Skip to content

ECB violations

1914-1926 Nostrand Avenue, Brooklyn • Block 05216 • Lot 0060

89 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Feb 20, 2024 39106382N ACTIVE CLASS - 2 REPAIR WHEELHOUSE DOOR LOCK. ADJUST DOOR CLOSING TIME. REPAIR CAR PHONE. SEAL HOIST MACHINE LEAKS. OIL LEAKING ONTO B... $3,125 $3,125 May 1, 2024
May 13, 2021 39041142J RESOLVE CLASS - 2 PERFORM BRAKE MAINTENANCE AND PROVIDE BRAKE TAG WITH FULL DATE ENTERED MM/DD/YEAR., PROVIDE MOTOR ROOM LIGHT GUARD., ... $1,563 $1 Nov 1, 2021
Dec 31, 2019 38272833K ACTIVE CLASS - 2 37M07, 70O02, 40O02: 37-M-07 PROVIDE LADDER/STAIRS TO ACCESS OVERHEAD ROOM SAFELY, 70-O-02 CLEAN PIT, 40-O-02 CLEAN M... $6,250 $6,250 Jan 28, 2021
Dec 12, 2018 38266850L RESOLVE CLASS - 2 37M07,57BB07,56Y13,56O02,59BB07,77Q07. 37M07-PROVIDE STAIRS TO ACCESSOVERHEAD; 57BB07-SERVICE FIRE EXTINGUISHER AND P... $655 $0 Mar 18, 2019
Dec 13, 2016 38251469K ACTIVE CLASS - 1 52K11. HOIST CABLES RUSTY, REPAIR. $1,000 $0 Jun 28, 2017
Sep 6, 2016 38245867P RESOLVE CLASS - 2 59M7,60Q07,67X10,80M7. 59M-BRAKE TAG MISSING (PROVIDE) 60Q7-LIGHTING MACHINE SPACE UNGUARDED (PROVIDE. 67X10-CAR PHON... $0 $0 Apr 10, 2017
Jun 14, 2016 38243434K RESOLVE CLASS - 1 97X10 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.SERVICE EQUIPMENT ELEVAOTR AS PER BC 3001.2 AND 27-987. D... $1,000 $0 Aug 17, 2016
Mar 22, 2016 35140397J RESOLVE CLASS - 1 WORK WITHOUT PERMIT. TIME OF INSPECTION 1:30PM ABOVE THE DATE. AT TIMEOF INSPECTION I OBSERVED ILLEGAL GAS CONNECTION... $0 $0 May 9, 2016
Jan 7, 2016 35148528R RESOLVE CLASS - 2 SEC. 28-201.2 FAILURE TO MAINTAIN SIDEWALK SHED AS REQUIRED BY CODE. NOTE: AT TIME OF INSPECITON,SIDEWALK SHED ERECTE... $0 $0 Feb 29, 2016
Jan 7, 2016 35148527P RESOLVE CLASS - 2 SEC. 3307.6.5 FAILURE TO MAINTAIN ADEQUATE ILLUMINATION BENEATH SIDEWALK SHED AS REQUIRED BY CODE. NOTE: SIDEWALK SHE... $0 $0 Feb 29, 2016
Oct 28, 2015 32075859H ACTIVE CLASS - 2 B254,50,50A,50B,50C. 50-STORAGE AND DEBRIS BLOCKING OUTSIDE FRESH AIRINLET TO BOILER ROOM; 50A-EXPOSED WOOD IN BOILER... $250 $0 Dec 14, 2015
Jun 1, 2015 38236457H RESOLVE CLASS - 2 05J01,100M07,67L10,05M07,52Q03,37T07,05R09,61G11,56Y13,52K11,52B14,16I10,16R09,70O02. 05J-GAP AT STRIKE POST; 100M-IN... $500 $0 Jul 20, 2015
Mar 4, 2015 32075081X RESOLVE CLASS - 2 B254,15,16,50A,50B,50C,50D,50E. 50A-NO SMOKE ALARM 30GPH; 50B-PIGTAIL TO BE BRASS; 50C-OIL SUPPLY PUMP TO HAVE GUARD;... $500 $0 Apr 20, 2015
Jan 7, 2015 32074893R RESOLVE CLASS - 2 B254,28A,28B,28C,50A. 50A-REPLACE PLUGGED TUBES. $500 $0 Sep 14, 2015
May 17, 2014 35010934K ACTIVE CLASS - 2 FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES-NOTED:@ TIME OF INSPOBSERVED CRACKS BATH VERTICAL,& STEPPED FORMING... $500 $0 Nov 10, 2014
Mar 10, 2014 35038073M RESOLVE CLASS - 2 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIAL,DEVICES,APPLIANCES OR WIRING IN USE.UNDER CANOPY... $400 $0 Nov 14, 2014
