ECB violations
1086-1088 Flatbush Avenue, Brooklyn • Block 05164 • Lot 0009
19 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 6, 2017 | 35307208N | RESOLVE | CLASS - 2 | FAILURE TO CONDUCT OR FILE A FINAL INSPECTION FOR COMPLETED WORK WITHIN 1 YEAR OF PERMIT EXPIRATION.ALT JOB # 3201760... | $400 | $0 | Mar 19, 2018 |
| May 8, 2017 | 32088434P | RESOLVE | CLASS - 2 | 5B,15,24A,32A,34B,38,48A,50, 50A, 50B,50C,50,50E,50F 50-STEAM CONTROLPIPING INCORRECT; 50A-SPILL SWITCH DEFETIVE; 50B... | $500 | $0 | Jun 26, 2017 |
| Jul 7, 2011 | 32070573J | RESOLVE | CLASS - 1 | 50A 32 50B 51. FULTON VT BOILER, 10HP, NB 39968, OIL-FIRED YR 1981. 50A-EVIDENCE OF ADVANCED INTERNAL & PROGRESSIVE (... | $0 | $0 | Aug 22, 2011 |
| Aug 4, 2009 | 32066638J | RESOLVE | CLASS - 1 | 18A,32A,50A,50B,50C,50D. 50A BOILER BLOW DOEN HAS A LOW PRESSURE VALVE125 PSI MUST BE H/P RATED VALVE 50B DRAFT INDUC... | $2,500 | -$2,500 | Apr 12, 2010 |
| Apr 21, 2008 | 32056401M | RESOLVE | Non-Hazardous | FULTON V.T BOILER 10HP NB 39668 OIL FD 1981 50A DETERIORATED SLEEVES AT COMBUSTIBLE CHAMBER PORTS AT UPPER AND LOWER ... | $180 | $0 | Jun 16, 2008 |
| Sep 25, 2007 | 34607917Y | RESOLVE | Hazardous | FAILURE TO COMPLY W/COMM'S ORDER TO CORRECT VIO#34555930R FOR WORK W/OA PERMIT ILLEGAL WALLS ERECTED IN BDRMS SUBDIVI... | $3,000 | $0 | Oct 20, 2009 |
| Sep 25, 2007 | 34607916M | RESOLVE | Hazardous | FAILURE TO MAINTAIN NOTE:WOOD STAIRCASE IS IN DISREPAIR STEP#6(1ST & 2ND FL)IS LOOSE,ROCKING & W/O ADEQUATE SUPPORT.R... | $800 | $0 | Jan 7, 2008 |
| May 23, 2007 | 34577391Y | RESOLVE | Non-Hazardous | FAILURE TO COMPLY WITH AN ORDER OF THE DEPARTMENT TO CORRECT VIO# 34555930R FOR WORK W/O PERMIT-ILLEGAL SUBDIVIDINGS ... | $1,500 | $0 | Oct 13, 2009 |
| Jan 22, 2007 | 34555930R | RESOLVE | Hazardous | WORK W/O A PERMIT. HAZARDOUS. NOTED: IN APT #2L &2R A BEDRM IS CREATED, W/ FULL HEIGHT. PARTITIONS, ILLEGALLY (IN EAC... | $800 | $0 | Sep 15, 2009 |
| Sep 9, 2006 | 32051190Z | RESOLVE | Non-Hazardous | 48A,B,50A,B. FUCTON V.T BOILER, 10 HP, NB 39668, GAS, 1987. 50A-NO SECONDARY LOW WATER CUT OFF MANUAL RESET SWITCH IS... | $2,500 | $0 | Oct 23, 2006 |
| Jan 29, 2005 | 32047125K | RESOLVE | Hazardous | BQ9/4A/19B/36 CROWN BOILER 50A)PIPE SAFETY VALVE DISCHARGE DOWN TO A SAFE POINT. | $5,000 | $0 | Mar 14, 2005 |
| Jan 29, 2005 | 32047024L | RESOLVE | Non-Hazardous | 48B/50A/50B/50C 1981 FULTON NATL BD 39668 50A)ADD A SLOW OPENING VALVE ON THE BOTTOM BLOWDOWN LINE 50B)PROVIDE PROTEC... | $2,500 | $0 | Mar 14, 2005 |
| Aug 7, 2002 | 32034581L | RESOLVE | Non-Hazardous | 18A-18B-48A-48B-49. 49-THREADED END ON SAFETY VALVE DISCHARGE PIPE. 18A-B CORRORED CEAILING HANDHROOP 48AB DIRTY LEAR... | $0 | $0 | Sep 23, 2002 |
| Feb 23, 2001 | 32024723Z | RESOLVE | Hazardous | 32A,38,48A,49A,49B,49C.49A-CHIMNEY NOT SEALED.B-WATER LEAK AT MIXING VALVE.C-DEBRIS AND GARBAGE IN BOILER ROOM.HB SMI... | $2,500 | $0 | Apr 30, 2001 |
| Nov 29, 2000 | 32019792X | RESOLVE | Non-Hazardous | 49) MUST INSTALL SECOND SHUT OFF VALUE ON WATER COLOM, WATER COLOM DRAIN LINE REDUCED, HANDHOLE SLEEVES CORRODED NEED... | $0 | $0 | Feb 12, 2001 |
| Nov 20, 2000 | 32020997H | RESOLVE | Hazardous | 1 32A 38 48A 49A,B,C, 51. H.B.SMITH GAS FIRED STEAM BOILER.49A)CHIMNEY NOT SEALED/NO CLEANOUT DOOR.49B)WATER LEAK AT ... | $400 | $0 | Jul 2, 2001 |
| Oct 30, 2000 | 32020996X | RESOLVE | Hazardous | 32A 38 48A 49A,B,C 51. H.B.SMITH GAS FIRED STEAM BOILER.49A)CHIMNEY NOT SEALED/CLEANOUT DOOR MISSING.49B)MIXING VALVE... | $400 | $0 | Jul 2, 2001 |
| Oct 30, 2000 | 32020983R | RESOLVE | Hazardous | 32A,38,48A,51,49A,49B.HB SMITH-GAS FIRED-STEAM BOILER.49A-CHIMEY NOT SEALED-CLEANOUT DOOR MISSING.49B-MIXING VALVE LE... | $0 | $0 | Sep 4, 2001 |
| Dec 21, 1992 | 34083790L | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE MAINTAIN FIRE STOPPING WHERE REQUESTED. STAIRWELL FROM AT 1ST FLOOR INTO CELLAR DOES NOT HAVE THE ... | $500 | $0 | Feb 1, 1993 |