Skip to content

ECB violations

641-669 62 Street, Brooklyn • Block 05793 • Lot 0052

46 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Dec 4, 2025 39169253P RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED AT REAR OF BUILDING AT EXPOSURE 3 THERE IS EXCESSIVE D... $5,000 $0 Feb 11, 2026
Apr 25, 2024 39112633J RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED : OBSERVED AT REAR OF BUILDING AT EXPOSURE 3 THERE IS EX... $1,250 $0 Feb 10, 2025
Apr 25, 2024 39112630Y ACTIVE CLASS - 2 WORK WITHOUT A PERMIT. NOTED : OBSERVED AT REAR OF BUILDING, AT EXPOSURE 3 A CANOPY WAS ERECTED ,THERE IS NO JOB FILI... $1,250 $0 Aug 7, 2024
Jun 23, 2022 39064647R ACTIVE CLASS - 3 THE GAS BOILER AND GAS HOT WATER HEATER WERE REMOVED WITHOUT THE WATER PIPE AND THE GAS PIPE AND THE CHIMNEY AND THE ... $500 $0 Oct 26, 2022
Apr 19, 2022 39060539L ACTIVE CLASS - 1 I OBSERVED IN COMMERCIAL SPACE MARKED 641F AN ILLEGAL BOILER INSTALLATION AND WATER HEATER SEVERAL GAS FLEXES INSTALL... $625 $0 Aug 24, 2022
Apr 19, 2022 39060540Z ACTIVE CLASS - 1 I OBSERVED IN COMMERCIAL AREA OF 641F BUILDING GAS BOILER INSTALLED WITH ALL GAS, WATER AND FLU PIPING AND NO PERMITS... $2,500 $0 Aug 24, 2022
Apr 19, 2022 39060544X ACTIVE CLASS - 1 FOUND GAS HOT WATER HEATER(UNKNOWN MAKE AND MODEL#) HAD TO CEASE USE WATER HEATER DUE TO HEATER BEING MOUNTED ON COMB... $1,250 $0 Aug 24, 2022
Apr 19, 2022 39060541K ACTIVE CLASS - 1 I OBSERVED IN COMMERCIAL BUILDING MARKED 641F BOILER INSTALLED WITHOUT ANY PERMITS ON FILE; THEREFORE NO PROPER TESTI... $1,250 $0 Aug 24, 2022
Apr 19, 2022 39060797Y ACTIVE CLASS - 2 FOUND H B SMITH(MODEL# 5210 S/W5) GAS FIRED BOILER IN REAR OF FACTORY NOT REGISTERED, MAINTAIN BOILER; REGISTER BOILE... $625 $0 Sep 28, 2022
Apr 19, 2022 39060536X ACTIVE CLASS - 1 FOUND H B SMITH(MODEL#5210S/W5) GAS FIRED BOILER HAD TO CEASE USE BOILER DUE TO BOILER BEING MOUNTED ON A COMBUSTIBLE... $1,250 $0 Aug 24, 2022
Apr 19, 2022 39060538J ACTIVE CLASS - 1 I OBSERVED IN COMMERCIAL BUILDING MARKED 641F BOILER INSTALLED WITHOUT ANY PERMITS ON FILE; THEREFORE NO PROPER GAS A... $5,000 $0 Aug 24, 2022
Aug 12, 2016 32077504H RESOLVE CLASS - 2 3A,50A,50B. FULTON YT BOILER, 15HP, NB67249, HP STM, GAS, 1993. 3A) SURFACE CORROSION ON SECTIONS OF THE FILE PIPE RU... $250 $0 Nov 16, 2016
Aug 12, 2016 32077500K RESOLVE CLASS - 1 CEASE USE. 50A,51. FULTON VT BER, 15HP NB64456, HP STM, GAS, 1992 50(A)REFERENCED BOILER WAS FOUND IN OPERATION W/ A ... $1,000 $0 Nov 16, 2016
Aug 11, 2009 32066711R RESOLVE CLASS - 3 48B,50A,50B 50A- REMOVE COOPER SOLDERED PIPES ON BOILER FEED PUMP AND INSTALL THREADED APPROVED TIRE PIPING. 50B- INS... $0 $0 Oct 5, 2009
Aug 11, 2009 32066713K RESOLVE CLASS - 3 18B $0 $0 Oct 5, 2009
Aug 11, 2009 32066712Z RESOLVE CLASS - 2 18B,50A,50B 50A- LOWER LEFT HAND HOLE AREA COMPLETELY COVERED WITH CEMENT UNABLE TO INSPECT CONDITION OF HANDHOLE AND... $500 $0 Oct 5, 2009
Jul 24, 2009 32066702P RESOLVE CLASS - 3 18B.48B.50A 50A REPLACE CORRODED NIPPLE ON BOILER FEED LINE $500 $0 Sep 14, 2009
