ECB violations
1 Kenilworth Place, Brooklyn • Block 05249 • Lot 0035
56 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 19, 2026 | 39189137X | ACTIVE | CLASS - 1 | ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED ON THE 6TH FL THAT THE ELECTRICAL... | $1,200 | $0 | Aug 5, 2026 |
| May 19, 2026 | 39189087R | ACTIVE | CLASS - 2 | LAARS BOILER#1 HAS THREADED END ON SAFETY DISCHARGE PIPE+BROKEN TRI GAUGE ON HW STORAGE TANK#2+BYPASS AROUND BACKFLOW... | $1,250 | $0 | Aug 5, 2026 |
| May 19, 2026 | 39189088Z | ACTIVE | CLASS - 2 | LAARS BOILER#3 HAS A OUTSIDE COMBUSTION AIR INLET LOUVER WITH A STRIPED BACKDRAFT DAMPER LOCKING SCREW+AO SMITH HWH H... | $1,250 | $0 | Aug 5, 2026 |
| May 19, 2026 | 39189136Y | ACTIVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE BASEMENT LAUNDRY RM THE NEW INSTALLATION OF EMT PIPES AND 30 AMP RE... | $2,500 | $0 | Aug 5, 2026 |
| Apr 22, 2026 | 39185697X | ACTIVE | CLASS - 1 | CLASS 1 - CEASE USE VIOLATION: FAILURE TO MAINTAIN ELEVATOR DEVICE IN A SAFE CONDITION. DOOR ZONE RESTRICTOR FOUND DE... | $1,280 | $30 | Jul 1, 2026 |
| Mar 24, 2026 | 39181582H | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS.... | $1,250 | $0 | Dec 15, 2026 |
| Mar 24, 2026 | 39181596Z | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS.... | $1,250 | $0 | Dec 15, 2026 |
| Mar 24, 2026 | 39181589K | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS.... | $1,250 | $0 | Dec 15, 2026 |
| May 21, 2025 | 39148744R | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED EXCESSIVE STORAGE IN PASSAGEWAY. ABOUT 4 TIERS HIGH OF PTEC... | $1,250 | $0 | Sep 14, 2026 |
| May 21, 2025 | 39148740J | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS AT EXITS AND MECHANICAL/UTILITY ROOMS THROUGHOUT BUILDING... | $625 | $0 | Aug 6, 2025 |
| May 21, 2025 | 39148742N | RESOLVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED EXCESSIVE STORAGE UNDERNEATH THE STAIRS AT CELLAR LEVE... | $2,500 | $0 | Sep 14, 2026 |
| May 21, 2025 | 39148745Z | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED UNPERMITTED FLEX HOSE ON EXHAUSTED OF COMMERCIAL DRYE... | $625 | $0 | Aug 6, 2025 |
| May 21, 2025 | 39148741L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Sep 14, 2026 |
| May 21, 2025 | 39148743P | RESOLVE | CLASS - 1 | FILED A CERTIFICATE, FORM, APPLICATION ETC., CONTAINING A MATERIAL FALSE STATEMENT(S). ON 3/18/25 A CERTIFICATE OF CO... | $10,000 | $0 | Apr 13, 2026 |
| Feb 11, 2025 | 37033150R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39098040X ISSUED ON 10/25/2023, AND FAILURE TO FILE... | $625 | $0 | Feb 18, 2026 |
| Feb 11, 2025 | 37033152K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39098044N ISSUED ON 10/25/2023, AND FAILURE TO FILE... | $625 | $0 | Feb 18, 2026 |
| Feb 11, 2025 | 37033151Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39098041H ISSUED ON 10/25/2023, AND FAILURE TO FILE... | $625 | $0 | Feb 18, 2026 |
