ECB violations

4512 Fort Hamilton Parkway, Brooklyn • Block 05614 • Lot 0028

7 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jul 29, 2008 32060039K ACTIVE CLASS - 2 50A.50B.50C.50D 50A FLUE PIPE NOT PROPERLY INSERTED INTO CHIMNEY BASE 50B INSTALL STRUCTURAL SUPPORT THREADED ROD & C... $250 $0 Nov 20, 2008
Jun 27, 2006 32051778J RESOLVE Non-Hazardous B4A,48A,48B,50A,18A,18B/50A-REPAIR FIRE STOPPING ON CEILING ABOVE BOILER/50B-CLEAN BASEMENT OF ALL DEBRIS/50C-SEAL CH... $180 $0 Mar 20, 2008
Dec 6, 2004 32046438R RESOLVE Non-Hazardous 19B/50 BQ9/36 50-SAFELY VALVE IS NOT INSTALLED VERTICAL WITH THE SPINDLE ON TOP- DISCHARGE PIPE HAS A THREADED END. B... $180 $0 Jan 24, 2005
Aug 13, 2003 32042888X RESOLVE Non-Hazardous 18A,50A,50B,50C,50D,48AB FULTON YERT TBLS BOILER NB76848 10HP GAS FIRED 1996 50A SAFETY VALVE DISCHARGE PIPE TOO SHOR... $0 $0 Sep 29, 2003
Oct 30, 2000 32021007Y RESOLVE Non-Hazardous 49,48A,48B.FLUE PIPE SECTION CRACKED AND CORRODED.WATER COLUMN DRAIN REDUCED.BLOWDOWN NIPPLE BETWEEN 1 + 2VALVE CORRO... $0 $0 Dec 18, 2000
Jan 18, 2000 32017816M RESOLVE Non-Hazardous 48A,48B,49 SAFETY VALVE OPENS PREMATURLY TO BE REPLACED BY NEW ONE $0 $0 Mar 6, 2000
Apr 25, 1996 32013970M ACTIVE Non-Hazardous 44C,49.1-WATER COLUMN AND BLOWDOWN LINES HAVE BEEN REDUCED THEY MUST BE THE SAME SIZE AS THE BOILER OPENING THROUGHOU... $350 $0 Jul 22, 1996