Issued Violation Status Severity Description Penalty Balance due Hearing
Jan 4, 2024 39102731Y ACTIVE CLASS - 2 OBTAIN CERTIFICATE OF COMPLIANCE FOR THIS DEVICE. $3,125 $3,125 Sep 23, 2024
Oct 18, 2023 39097324N ACTIVE CLASS - 1 ONLY ELEVATOR IN THE BUILDING OUT OF SERVICE NO PERMIT POSTED. RESTORE TO SERVICE TO SERVICE IMMEDIATELY AND CONTACT ... $12,500 $12,500 Jun 24, 2024
Sep 8, 2023 39094386P RESOLVE CLASS - 1 THE ONLY ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT... $3,125 $3,125 Jun 16, 2025
Aug 8, 2023 39092064N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSP... $1,250 $1,250 May 9, 2024
Jun 26, 2023 39089193M RESOLVE CLASS - 1 (ONLY ELEVATOR IN THE BUILDING) OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE. REMEDY: RE... $3,125 $3,125 Jun 26, 2024
Jun 8, 2022 39063749N ACTIVE CLASS - 2 CORRODED FLUE PIPE. MISSING MANUAL LOW WATER CUT OFF.BOILER SECTION LEAKING. $312 $312 Jan 18, 2023
Feb 10, 2022 39055970M ACTIVE CLASS - 1 DLM IMPROPERLY INSTALLED ON THIS DEVICE. NO FIREMANS' SERVICE PRESENT IN CONTROLLER. INSTALL FIREMANS' SERVICE SO DLM... $1,250 $1,250 Dec 7, 2022
Dec 1, 2021 39052035H ACTIVE CLASS - 1 CLASS 1 ITEM: MISSING DLM AS NOW REQUIRED BY CODE. CLASS 2 ITEMS: ADJUST FLOOR STOPS. REPAIR CAR PHONE. MISSING IN CA... $1,250 $1,250 Dec 7, 2022
Jan 7, 2021 39034501R ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $1,250 $1,250 May 7, 2026
Sep 8, 2020 39028248L ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $6,250 $6,250 Sep 10, 2021
Jun 2, 2020 39023327R ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $6,250 $6,250 Sep 3, 2021
Apr 14, 2020 39021105M ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $6,250 $6,250 Jul 14, 2021
Mar 5, 2020 39019030Y ACTIVE CLASS - 1 C/U SECURE BASEMENT HOIST DOOR....NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPE... $6,250 $6,250 Sep 21, 2020
Jan 22, 2019 38267421H RESOLVE CLASS - 2 05I10,41D06,39P16,59M07,68M07,70P16,10H11. 05I10-CAR DOOR DAMAGED REPAIR; 10H11-CAR DORO GIBS WORN REPLACE; 39P16-NO ... $0 $0 Apr 29, 2019
Nov 27, 2018 38266575X RESOLVE CLASS - 1 CU42N9,59M7,67X10. CU42N09-TWO FUSE BYPASS ON CONTROLLER; 59M7-BRAKE MAINTENANCE EXPIRED; 67X10- CAR PHONE INOPERATIVE. $0 $0 Feb 21, 2020
Sep 19, 2018 38264804L RESOLVE CLASS - 1 39X10,42N11,59BB7,56Y10,56Y13,16B10,68M7. 39X-REPIAR STOP SW ON TOP OF CAR. 42N-REPLACE BYPASSED FUSE ON THE CONTROLL... $0 $0 Feb 14, 2020