| Jan 29, 2025 | 37033097R | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39097465R ISSUED ON 10/19/2023, AND FAILURE TO FILE... | $1,250 | $0 | Apr 23, 2025 |
| Jan 29, 2025 | 37032798P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39078655Y ISSUED ON 01/30/2023, AND FAILURE TO FILE... | $1,250 | $0 | Apr 16, 2025 |
| Jan 29, 2025 | 37032799R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39078656X ISSUED ON 01/30/2023, AND FAILURE TO FILE... | $1,250 | $0 | Apr 16, 2025 |
| Jul 22, 2024 | 39119521R | RESOLVE | CLASS - 2 | ELEVATOR OUT OF SERVICE. REMEDY: RESTORE TO SERVICE. | $625 | $0 | Sep 25, 2024 |
| Jul 18, 2024 | 39119545L | RESOLVE | CLASS - 2 | UNREGISTERED BOILER LAARS PNCVO5OONACK2BXN SER# C-08-206331 BTUS 500,000, MAINTAIN BOILER; REGISTER BOILER | $625 | $0 | Feb 14, 2025 |
| Jul 18, 2024 | 39119543H | RESOLVE | CLASS - 2 | UNREGISTERED BOILER LAAR MODEL PNCH0500NACH2CJN SER #C-09-210854 500,000 BTUS, MAINTAIN BOILER; REGISTER BOILER | $625 | $0 | Feb 14, 2025 |
| Jul 18, 2024 | 39119544J | RESOLVE | CLASS - 2 | UNREGISTERED BOILER LAARS PNCV0500NACK2BXN SER# C-08-208037 BTUS 499,980, MAINTAIN BOILER; REGISTER BOILER | $625 | $0 | Feb 14, 2025 |
| Jul 16, 2024 | 39119208K | RESOLVE | CLASS - 2 | RESTORE TO SERVICE SO A FULL INSPECTION CAN BE MADE BY THIS DEPARTMENT. | $625 | $0 | Sep 25, 2024 |
| Oct 25, 2023 | 39098045P | RESOLVE | CLASS - 2 | ILLEGAL PLASTIC EXCESS PANELS THROUGHOUT BUILDING., PROVIDE/MAINTAIN FIRE STOPPING | $1,250 | $0 | Jan 3, 2024 |
| Oct 25, 2023 | 39098043L | RESOLVE | CLASS - 2 | EMERGENCY EXIT DOOR AND HARDWARE IS DEFECTIVE, GROUND LEVEL EXPOSURE #2., PROVIDE LEGAL HARDWARE | $625 | $0 | Jan 3, 2024 |
| Oct 25, 2023 | 39098042J | RESOLVE | CLASS - 2 | SELF-CLOSING DOOR BROKEN OFF HINGE TO THE ELECTRICAL ROOM, ROOF LEVEL, REPAIR/REPLACE DOOR | $625 | $0 | Jan 3, 2024 |
| Oct 25, 2023 | 39098046R | RESOLVE | CLASS - 2 | EMERGENCY LIGHTING DOES NOT WORK THROUGHOUT BUILDING., REPAIR AND/OR REPLACE LIGHTING | $1,250 | $0 | Jun 17, 2024 |
| Oct 25, 2023 | 39098044N | RESOLVE | CLASS - 2 | WATER PENETRATIONS/LEAKS THROUGHOUT BUILDING., REPAIR AND/OR REPLACE | $625 | $0 | Jan 3, 2024 |
| Oct 25, 2023 | 39098041H | RESOLVE | CLASS - 2 | EXCESSIVE FOAM INSTALLED THROUGHOUT BUILDING., REPAIR AND/OR REPLACE | $625 | $0 | Jan 3, 2024 |
| Oct 25, 2023 | 39098040X | RESOLVE | CLASS - 2 | HOLE PENETRATIONS, THROUGHOUT BUILDING., REPAIR AND/OR REPLACE | $625 | $0 | Jan 3, 2024 |
| Oct 19, 2023 | 39097488J | RESOLVE | CLASS - 2 | OBSERVED IN THE BOILER ROOM LOCATED ON THE ROOF LEVEL ACTIVE LWAK ON THE BOTTOM OF THE GAS FIRED WATER HEATER. 102.3 ... | $625 | $0 | May 9, 2024 |
| Oct 19, 2023 | 39097465R | ACTIVE | CLASS - 2 | BACK FLOW PREVENTER FOR DOMESTIC HOT WATER BOILER LEAKING., MAINTAIN BOILER; CORRECT VIOLATING CONDITION AND SUBMIT A... | $625 | $0 | Dec 27, 2023 |
| Jun 20, 2023 | 39088781Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING & PARTS THEREOF IN A CODE COMPLIANT MANNER: ATOI, EVIDENCE OF WATER LEAKS WITH WATER STA... | $625 | $0 | Oct 4, 2023 |
