Maintenance code violations

46-62 Tennis Court, Brooklyn • Block 05100 • Lot 0056

262 records

HPD grades a violation A for non-hazardous through C for immediately hazardous.

Issued Class Status Violation Apartment Correct by
May 30, 2017 B VIOLATION CLOSED § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK WALL AT UPPER EAST SECTION IN ... 5F Jul 4, 2017
May 30, 2017 A VIOLATION DISMISSED § 27-2005 ADM CODE REFIT DOOR AT SOUTH WALL CABINET IN THE KITCHEN LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM N... 5F Sep 2, 2017
May 30, 2017 B VIOLATION CLOSED § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL FLOOR TILES IN THE KITCHEN LOC... 5F Jul 4, 2017
May 30, 2017 B VIOLATION CLOSED § 27-2005 ADM CODE PROPERLY SECURE THE LOOSE CERAMIC WALL TILES IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APA... 5F Jul 4, 2017
May 30, 2017 B VIOLATION CLOSED § 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET .. IN ... 5F Jul 4, 2017
Mar 13, 2017 C VIOLATION DISMISSED § 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICAT... 4F Apr 10, 2017
Mar 10, 2017 C VIOLATION CLOSED § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE GLASS AT THE BUILDING ENTRANCE DOOR Mar 18, 2017
Feb 15, 2017 A VIOLATION CLOSED § 27-2026 ADM CODE RESET, SO AS TO SECURE A PROPER AND TIGHT CONNECTION, THE WATER CLOSET BOWL .. IN THE BATHROOM LOC... 4F May 21, 2017
Feb 15, 2017 A VIOLATION CLOSED § 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 4F, 4th STORY, 1st... 4F May 21, 2017
Feb 15, 2017 A VIOLATION CLOSED § 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE ... May 21, 2017
Feb 15, 2017 C VIOLATION DISMISSED § 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICAT... 4F Mar 15, 2017
Feb 15, 2017 A NOT COMPLIED WITH § 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL OUTLET CAP AT PUBLIC HALL, 1st STORY May 21, 2017
Feb 15, 2017 B VIOLATION DISMISSED § 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). INOPERATIVE LOCATED AT APT 4F, 4th STORY,... 4F Mar 22, 2017
Feb 15, 2017 B VIOLATION DISMISSED § 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR INOPERATIVE LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM ... 4F Mar 22, 2017
Feb 15, 2017 A VIOLATION CLOSED § 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET .. IN ... 4F May 21, 2017
Sep 12, 2016 A VIOLATION DISMISSED § 27-2005 ADM CODE REFIT BULK HEAD DOOR TO CLOSE PROPERLY LEADING TO ROOF AT PUBLIC HALL STAIRS, 6th STORY Dec 16, 2016
Sep 12, 2016 C VIOLATION DISMISSED § 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) THROUGHOUT THE PUBLIC AREAS IN AC... Oct 10, 2016
Sep 12, 2016 B VIOLATION DISMISSED § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDED WALLS AT BULK HEAD DOO... Oct 17, 2016
Sep 12, 2016 B VIOLATION DISMISSED § 27-2005, 2007 ADM CODE ARRANGE AND MAKE SELF-CLOSING THE DOORS BULK HEAD DOOR LEADING ON TO ROOF AT PUBLIC HALL STA... Oct 17, 2016
Sep 12, 2016 B VIOLATION DISMISSED § 27-2005 ADM CODE PROPERLY SECURE THE LOOSE HAND RAIL AT PUBLIC HALL STAIRS, 5th STORY Oct 17, 2016
Sep 12, 2016 B VIOLATION DISMISSED § 27-2005 ADM CODE PROPERLY SECURE THE LOOSE HAND RAIL AT PUBLIC HALL STAIRS, 4th STORY Oct 17, 2016
Jul 5, 2016 B VIOLATION CLOSED SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN TH... 2F Aug 9, 2016
Jul 5, 2016 B VIOLATION CLOSED SECTION 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHRO... 2F Aug 9, 2016
Jul 5, 2016 B VIOLATION CLOSED SECTION 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHE... 2F Aug 9, 2016
May 6, 2016 C VIOLATION CLOSED § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CEMENT TREADS 1ST AND 2ND UP STAIRS ... May 14, 2016
