ECB violations
449-457 Ocean Parkway, Brooklyn • Block 05390 • Lot 0074
95 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 30, 2026 | 39194290Z | ACTIVE | CLASS - 2 | REPLACE WORN GIBS WHERE NEEDED (2.11.11.5.7). SECURE GIBS WHERE NEEDED (2.11.11.5.7). ADJUST HOISTWAY DOOR ACCESS HOL... | $625 | $625 | Sep 9, 2026 |
| May 11, 2026 | 39188002Y | RESOLVE | CLASS - 2 | 1) ELEVATOR COMPANY MISSING CAT1 TAGS. | $0 | $0 | Jul 22, 2026 |
| Apr 21, 2026 | 39185470L | RESOLVE | CLASS - 2 | INTERMITTENT WILDCARDING OF DEVICE MAINLY IN DOWN DIRECTION. ADJUST HOISTWAY DOOR ACCESS HOLES WHERE NEEDED. (2.12.6)... | $0 | $0 | Jul 1, 2026 |
| Apr 6, 2026 | 39183316Y | RESOLVE | CLASS - 2 | 1) THIS ELEVATOR IS RUNNING DOWN, STOPPING ON EVERY FLOOR (THE DISPATCH IS NOT WORKING AS DESIGN). 2) THERE IS A HOLE... | $0 | $0 | Jun 10, 2026 |
| Apr 6, 2026 | 39183317X | RESOLVE | CLASS - 2 | 1) THE CAT-1 TAG IS EXPIRED 2) THE BRAKE TAG IS EXPIRED 3) THE WIRES FOR THE DLM DEVICE NEEDS TO BE PROTECTED (WITH T... | $0 | $0 | Jun 10, 2026 |
| Sep 11, 2025 | 39160127N | RESOLVE | CLASS - 1 | CEASE USE ITEM: DISABLED ZONE LOCK RESTRICTOR. CLASS 2 ITEMS: CLEAN PIT. REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS ... | $1,250 | $0 | Nov 19, 2025 |
| Sep 9, 2025 | 39159732N | RESOLVE | CLASS - 2 | CLASS 2: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. THIS IS A SAFETY HAZZARD AFFECTING SPECIAL NEEDS RESIDENT... | $0 | $0 | Nov 19, 2025 |
| Jun 17, 2025 | 39151304K | RESOLVE | CLASS - 2 | CLASS 2: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. THIS IS A SAFETY HAZZARD AFFECTING SPECIAL NEEDS RESIDENT... | $0 | $0 | Aug 27, 2025 |
| Jun 17, 2025 | 39151305M | RESOLVE | CLASS - 2 | CLASS 2: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. THIS IS A SAFETY HAZZARD AFFECTING SPECIAL NEEDS RESIDENT... | $0 | $0 | Aug 27, 2025 |
| Feb 21, 2025 | 39139197M | RESOLVE | CLASS - 1 | ELEVATOR IN A 19 STORY BUILING OUT OF SERVICE. THIS CONDITION AFFECTS NUMEROUS TENANTS, INCLUDING THOSE WITH SPECIAL ... | $1,250 | $0 | Dec 1, 2025 |
| Dec 20, 2024 | 39133428N | RESOLVE | CLASS - 2 | REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. SEAL HOIST MACHINE LEAKS. UNREADABLE CONTROLLER FUSES. MAIN... | $0 | $0 | Mar 31, 2025 |
| Dec 20, 2024 | 39133427L | RESOLVE | CLASS - 1 | CEASE USE ITEM: INOPERATIVE DLM. CLASS 2 ITEMS: REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. SEAL HOIST ... | $1,250 | $0 | Mar 31, 2025 |
| Mar 20, 2024 | 39109298Y | RESOLVE | CLASS - 2 | REPLACE WORN GIBS WHERE NEEDED. EXPIRED BRAKE MAINTENANCE TAG. UNREADABLE CONTROLLER FUSES. WORN GENERATOR BRUSHES. S... | $655 | $0 | Jun 5, 2024 |
| Mar 20, 2024 | 39109297M | RESOLVE | CLASS - 2 | REPLACE WORN GIBS WHERE NEEDED. EXPIRED BRAKE MAINTENANCE TAG. UNREADABLE CONTROLLER FUSES. UNGUARDED HOIST MOTOR WIR... | $655 | $0 | Jun 5, 2024 |
| Sep 18, 2023 | 39095083M | RESOLVE | CLASS - 1 | CEASE USE ITEM: 1) IN CAR STOP SWITCH UNSECURE AND UNABLE TO BE EASILY OPERATED IF NEEDED. 2) REMOVAL OF THIS CAR FRO... | $1,250 | $0 | Dec 18, 2023 |