Apr 11, 2018 38262578N ACTIVE CLASS - 1 97X17. THE ONLY ELEVATOR IN BLDG OUT OF SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A ... $1,250 $1,250 Dec 12, 2018
Dec 19, 2017 38260115H ACTIVE CLASS - 2 8V1,5E1,10H11,11L10,29J1,99BB5,68M7,56Y2,56Y13-8V1)CAR FLOOR LANDING SILL NOT LEVEL, ADJUST. 5E1)CAR DOOR RUBBING, AD... $250 $250 Dec 5, 2018
May 23, 2017 38255625L RESOLVE CLASS - 2 8V1,5E1,10H11,16J10,29J1,56Y2,56Y13,11L10,70M7. 8V1-CAR FLOOR TO LANDING SILL NOT LEVEL ADJUST; 5E1-CAR DOOR RUBBING ... $0 $0 Sep 6, 2017
Mar 1, 2017 38253439Z ACTIVE CLASS - 2 8V1 CAR FLOOR TO LANDING SILL IN UP DIRECTION NOT LEVEL ADJUST $250 $0 Jul 19, 2017
Feb 6, 2017 38253278R ACTIVE CLASS - 2 10H11,1B11,1B10,39M7,58Y13,60M7,70P16,70O2. 1B11 OR 10 - CORRECT ALARM BELL TO EM STOP SWITCH; 39M7-PROVIDE 5YEAR TES... $500 $0 Jul 3, 2017
Dec 18, 2016 38251642P ACTIVE CLASS - 1 97X17 THE ONLY ELEVATOR IN BUILDING IS OUT OF SERVICE.UPON INSPECTIONTHE DEVICE IS FOUND TO BE OUT OF SERVICE CREATIN... $1,000 $0 Oct 25, 2017
Apr 20, 2016 38242158Z ACTIVE CLASS - 2 05X10 EXCESSIVE GAP BETWEEN THE REAR SIDE OF THE DOOR AND THE FRAME $4,000 $0 Jun 13, 2016
Apr 18, 2016 38240613M RESOLVE CLASS - 1 16I11 HOISTWAY DOOR DAMAGED REPAIR/REPLACE BASEMENT. $0 $0 Jul 29, 2016
Apr 8, 2016 38240612K RESOLVE CLASS - 1 16R09,21R11,70M07. 16R09-HOISTWAY DOOR ILLEGAL REMOVE DEADBOLT LOCK ONBASEMENT DOOR; 21411-INTERLOCK ILLEGAL REMOVE/R... $0 $0 Nov 23, 2016
Apr 6, 2016 38239829N RESOLVE CLASS - 1 CU72M07,16I11,02X10,67X10,59M07,60M07,58B07,70O02.CU-72M07-PIT STOPSW ITCH MISSING; 16I11-BASEMENT HOISTWAY DOOR DAMA... $0 $0 Nov 14, 2016
Mar 30, 2016 35176661Y RESOLVE CLASS - 2 WORK W/O A PERMIT. NOTED: IN APT 3C ERECTED NON-BEARING PARTITIONS CREATING TWO ADDITIONAL BEDROOMS,ONE OF EACH DOES ... $0 $0 Jul 25, 2016
Oct 28, 2015 38239020Z RESOLVE CLASS - 2 02X10,70O02,25M07. 02X-ALARM BELL INOPERATIVE; 70O-PIT DIRTY; 25M-ELEVATOR EMERG FIRE SIGNAGE MISSING ALL FLRS. $500 $0 Jun 13, 2016
Oct 16, 2015 38238490Z ACTIVE CLASS - 1 05B01 EXCESSIVE GAP IN CAR DOOR. $2,500 $0 Jun 1, 2016
Oct 15, 2015 38238489L ACTIVE CLASS - 1 05B01,40P11. 05B01-EXCESSIVE GAP IN CAR DOOR; 40P16-PROVIDE ACCESS TO MOTOR ROOM. $2,500 $0 May 23, 2016
Sep 4, 2015 32075727X ACTIVE CLASS - 2 B254,34A,34B,40,32A,50A,50B,50C,50D,50E,50F. 50A-FLUE PIPE NOT PROPERLY SEALED TO CHIMNEY; 50B-FLUE PIPE NEED TO BE S... $500 $0 Oct 26, 2015
