ECB violations

Flatbush Ascend Elementary Schl, Brooklyn • Block 05084 • Lot 0084

92 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Sep 11, 2025 39159990X RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED AT LOBBY LEVEL WHERE STAIRCASE'S B... $2,500 $2,500 Jul 24, 2026
Aug 8, 2025 39156477L RESOLVE CLASS - 2 UPON MY INSPECTOIN ELEVATOR WAS FOUND TO BE OUT OF SERVICE. RESTORE TO SERVICE. $312 $312 Jun 29, 2026
Oct 1, 2024 37031228Z ACTIVE CLASS - 1 FAILURE TO SUBMIT THE REQUIRED PARKING STRUCTURE INITIAL OBSERVATION REPORT FOR AN EXISTING PARKING STRUCTURE OR A PE... $1,250 $1,250 Jul 9, 2025
Nov 13, 2023 39099231N RESOLVE CLASS - 2 AT TIME OF INSPECTION OBSERVED CONCRETE WORK BEEN DONE AT REAR BUILDING WITHOUT D.O.B APPROVAL OR PERMIT POSTED., OBT... $0 $0 May 20, 2024
Nov 13, 2023 39099230L RESOLVE CLASS - 2 AT TIME OF INSPECTION OBSERVED AT REAR BUILDING CONCRETE WORK IN PROGRESS LEAVING A 9 FEET HOLE OPEN 33 FEET BY 6 FEE... $0 $0 May 20, 2024
Sep 27, 2023 39095903Z ACTIVE CLASS - 1 16:P:17; CAB DOOR AND HOISTWAY DOORS OPEN ON THE 3RD FLOOR, BUT THE 3RD FLOOR DOOR BUCK IS CLOSED OFF COMPLETELY BY S... $2,500 $2,520 Oct 21, 2024
Sep 27, 2023 39095902R ACTIVE CLASS - 1 16:P:17; CAB DOOR AND HOISTWAY DOORS OPEN ON THE 3RD FLOOR, BUT THE 3RD FLOOR DOOR BUCK IS CLOSED OFF COMPLETELY BY S... $2,500 $2,520 Oct 21, 2024
Sep 27, 2023 39095901P ACTIVE CLASS - 1 16:P:17; CAB DOOR AND HOISTWAY DOORS OPEN ON THE 3RD FLOOR, BUT THE 3RD FLOOR DOOR BUCK IS CLOSED OFF COMPLETELY BY S... $2,500 $2,520 Oct 21, 2024
Sep 27, 2023 39095904K ACTIVE CLASS - 1 16:P:17; CAB DOOR AND HOISTWAY DOORS OPEN ON THE 3RD FLOOR, BUT THE 3RD FLOOR DOOR BUCK IS CLOSED OFF COMPLETELY BY S... $2,500 $2,540 Oct 21, 2024
Apr 18, 2023 39084035Y ACTIVE CLASS - 2 FOUND STATE WATER HEATER S/N1848112733832 INSIDE UNIT 6R DEFECTIVE. PRESSURE RELIEF VALVE DEFECTIVE LEAKING CAUSING C... $625 $0 Jan 3, 2024
Mar 27, 2023 39082318P ACTIVE CLASS - 2 AT TIME OF INSPECTION OBSERVED CEILING AT APARTMENT 6R HAVE WATER DAMAGE PAINT PILING AND HANGING, WINDOW ON LIVING R... $3,125 $0 Jun 7, 2023
Jan 4, 2023 35669571X ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING EXTERIOR WALLS OR APPURTENANCES.NOTE:AT TIME OF INSPECTION OBSERVED EXP #1 SOUTH ELEVATI... $1,250 $0 Nov 27, 2023
Dec 9, 2022 37024743H ACTIVE CLASS - 2 FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... $6,250 $6,250 Mar 1, 2023
Oct 31, 2022 35669288K RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG EXTERIOR WALL FACADE&APPURTENANCES.OBSERVED@EXP1S ELEVATION DAMAGED BALCONY SLAB@12FL LINE W... $2,500 $2,500 May 10, 2023
Oct 31, 2022 35669283L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING EXTERIOR WALLS FACADE & APPURTENANCES.OBSERVED AT EXP #1 SOUTH ELEVATION DAMAGED BALCONY... $0 $0 Apr 12, 2023
Nov 16, 2020 35510094H RESOLVE CLASS - 1 SEC. 3303.4.7 STORAGE NEAR SIDEWALK PATHWAY. NOTE: AT TIME OF MY INSPECTION OF A 26 STY BLDG TOPPED OFF COMPLETED & O... $625 $0 Apr 28, 2021