| Jan 30, 2023 | 39078663Y | RESOLVE | CLASS - 2 | OBSERVED: AT FIRST FLOOR, MAIN ENTRANCE, EXTERIOR EXIT DOOR AND STAIR A&B EXIT DOORS, ILLEGAL HARDWARE IS BEING USED ... | $312 | $0 | Apr 5, 2023 |
| Jan 30, 2023 | 39078656X | RESOLVE | CLASS - 2 | MISALIGNED CAB MIRROR. REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. DEFECTIVE CAR PHONE. UNREADABLE CONT... | $625 | $0 | Apr 5, 2023 |
| Jan 30, 2023 | 39078624L | RESOLVE | CLASS - 2 | FOUND LAARS BOILER MODEL# PNCH500 ON ROOF. UNREGISTERED BOILER, MAINTAIN BOILER; REGISTER BOILER | $1,562 | -$1,562 | Oct 23, 2023 |
| Jan 30, 2023 | 39078662M | RESOLVE | CLASS - 2 | OBSERVED: AT ROOF LEVEL, BOILER RM, STAIR A&B, (FROM 8FL TO CELLAR), AT CELLAR LEVEL, ELECTRICAL, GAS, SPRINKLER ROOM... | $1,250 | $0 | Apr 5, 2023 |
| Jan 30, 2023 | 39078659L | RESOLVE | CLASS - 2 | OBSERVED ON THE ROOF LEVEL GAS PIPING TO HVAC IS STARTING TO RUST AND CORRODE, THE GAS IN NOT PROTECTED FROM THE ELEM... | $625 | $0 | Apr 5, 2023 |
| Jan 30, 2023 | 39078626P | RESOLVE | CLASS - 2 | FOUND LARRS BOILER ON ROOF.BOILER UN REGISTERED, MAINTAIN BOILER; REGISTER BOILER | $1,562 | -$1,562 | Oct 23, 2023 |
| Jan 30, 2023 | 39078655Y | RESOLVE | CLASS - 2 | MISALIGNED CAB MIRROR. REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. DEFECTIVE CAR PHONE. UNREADABLE CONT... | $625 | $0 | Apr 5, 2023 |
| Jan 30, 2023 | 39078664X | RESOLVE | CLASS - 2 | OBSERVED: - AT FIRST FLOOR, MAIN ENTRANCE, EXTERIOR EXIT DOOR AND STAIR A&B EXIT DOORS, ILLEGAL HARDWARE IS BEING USE... | $0 | $0 | Apr 5, 2023 |
| Jan 30, 2023 | 39078625N | RESOLVE | CLASS - 2 | FOUND LAARS BOILER MODEL# PNCH5OO ON ROOF. BOILER UNREGISTERED, MAINTAIN BOILER; REGISTER BOILER | $1,562 | -$1,562 | Oct 23, 2023 |
| Mar 23, 2021 | 39038110H | RESOLVE | CLASS - 1 | CEASE USE ITEM: INOPERATIVE ZONE LOCK RESTRICTOR. CLASS 1 ITEM: MISSING DLM AS NOW REQUIRED BY CODE. CLASS 2 ITEMS: M... | $3,125 | $0 | Jul 28, 2021 |
| Mar 23, 2021 | 39038111J | RESOLVE | CLASS - 1 | CLASS ONE ITEM: MISSING DLM AS NOW REQUIRED BY CODE. CLASS 2 ITEMS: MISALIGNED CAB MIRROR. INOPERATIVE CAR PHONE. REP... | $3,125 | $0 | Jul 28, 2021 |
| Mar 26, 2008 | 34630182H | RESOLVE | Hazardous | FAILURE TO PROVIDE CONTRACTOR'S SIGN. NOTED: AT TIME OF INSPECTION FORSWO #030308CEX01LP AND NO CONTRATOR SIGN AT KEN... | $0 | $0 | May 19, 2008 |
| Mar 26, 2008 | 34630173X | RESOLVE | Hazardous | FAILURE TO SAFEGUARD PUBLIC AND PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. NOTED: AT TIEM OF INSPECTION TO RESCIND... | $0 | $0 | Oct 23, 2009 |
| Mar 3, 2008 | 34625607H | RESOLVE | Non-Hazardous | FAILURE TO ADEQUATELY SUPPORT ADJOINING GROUND OR STRUCTURES AFFECTED BY EXCAVATION. NOTED: UNDER APP #302384159 ISSU... | $1,000 | $0 | Apr 28, 2008 |
| Mar 3, 2008 | 34625609L | RESOLVE | Hazardous | WORK CONTRARY TO APPROVED PLANS. NOTED: UNDER APP# 302384159 ISSUED ON12-27-07 AFTER UNDERMINING ADJ PROPERTY RETAINI... | $500 | $0 | Apr 28, 2008 |