Jan 5, 2015 38234272M ACTIVE CLASS - 2 67X10,14H11,12Q03,100M07,08V01,76Q03,39D06,37Y02,27BB15,41D06,56Y13,40Y02,42M07,40M07,60Q03,42G11,16H1Q1,05J01,77B11,... $2,500 $0 Feb 23, 2015
May 5, 2014 38231339Y RESOLVE CLASS - 2 67X10,12Q03,10H11,05J01,76Q03,39X10,39Q03,37Y02,27BB05,16H11,08V01,61L10,60Q03,42G11,40M07,40Y02,42H11,59H11,14H11,70... $0 $0 Jan 26, 2015
Apr 22, 2014 38231126K RESOLVE CLASS - 2 67X10,39M07,60B07,69M07,41D06,16P16.67-X-10 PHONE INOPERATIVE 39-M-07 MISSING GUARD ON TOP OF CAR 60-B-07 INSUFFICIEN... $0 $0 Feb 2, 2015
Feb 5, 2014 38230056J ACTIVE CLASS - 2 67X10,16I10,20I07,69M07,60Q07,97O02. 67X- PHONE INOPERATIVE. 16I- BASEMENT DOOR BROKEN NO ACCESS TO PIT. 20I- BROKEN ... $500 $0 Mar 24, 2014
Aug 16, 2011 38217674K ACTIVE CLASS - 2 01B10,10H11,12Q03,14O02,24X11,39M07,39O02,40Z10,41I10,53H14,52B07,58E10,60Q03,61R10,64M07,67M07,68M07,69M07,70O02,70K... $500 $0 Oct 3, 2011
Mar 24, 2009 34767845R ACTIVE CLASS - 2 WORK W/O PERMIT. NOTED: AT CELLAR LEVEL ERECTED PARTITIONS CREATING CLASS A APTS W/ 2 ROOMS KITCHEN W/GAS CONNECTION ... $4,000 $0 May 18, 2009
Mar 19, 2008 34640746N ACTIVE Non-Hazardous FAILURE TO MAINTAIN BLDG. NOTE: AT NORTH SIDE OF PREMISES 5' HIGH PERIMETER YARD FENCE BROKEN BEING HELD UP BY WIRES.... $350 $0 Aug 3, 2009
Sep 25, 2007 34607918X ACTIVE Hazardous FAILURE TO COMPLY W/ COMMISSIONER ORDER TO CORRECT VIOL # 34555329X FOR WORK W/O PERMIT @ CELLAR INSTALLED 3 PC BATHR... $5,000 $0 Nov 19, 2007
May 23, 2007 34577389P ACTIVE Non-Hazardous USE OF ILLEGAL HARDWARE. NOTE IN BASEMENT APT NON FIRE DEPARTMENT APPROVED GATES INSTALLED AT ALL WINDOWS & SCREWED/ ... $350 $0 Aug 3, 2009
May 23, 2007 34577390M ACTIVE Hazardous OCCUPANCY CONTRARY TO DOB RECORDS. NOTE: IN CELLAR AT REAR 1 CLASS A APT OCCUPIED BY 3 ADULTS & 1 CHILD.(OCCUPANT IS ... $800 $0 Jul 24, 2008
May 23, 2007 34577388N ACTIVE Hazardous FAILURE TO COMPLY WITH AN ORDER OF THE DEPT TO CORRECT VIO #34555329X FOR WORK W/O PERMIT.1-CELLAR ERECTED PARTITIONS... $1,500 $0 Dec 22, 2009
Jan 19, 2007 34555328Y ACTIVE Hazardous OCCUPANCY CONTRARY TO THAT ALLOWED BY BLDG DEPT RECORDS.ILLEGAL OCCUPANCY NOTED:AT CELLAR LEVEL OF ABOVE PREMISES FUL... $2,500 $0 Mar 31, 2008
Jan 19, 2007 34555329X ACTIVE Hazardous WORK W/O A PERMIT.WORK NOTED:AT CELLAR LEVEL OF ABOVE PREMISES FULL HEIGHT PARTITION WALLS WERE ERECTED & NEW PLUMBIN... $800 $0 Dec 8, 2008
Jul 2, 1997 38061603P ACTIVE Non-Hazardous 36T31Q36L57O30O 36-PROVIDE LOCK & SELF CLOSING DEVICE 31-EXPOSED WIRES ON CAR TOP. $100 $0 Nov 17, 1997