Jul 15, 2020 35474149K RESOLVE CLASS - 1 28-104.8.4-TENANT PROTECTION PLAN NOT FILED NOTE AT TIME OF INSPECTION OBSERVED WORK BEING PERFORMED UNDER THE AFOREM... $2,500 $0 Jan 28, 2021
Jul 15, 2020 35474274J RESOLVE CLASS - 1 FILED FORM CONTAINING FALSE STATEMENTS NOTE AT TIME OF INSPECTION OBSERVED WORK BEING PERFORMED UNDER THE AFOREMENTIO... $0 $0 Jan 28, 2021
Jun 30, 2020 35492151Z RESOLVE CLASS - 2 SEC. 3310.8.4 INADEQUATE SITE SAFETY LOGS. NOTED: AT THE TIME OF MY INSPECTION OF AN ACTIVE NEW BLDG PERMITTED JOB I ... $625 $0 May 17, 2021
Jun 30, 2020 35492150R RESOLVE CLASS - 1 REMOVED OHP CONTRARY TO APPROVED SSP. NOTED: AT THE TIME OF MY INSPECTION ON AN ACTIVE JOB SITE I OBSERVE OVERHEAD PR... $625 $0 Feb 18, 2021
May 8, 2020 35480513Z RESOLVE CLASS - 1 WORK DOES NOT CONFORM TO APPROVE CONSTRUCTION DOCUMENTS &/OR APPROVED AMENDMENTS. AT THE TIME OF MY INSPECTION,I OBSE... $2,530 $0 Sep 16, 2020
May 8, 2020 35480512R RESOLVE CLASS - 1 SEC. TITLE 28 ILLEGAL ENGAGING IN ANY BUSINESS OT OCCUPATION W/O A REQUIRED LICENSE OR OTHER AUTHORIZATION. AT THE TI... $5,000 $0 Sep 16, 2020
May 8, 2020 35480515M RESOLVE CLASS - 2 POSTING OF UNLAWFUL SIGNS,INFORMATION,PICTORIAL REP,BUSINESS OR ADVERTISING MESSAGES ON PROTECTION STRUCTURE. AT THE ... $0 $0 Sep 16, 2020
May 8, 2020 35480514K RESOLVE CLASS - 2 FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS. ATTHE TINE OF MY INSPECTION I OBSERVED THE HOUSEK... $0 $0 Sep 16, 2020
Feb 20, 2020 35469922M RESOLVE CLASS - 1 BC3303.7.2.FIRE EXTINGUISHERS(NOT MAINTAINED)AT TIME OF INSPECTION I OBSERVED ON ROOF, FIRE EXTINGUISHERS WAS PLACED ... $250 $0 Nov 19, 2020
Feb 5, 2020 38272927L RESOLVE CLASS - 1 97B17: (97-B-17) ELEVATORS MUST BE ON PERMANENT POWER. MUST DO A COMPLETE RE-TEST OF ELEVATOR WHEN BUILDING IS ON PER... $1,250 $0 Jan 25, 2021
Feb 5, 2020 38272928N RESOLVE CLASS - 1 97B17: (97-B-17) ELEVATOR MUST BE ON PERMANENT POWER. MUST DO A COMPLETE RETEST OF ELEVATOR WHEN BUILDING IS ON PERMA... $1,250 $0 Jan 25, 2021
Feb 5, 2020 38272929P RESOLVE CLASS - 1 97B17: (97-B-17) ELEVATOR MUST BE ON PERMANENT POWER. MUST DO A COMPLETE RE-TEST OF ELEVATOR WHEN BUILDING IS ON PERM... $1,250 $0 Jan 25, 2021
Feb 3, 2020 38272925H RESOLVE CLASS - 1 97X10:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE EQUIPMENT ELEVATOR BC 3001.2&27-297 DOB RECORDS ... $1,250 $0 Jan 25, 2021
Jan 7, 2020 35456132P RESOLVE CLASS - 2 FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING.NOTE:AT TIME OF MY INSPECTION OF A 26 STORY BLDGS TOPPED OFF AT ROOF CONSTR... $0 $0 May 13, 2020
Jan 3, 2020 35462633Y RESOLVE CLASS - 1 WORK DOES NOT CONFORM TO APPROVED CONSTRUCITON DOCUMENTS AND/OR APPROVED AMENDEMENTS.-TPP.AT TIME OF INSPECTION OF A ... $0 $0 Nov 30, 2020
Jan 3, 2020 35462635H RESOLVE CLASS - 2 FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS.AT TIME OF INSPECTION OF A 26 STORY NEW BUILDING U... $0 $0 May 6, 2020
Jan 3, 2020 35462631K RESOLVE CLASS - 1 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS.AT TIEM OF INSPECTION OF A 26 STO... $2,500 $0 Nov 30, 2020