Mar 10, 2014 35038071Z RESOLVE CLASS - 2 ELECTRICAL WORK W/O A PERMIT. BRANCH CIRCUIT,FIXTURES,FRONT OF BLDG UNDER CANOPY. OBTAIN A PERMIT $400 $0 Nov 14, 2014
Feb 19, 2014 35038739J RESOLVE CLASS - 2 UNAPPROVED UNSAFE UNSUITALBE ELECTRICAL EQUIPMENT DEVICES MATERIALS APPARATUS APPLIANCES OR WIRING IN USE. (4) 8' FLU... $400 $0 Apr 7, 2014
Feb 19, 2014 35038740R ACTIVE CLASS - 2 FAIL TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS/ENCLOSURES/CABLE ARMOR. RACEWAY FEEDING FLUORESCEN... $600 $0 Apr 8, 2014
Feb 19, 2014 35038741Z ACTIVE CLASS - 1 OPEN WIRING UNDER AWNING. ELECTRICAL WIRING 8' FIXTURES UNDER AWNING NOT PROVIDED IN RACEWAY. REMEDY: COMPLY W/EC CODE. $1,600 $0 Apr 8, 2014
Jan 8, 2014 35081219J ACTIVE CLASS - 2 FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES.NOTED @ REAR OF BLDG EXP 3SLIGHT HAIRLING CRACKS OBSERVED @GROUND LEV... $500 $0 Feb 24, 2014
Jul 13, 2013 35050574M RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOV #34893444N ISSUED ON 1.13.11 FOR WORK W/O A PERMIT - IN... $12,000 $0 Sep 9, 2013
May 17, 2013 35060154P RESOLVE CLASS - 1 FAILURE TO COMPLY W/COMMISSIONER'S ORDER CONTAINED IN NOV#34893444N ISSUED ON 1/13/11. (INSTALLING GAS & PLUMBING LIN... $24,000 $0 Jul 1, 2013
Mar 29, 2013 38226142Y RESOLVE CLASS - 2 09B07,16I10,40P07. PEOPLE COMPLAINING OF SADDLE,WHERE IT IS CUT,PROVIDE FILLER OR REPLACE W/LONGER SADDLE IF POSSIBLE... $2,500 $0 May 13, 2013
Mar 22, 2013 38225513J RESOLVE CLASS - 2 16D10,70O02,16##,16B04. 16D10-BASEMENT DORO LOCK RUBBING AGAINST ELEVATOR; 16B04-PATCH HOLE ON BASEMENT DOOR; 16##-RE... $2,500 $0 May 6, 2013
Jan 3, 2013 35002612H RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER TO CORRECT CONDITIONS CITED IN NOV #34893444N ISSUED ON 1.13.11 FOR INST... $24,000 $0 Feb 25, 2013
Oct 23, 2012 32072515K RESOLVE CLASS - 2 B254,6A,15,34B,50,50A,B. 50- GAS PIOLITE REGULATOR MISSING VEUT LIMMITER. 50A- OIL PUMP MISSING BELT GUARD. 50B- GAS ... $2,500 $0 Dec 10, 2012
Jul 24, 2012 34988092K RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOV #34893444N ISSUED ON 1.13.11 FOR WORK W/O PERMIT - CELL... $24,000 $0 Sep 10, 2012
Mar 10, 2012 32071778H RESOLVE CLASS - 3 B354,16,5B,50A,B,C,D,E. 50A- BRASS PIGTAIL REQUIRED FOR PRESSURE GAUGE. 50B- GUARD MISSING ON OIL SUPPLY PUMP. 50C- B... $500 $0 Apr 30, 2012
Mar 1, 2012 34964320R RESOLVE CLASS - 1 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN NOTICE OFVIOLATION #348934 ISSUED ON 1-13-11. THE RESPON... $12,000 $0 Apr 16, 2012
Nov 15, 2011 32071532H RESOLVE CLASS - 3 B354,50A,50B,50C, 50A-REMOVE WASTE OIL FROM BOILER ROOM 50B-LABE JUEL CUT OFF SWITCH OUTSIDE OF BOILER ROOM DOOR 50C-... $200 -$23 Jan 9, 2012
Sep 13, 2011 34961383K RESOLVE CLASS - 1 FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN NOTICE OF VIOLATION# 34893444N ISSUED ON 01/13/11. FOR WO... $12,000 $0 Oct 31, 2011
Jul 28, 2011 34960565R RESOLVE CLASS - 1 FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOTICE OF VIOLATION #34893444N ISSUED ON 1/13/11. REMEDY: C... $2,400 $0 Nov 14, 2011