| Jul 25, 2023 | 39090992R | RESOLVE | CLASS - 1 | 97:X:10; ENTIRE DEVICE IS SHUT DOWN BETWEEN 12TH AND 14TH FLOORS, NEED TO REPAIR. THERE ARE 18 FLOORS IN THE BUILDING... | $3,125 | $0 | Oct 4, 2023 |
| Dec 19, 2022 | 39075887J | RESOLVE | CLASS - 2 | REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. OPERATOR COVER MISSING. WORN GENERATOR BRUSHES. SHOIORTEN H... | $655 | $0 | Feb 22, 2023 |
| Dec 19, 2022 | 39075888L | RESOLVE | CLASS - 2 | REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. OPERATOR COVER MISSING. WORN GENERATOR BRUSHES. MUTED ALARM... | $655 | $0 | Feb 22, 2023 |
| Oct 5, 2022 | 39071437Y | RESOLVE | CLASS - 1 | CEASE USE ITEM: DLM IMPROPERLY INSTALLED ON THIS DEVICE. NO FIREMANS' SERVICE PRESENTIN CONTROLLER. INSTALL FIREMANS'... | $1,250 | $0 | Aug 7, 2023 |
| Jun 7, 2022 | 39063606X | RESOLVE | CLASS - 1 | DLM IMPROPERLY INSTALLED ON THIS DEVICE . NO FIREMAN'S SERVICE PRESENT IN CONTROLLER . INSTALL FIREMAN'S SERVICE SO D... | $1,250 | $0 | Apr 8, 2024 |
| Apr 25, 2022 | 35648861L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN/DISPLAY ONSITE DOCS RETURNED BY BCCH33 NOTED:ATO MY INSP OF ACTIVE CONST JOBSITE I OBSERVED 2SUSP... | $625 | $0 | Sep 21, 2022 |
| Apr 25, 2022 | 35648862N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN/DISPLAY ONSITE DOCS REQUIRED BY BCCH33 NOTED:ATO MY INSP OF ACTIVE CONST JOBSITE I OBSERVED SWS@E... | $625 | $0 | Sep 21, 2022 |
| Mar 11, 2022 | 35647595N | RESOLVE | CLASS - 2 | PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS.AT WEST ELEVATION,EXPOSURE#1 OBSERVED MISSING WOODEN SIDE PAN... | $2,400 | $0 | Jul 27, 2022 |
| Oct 8, 2021 | 37022425N | RESOLVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 6,7B & 8B REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INI... | $0 | $0 | May 11, 2022 |
| Aug 10, 2021 | 39045759H | RESOLVE | CLASS - 2 | REPAIR AND RESTORE TO SERVICE. | $625 | $0 | Jan 5, 2022 |
| Jun 1, 2021 | 37021564Z | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $3,125 | $0 | Dec 15, 2021 |
| Apr 2, 2021 | 39038782K | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $3,125 | $0 | Oct 25, 2021 |
| Jan 12, 2021 | 39034734H | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Jun 16, 2021 |
| Nov 5, 2020 | 39031556K | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Dec 6, 2021 |
| Nov 5, 2020 | 39031555Z | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Dec 6, 2021 |
| Jul 24, 2020 | 39025883R | RESOLVE | CLASS - 2 | RESTORE SERVICE TO DEVICE IN ORDER FOR A FULL AND PROPER INSPECTION TO BE PERFORMED | $0 | $0 | Nov 25, 2020 |
| Jul 15, 2020 | 35500305J | RESOLVE | CLASS - 1 | BC3303.4 HOUSEKEEPING NOTE:AT THE TIME OF MY INSPECTION OF A 15 STORY BLDG I OBSERVED INADEQUATE HOUSEKEEPING ON ROOF... | $1,250 | $0 | Nov 25, 2020 |
| Jul 15, 2020 | 35500303X | RESOLVE | CLASS - 1 | BC3314.1-UNSAFE SUPPROTED SCAFFOLD NOTE AT THE TIME OF INSPECTION OF A 15 STORY BUILDING I OBSERVED A SUPPROTED SCAFF... | $0 | $0 | Nov 25, 2020 |
| Jun 3, 2020 | 37019212M | RESOLVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 7B REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... | $1,250 | $0 | Feb 18, 2021 |