Jan 3, 2020 35462632M RESOLVE CLASS - 1 FAILURE TO INSTITUTE/MAINTAIN SAFETY EQUIPMENT MEASURES OR TEMPORARY CONSTRUCTION-GUARD RAILS,PERIMETER PROJECTION.AT... $2,500 $0 Nov 30, 2020
Jan 3, 2020 35462630Z RESOLVE CLASS - 1 BC330345-FAILURE TO OBTAIN/PROVIDE FDNY PERMIT FOR GENERATOR AND FUEL TANK.AT TIME OF INSPECTION OF A 26 STORY NEW BU... $2,500 $0 Dec 7, 2020
Jan 3, 2020 35462629L RESOLVE CLASS - 2 FAILURE TO PROVIDE/MAINTAIN ADEQUATE/SAFE CONTROLLED ACCESS ZONE AT THE CONSTRUCTION SITE.AT TIME OF INSPECTION OF A ... $5,000 $0 Nov 30, 2020
Jan 3, 2020 35462634X RESOLVE CLASS - 2 FAILURE TO POST OR DISTRIBUTE SAFE CONSTRUCTION BILL OF RIGHTS.AT TIMEOF INSPECTION OF A 26 STORY NEW BUILDING UNDER ... $0 $0 Nov 30, 2020
Jan 3, 2020 35462628J RESOLVE CLASS - 2 FAILURE TO PROVIDE APPROVED/ACCEPTED DOCUMENTS AT TIME OF INSPECTION.AT TIME OF INSPECTION OF A 26 STORY BUILDING UND... $312 $0 Nov 30, 2020
Jan 3, 2020 35462627H RESOLVE CLASS - 1 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APROVED AMENDMENTS.AT TIME OF INSPECTION OF A 26 STOR... $2,500 $0 Nov 30, 2020
Dec 3, 2019 35424494X RESOLVE CLASS - 1 ELAVATOR AND HOIST DURING CONSTRUCTION OR DEMOLITION.NOTE:AT THE TIME OF MY INSPECTION RESPONDING TO A COMPLAINT THAT... $0 $0 May 24, 2021
Dec 3, 2019 35424496J RESOLVE CLASS - 2 FAILURE TO INSTITUTE AND MAINTAIN SAFETY EQUIPMENT MEASURES AND TEMPORARY CONSTRUCTION.NOTE:AT THE TIME OF INSPECTION... $5,000 $0 May 24, 2021
Dec 3, 2019 35424497L RESOLVE CLASS - 1 FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING AS PER SECTION REQUIREMENTS.NOTE:AT THE TIME OF INSPECTION OA A 26 STORY NE... $2,500 $0 May 24, 2021
Dec 3, 2019 35424495H RESOLVE CLASS - 1 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND /OR APPROVED AMENDMENTS.NOTE:AT THE TIME OF INSPECTION O... $0 $0 May 24, 2021
Nov 15, 2019 35461691H RESOLVE CLASS - 1 FAILURE TO MAINTAIN/DISPLAY ON SITE DOCUMENTS REQUIRED BY CHAPTER 33-CONCRETE SAFETY STRAP(D-RINGS)LETTER OF TRANSFER... $1,250 $0 Mar 8, 2021
Nov 15, 2019 35461692J RESOLVE CLASS - 1 FAILURE TO INSTITUTE SAFATY MEASURES AT JOBSITE. AT TIME OF INSPECTIONAT AN ACTIVE JOB SITE,I OBSERVED WORKER STANDIN... $0 $0 Jul 8, 2021
Nov 15, 2019 35461690X RESOLVE CLASS - 1 SEC. 3307.6.5.11 THE PERMIT HOLDER FAILED TO NOTIFY THE DEPT MORE THAN2 BUSSINESS DAY FOLLOWING THE REMOVAL OF SIDEWA... $0 $0 Mar 8, 2021
Aug 12, 2019 35438827M RESOLVE CLASS - 1 HOUSEKEEPING INADEQUATE. NB AT TIME OF MY INSPECTION OF 26 STY NEW BLDG TOPPED OFF AT ROOF. AT TIME JOB SITE I OBSERV... $625 $0 Dec 16, 2019
Jun 5, 2019 35435171P RESOLVE CLASS - 2 FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS. ATTHE TIME OF INSPECTION I OBSERVED PROPOSED 26 S... $0 $0 Sep 23, 2019
May 24, 2019 39003381J RESOLVE CLASS - 1 FAILURE TO PRODUCE DAILY LOG FOR INSPECTION. ATOI, HOLDER OF NB PERMIT #321228603 FAILED TO PRODUCE THE DAILY LOG THA... $0 $0 Jul 15, 2019
May 10, 2019 35425003R RESOLVE CLASS - 1 3301.12 FAILURE TO PROVIDE PRE-SHIFT SAFETY MEETING.AT TIME OF MY INSPECTION OBSERVED ACTIVE JOB SITE.WORKER FELL OFF... $625 $0 Aug 26, 2019