N09*97L10*21Q03*72M07. 02B10,67M07,15M07,14J01,03I10,16J11,16H11,16I11,39O02,76Q03,39L100,52Y02,53Y02,... | $5,000 | $0 | Jan 27, 2014 |
| Jun 2, 2011 | 34908567M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. RESPONDENT FAILED TOFILE A C/C FOR #34902805L. SPALLING ROOF COPING... | $800 | $0 | Sep 12, 2011 |
| Mar 2, 2011 | 34902805L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING EXTERIOR OBSERVED ALONG FLATBUSH AVE SIDESPALLING PARAPET CAPSTONE AT CORNER, STEP AND H... | $500 | $0 | Dec 5, 2011 |
| Dec 15, 2010 | 34893593R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. SEVERELY RUSTED & DEFLECTED LINTELS @ MOST WINDOWS W/SPORADIC ... | $2,500 | $0 | May 2, 2011 |
| Oct 21, 2010 | 34874319K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALL BRICK WALL HAS VERTICAL CRACKS FROM PARAPET TO APPROX 3RD FLR IN VARIOUS SECTIONS OF WA... | $500 | $0 | Dec 13, 2010 |
| May 6, 2009 | 38203032L | RESOLVE | CLASS - 2 | 08V10.32H10.29I11.26D6.38I11.56Y2.40O2.29I11 DOOR OPERATOR BELT DAMAGED REPLACE BELT 16J10 REPLACE OR DECURE HATCH DO... | $500 | $0 | Jul 2, 2009 |
| Oct 9, 2007 | 34418534Y | RESOLVE | Hazardous | FAILURE TO PROVIDE ELEVATOR LANDING SIGN THAT SHALL READ"IN CASE OF FIRE USE STAIRS,UNLESS OTHERWISE INSTRUCTED" AT T... | $1,200 | $0 | Feb 14, 2008 |
| Aug 31, 2007 | 34562341Y | RESOLVE | Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O & DOB RECORDS. NO SECONDARY MEANS OF EGRESS FROM APT 2C- FIRE ESCAPE ENC... | $2,500 | $0 | Dec 3, 2007 |
| Dec 9, 2003 | 32043678M | RESOLVE | Non-Hazardous | B4A,32A,36,50A,50B. (50A) BOILER SAFETY VALVE NOT PIPED DOWN. (50B) FLUE PIPE NOT SUPPORTED | $350 | $0 | Jan 26, 2004 |
| Dec 9, 2003 | 32043677K | RESOLVE | Non-Hazardous | B4A,22C,42,48A,50A,50B,50C,50D,50E,50F,50G. (50A) FRONT BOILER JACKET CORRODED. (50B) HEAT TIMER WAS CALLING OF HEAT ... | $350 | $0 | Jan 26, 2004 |
| Mar 27, 2002 | 38122555X | RESOLVE | Non-Hazardous | 35P7/74M7/17Q3/62K11/28H12/29H12/17B12. 74M- PROVIDE MISSING TOE GUARD. 17Q LOBBY AND 4TFL. 17B 4TH FL GLASS. | $350 | $0 | Mar 15, 2004 |
| Feb 2, 2002 | 38115298Z | RESOLVE | Non-Hazardous | 08J01/14M07/35P17. | $350 | $0 | Mar 10, 2004 |
| Jul 18, 2000 | 38099206P | RESOLVE | Non-Hazardous | 37G12,57O02,39H08,46#01,47O02,50Y02,53B07,31Q03,08V01.46-ADJUST TENSION ON HOIST RAPES.31-EXPOSED WIRING IN BSMT. | $180 | $0 | Sep 1, 2000 |