May 26, 2011 34919051P RESOLVE CLASS - 1 FAILURE TO COMPLY W/ THE COMM ORDER TO CORRECT VIOLATING CONDITIONS NOTED IN ECB NOV#34893444N FOR WORK W/O A PERMIT ... $12,000 $0 Jul 11, 2011
Apr 1, 2011 34905891K RESOLVE CLASS - 3 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.FRONT ENTRANCE-1)MISSING RAILINGS @ EXTERIOR FRONT ENTRANCE LANDING... $500 $0 May 16, 2011
Mar 17, 2011 34905706J RESOLVE CLASS - 1 FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. RESPONDENT FAILED TOCORRECT CONDITIONS CITED ON ECB VIO 34893444N F... $12,000 $0 May 9, 2011
Jan 13, 2011 34893444N RESOLVE CLASS - 1 WORK W/O PERMIT; ILLEGAL WORK NOTED AT CELLAR 1 CLASS'A' APT W/3PCS BATHROOM RESIDENTIAL SINK,TOILET,SHOWER,WATER,WAS... $16,000 $0 Feb 28, 2011
Jan 13, 2011 34893443L RESOLVE CLASS - 2 RESIDENCE ALTERED FOR OCCUPANCY AS A DWELLING FOR MORE THAN THE LEGALLY APPROVED # OF FAMILIES.NOTED:CELLAR LEVEL CLA... $0 $0 Aug 8, 2011
Oct 20, 2010 32069716J RESOLVE CLASS - 2 16/50A/50B/50C/50D/50E 50A-REMOVE ALL STORAGE 50B-REMOVED ALL FLAMABLES 50C-OPEN CONTAINERS OF FUEL OIL 50D-NO TEST C... $2,500 $0 Dec 13, 2010
Apr 6, 2010 32068459N RESOLVE CLASS - 3 15,21C,34B,40,48A,50A-REMOVE ALL STORAGE FROM BOILER ROOM. $100 $0 Jun 7, 2010
Feb 24, 2010 38208873Z RESOLVE CLASS - 2 58BB5.80B14.20R11.70O2.56Y2. $2,500 $0 Apr 19, 2010
Dec 14, 2009 32067952M RESOLVE CLASS - 3 B354 15.16.50A.50B.50C.50D 50A REMOVE ALL STORAGE 50B ALL FLAMABLES 50C BO TEST CHAINS ON RELIEF VALVES 50D TRAIN EMP... $500 $0 Feb 8, 2010
Oct 27, 2009 32067356X RESOLVE CLASS - 3 B354 15.50A.50B.50A FLUE PIPE NOT PROPERLY SEALED TO CHIMNEY 50B FLUE PIPE NEED SUPPORT $500 $0 Dec 21, 2009
Sep 17, 2009 34807307N RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: AT ROOF LEVEL TO 6TH FLR HAIR LINE MORTAR CRACKS EXIST IN SEV... $250 $0 Nov 9, 2009
Mar 18, 2009 38202102N RESOLVE CLASS - 2 16E10.16H11.42G11.59Y02.56Y02.56Y13.71L10.32H10.10H11.39O02.34O02.40R09.16J01.16H11 HATCH DOOR PIVOTS WORN REPLACE 40... $250 $0 Feb 1, 2010
Mar 16, 2009 32065922M RESOLVE CLASS - 3 B354 50A.50B.50C 50A FLUE PIPE NOT PREOPERLY SEALED TO CHIMNEY 50B SEALED AROUND CLEAN OUT DOOR ON CHIMNEY BASE 50C B... $500 $0 Jan 4, 2010
Oct 11, 2008 32060891X RESOLVE CLASS - 2 B254,50A,B,C,D,E,F.50A-HOLES IN BOILER ROOM WALLS & CEILING.50B-BOILERROOM FIRE DOOR DEFECTIVE NOT SELF CLOSING.50F-L... $2,500 $0 Dec 1, 2008
Jul 31, 2008 34697606Z ACTIVE CLASS - 1 SEC. 28-201.1. FAILURE TO COMPLY W/COMM'S ORDER TO CORRECT VIO #34640350R FOR WORK W/O PERMIT @ CELLAR BUILT 1) ILLEG... $8,000 $0 Sep 22, 2008
Mar 31, 2008 34640350R RESOLVE Hazardous WORK W/O A PERMIT. WORK NOTED: CELLAR CLASS A APT ERECTED INTERIOR PARTITION CREATING 3 PC BATHROOM, FULL KITCHEN W/G... $2,500 $0 May 19, 2008
Mar 31, 2008 32056263N RESOLVE Non-Hazardous B4A, 50A,50B,50C,50D,50E,50F: 50A-REMOVE WASTE OIL FROM BOILER ROOM 50B-BOILER ROOM NOT A STORAGE ROOM. 50C-FLUE PIPE... $2,500 $0 Jun 2, 2008