| Aug 21, 2019 | 35446683M | RESOLVE | CLASS - 1 | TENANT PROTECTION PLAN-NONE. NOTE: AT TIME OF INSPECTION OF A 15 STY OCCUPIED BLDG UNDER ALTERATION WORKS & DEMOLITIO... | $1,250 | $0 | Jun 4, 2020 |
| Aug 21, 2019 | 35446682K | RESOLVE | CLASS - 1 | FAILURE TO INSTITUTE MAINTAIN SAFETY EQUIPMENT MEASURES OR TEMPORARY CONSTRUCTION-NO GUARDRAIL. AT TIME OF INSPECTION... | $2,500 | $0 | Mar 2, 2020 |
| Apr 16, 2019 | 35418268R | RESOLVE | CLASS - 2 | PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS. NOTE:AT TIME OF INSPECTION I OBSERVED SIDEWALK SHED IN PLACE... | $2,400 | $0 | Apr 27, 2020 |
| Oct 15, 2018 | 37013250X | RESOLVE | CLASS - 2 | FALIURE TO SUBMIT A REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPUR... | $1,250 | $0 | Jun 29, 2020 |
| Jul 3, 2018 | 38263864Z | RESOLVE | CLASS - 2 | 17H11,17D06,100M07,52K11,42G11,50B10,50H11,56V13,56AA09,68BB11,37O02,39V02,76M07,15M07,03M07,77B11,79J01,10H11,59J01.... | $310 | $0 | Sep 10, 2018 |
| Nov 29, 2017 | 35295830H | RESOLVE | CLASS - 1 | 3310.10.2 ALL WORKERS EMPLOYEDD @MAJOR BLDG SITE SHALL SUCCESSFULLY COMPLETED W/IN THE PREVIOUS FIVE YEARS A COURSE T... | $4,000 | $0 | Feb 26, 2018 |
| Nov 29, 2017 | 35295829K | RESOLVE | CLASS - 2 | PSWO WORK UNDER PERMIT #340043214 THE DEPT SHALL BE NOTIFIED @LEAST 24 HRS,BUT NOT MORE THAN MORE THAN 48 HOURS PRIOR... | $2,000 | -$2,000 | Feb 26, 2018 |
| Nov 29, 2017 | 35295831J | RESOLVE | CLASS - 2 | 3310.8.4 A SITE SAFTEY LOG SHALL BE MAINTAINED & KEPT @SITE NOTED:@TIME OF INSP SSM HAS APPROVE PART TIME BY THE COMM... | $0 | $0 | Feb 26, 2018 |
| Dec 16, 2016 | 35200170R | RESOLVE | CLASS - 2 | EXPIRED PERMIT FOR TEMPORARY CONSTRUCTION. NOTE AT TIME OF INSPECTION I OBSERVED SIDEWALK SHED IN PLACE WITH PERMIT #... | $2,000 | -$2,000 | Jan 30, 2017 |
| Apr 27, 2016 | 35185056K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN NOV #35097803P ISSUED ON 09/24/14 & TO FILE A CERTIFICATE ... | $400 | $0 | Aug 15, 2016 |
| Apr 20, 2016 | 38242139N | RESOLVE | CLASS - 2 | 56Y13,59Y02,40Y02,58H10,40R07,50H11,68M07,17H11,29Q03,52O02,53E01,53B14,71X10. 56Y-SEAL LEAKS; 59Y-CLEAN ROOM; 58H-WO... | $0 | $0 | Jun 13, 2016 |
| Apr 20, 2016 | 38242140K | RESOLVE | CLASS - 2 | 17H11,56Y13,52K11,52H11,50H11,68M07,39O02,52O02,72D06,71X10. 17H-WHERENEEDED; 56Y-SEAL LEAKS; 52K,H-ROUGLE/UNDERSIDE ... | $0 | $0 | Jun 13, 2016 |
| Nov 30, 2015 | 38239979Z | RESOLVE | CLASS - 2 | 17,H,11,17,D,06,40,O,02,40,R,09,40,Y,02,40,I,10,43,Q,03,43,X,10,42,G,11,56,Y,11,68,B,10,100,M,07.33,J,01,10,H,11,10,M... | $0 | $0 | Jan 25, 2016 |
| Nov 30, 2015 | 38239980X | RESOLVE | CLASS - 2 | 17H11,17D16,52K11,67M07,15M07,01H11,10H11,58H10,42G11,40Y02,59Y11,42G11,43X10,43Q03,05M07.17-H-10-REPLACE/SECURE WHER... | $0 | $0 | Jan 25, 2016 |
| Sep 16, 2015 | 35157163H | RESOLVE | CLASS - 2 | 3310.4 PARTIAL STOP WORK ORDER FOR MATERIAL HOIST & FACADE JOB @EXP#1 ISSUED PURSUANT TO 28-207.2 & POSTED @PREMISES.... | $800 | $0 | Mar 14, 2016 |
| Oct 21, 2014 | 36019964Z | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXT... | $0 | $0 | Jan 12, 2015 |