Apr 22, 2016 B VIOLATION CLOSED § 27-2005 ADM CODE PROVIDE (IN THE EVENT OF A POWER OUTAGE) AN ACCEPTABLE HEAVY-DUTY LOCK-AND-LATCH SET ON STREET ENT... May 27, 2016
Apr 22, 2016 C VIOLATION CLOSED § 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF AN UNACCEPTABLE ELECTROMAGNETIC LOCKING DEVICE IN... Apr 30, 2016
Apr 22, 2016 A VIOLATION CLOSED SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING I... 5C Jul 26, 2016
Apr 22, 2016 B VIOLATION CLOSED § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK FROM THE CEILING IN THE BATHRO... 5C May 27, 2016
Apr 22, 2016 A VIOLATION CLOSED SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING I... 5C Jul 26, 2016
Apr 22, 2016 B VIOLATION CLOSED § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING IN THE 3rd ROOM... 5C May 27, 2016
Dec 15, 2015 B VIOLATION DISMISSED SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING I... 3K Jan 19, 2016
Dec 15, 2015 A VIOLATION CLOSED § 27-2026 ADM CODE RESET, SO AS TO SECURE A PROPER AND TIGHT CONNECTION, THE WATER CLOSET BOWL ... IN THE BATHROOM LO... 3K Mar 19, 2016
Dec 15, 2015 A VIOLATION CLOSED § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL WALLS AND CEILING IN THE... 3K Mar 19, 2016
Dec 15, 2015 B VIOLATION DISMISSED SECTION 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE MORTISE LOCK AT DOOR IN THE ENTRANCE LOCATED AT APT ... 3K Jan 19, 2016
Dec 15, 2015 A VIOLATION CLOSED § 27-2005 ADM CODE PROPERLY SECURE THE LOOSE DOOR AT BASE CABINET IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 1st AP... 3K Mar 19, 2016
Dec 3, 2015 B VIOLATION CLOSED § 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE CERAMIC TILES AT SHOWER EXTERIOR AND INTERIOR WALLS IN TH... 4F Jan 7, 2016
Dec 3, 2015 B VIOLATION CLOSED § 27-2005 ADM CODE REPLACE WITH NEW THE MISSING SHOWERBODY AND SHOWER HEAD IN THE BATHROOM LOCATED AT APT 4F, 4th STO... 4F Jan 7, 2016
Dec 3, 2015 B VIOLATION CLOSED § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILE FLOOR IN THE BATHROOM L... 4F Jan 7, 2016
Dec 1, 2015 B VIOLATION CLOSED § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR HOLE IN THE KITCHEN LOCAT... 4F Jan 5, 2016
Dec 1, 2015 C VIOLATION CLOSED § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS ... 4F Dec 29, 2015
Dec 1, 2015 B VIOLATION CLOSED § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR , EAST WALL, SOUTH ... 4F Jan 5, 2016
Dec 1, 2015 A VIOLATION CLOSED § 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION , 1st DOOR FROM SOUTH AT WEST WALL, 1st DOOR FRAME... 4F Mar 5, 2016
Dec 1, 2015 B VIOLATION CLOSED § 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES FROM WEST WALL SWITCH TO ... 4F Jan 5, 2016
Dec 1, 2015 A VIOLATION CLOSED § 27-2005 ADM CODE REPLACE WITH NEW THE MISSING GLASS GLOBE AT CEILING LIGHT FIXTURE IN THE 1st ROOM FROM EAST AT NOR... 4F Mar 5, 2016
Dec 1, 2015 B VIOLATION CLOSED § 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF LOOSE AND HANGING ELECTRIC WIRES AT NORTH CLOSET IN... 4F Jan 5, 2016
Dec 1, 2015 B VIOLATION CLOSED § 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT WASH BASIN IN THE BATHROOM LOCATED AT APT 4F, 4th STO... 4F Jan 5, 2016
Feb 3, 2015 B VIOLATION CLOSED SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND S... 2C Mar 10, 2015
Feb 3, 2015 B VIOLATION CLOSED SECTION 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 2C, 2nd STORY, 2nd APARTMENT FRO... 2C Mar 10, 2015
Feb 3, 2015 B VIOLATION CLOSED SECTION 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACC... 2C Mar 10, 2015