May 30, 2008 32056468R RESOLVE Hazardous 50A50B. 50A DISCHARGE PIPE CAUSING STRESS ON SAFETY VALVE. 50B INSTALLSTRUCTURAL SUPPORT FOR FLUE PIPE (CHANNEL & THR... $0 $0 Jul 21, 2008
May 30, 2008 32056466N RESOLVE Non-Hazardous 3850A50B24C. 38 FRESH AIR BLOCKED. 50A INSTALL STRUCTURAL SUPPORT FOR PIPE CHANNEL AND THREADED ROD. 50B CLEAN BOILER... $0 $0 Jul 21, 2008
May 30, 2008 32056470X RESOLVE Hazardous 18A18B50A48A48B. 50A INSTALL STRUCTURAL SUPPORT ON FLUE PIPE. (CHANNEL& THREADED ROD) $0 $0 Jul 21, 2008
May 30, 2008 32056471H RESOLVE Hazardous 18A18B50A. 50A INSTALL STRUCTURAL SUPPORT ON FLUE PIPE. (CHANNEL & THREADED ROD) $0 $0 Jul 21, 2008
May 30, 2008 32056467P RESOLVE Hazardous 50A18B50B. 50A LARGE AMOUNT OF DEBRIS AND STORAGE IN BOILER. 50B INSTALL PROPER SUPPORT FOR FLUE PIPE (CHANNEL & THRE... $2,500 $0 Feb 9, 2009
May 30, 2008 32056469Z RESOLVE Hazardous 18B50A50B24B. 50A LOW WATER RESET SWITCH DISCONNECTED. 50B INSTALL STRUCTURAL SUPPORT ON FLUE PIPE (CHANNEL & THREADE... $0 $0 Jul 21, 2008
Oct 4, 2006 32051096M RESOLVE Non-Hazardous 50A/50B/48B/44C/50C/50A-SAFETY VALVE LEAKING/50B-WATER COLUMN LEAKING/50C-CLEAN BOILER RM REMOVE DEBRIS $0 $0 Nov 20, 2006
Oct 4, 2006 32051095K RESOLVE Non-Hazardous 18A/18B/48B/50A/50B/50C/50A-REVERSE BLOWDOWN VALVE TO HAVE SLOW OPENING VALVE TERMINATE LAST/50B-CLEAN DEBRIS FROM BO... $0 $0 Nov 20, 2006
Oct 4, 2006 32051094Z RESOLVE Non-Hazardous 18A/18B/48B/50A/50A-FEEDLINE TO BOILER LEAKING $0 $0 Nov 20, 2006
Feb 28, 2005 32047200L RESOLVE Non-Hazardous 50A/50B 50C FULTON V.T. BOILER, 15HP, NB 43713, GAS, 1983 50A) IMPROPER ARRANGEMENT OF THE BLOWDOWN VALVES. INSTALL S... $2,500 $0 May 10, 2006
Feb 28, 2005 32047199N RESOLVE Non-Hazardous 50A/48AB FULTON V.T. BOILER, 15HP, NB64480, GAS, 1992 50A) IMPROPER ARRANGEMENT OF THE BLOWDOWN VALVES. INSTALL A SCR... $0 $0 Apr 18, 2005
Feb 28, 2005 32047201N RESOLVE Non-Hazardous 50 FULTON V.T. BOILER, 15HP, NB64478, GAS 1992 50 NO SECONDARY SCREW TYPE (SLOW) SHUT OFF VALVE ON THE BLOWDOWN LINE. $0 $0 Apr 18, 2005
Feb 28, 2005 32047198L RESOLVE Non-Hazardous 50A/50B 50C/50D 50E FULTON V.T. BOILER, 15HP, NB66456, GAS, 1992 50A) NO DISCHARGE PIPE ON THE SAFETY VALVE. 50B) NO ... $2,500 $0 Apr 18, 2005
Feb 26, 2005 32047197J RESOLVE Non-Hazardous 50A/50B 50C FULTON V.T. BOILER, 15HP, NB 67249, GAS, 1993 50A) SCREW THREADS FOUND AT THE OUTLET END OF SAFETY VALVE ... $0 $0 Apr 11, 2005
Feb 26, 2005 32047196H RESOLVE Non-Hazardous 50 FULTON V.T. BOILER, 15HP, NB69390, GAS 1994 50 IMPROPER ARRANGEMENTOF THE BLOWDOWN VALVES INSTALL A SCREW-TYPE (SL... $0 $0 Apr 11, 2005
Jun 26, 2001 32025389R ACTIVE Non-Hazardous 18A, 49, 16, 49)MUST RECONNECT 2ND LOW WATER CUTOFF CONTROL 49)WATER COLOR DRAIN LINE IS REDUCED MUST BE SAME SIZE PI... $2,500 $0 Aug 20, 2001
Jun 14, 2001 34296029K ACTIVE Non-Hazardous ALTERED OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY UNDER JOB # 300304677-01A1 TO DIVIDE EXISTING BUILDING TO 6... $350 $0 Aug 6, 2001
May 21, 2001 34290505P RESOLVE Non-Hazardous WORK WITHOUT A PERMIT, NOTED:HAVING INSTALLED A MEZZANINE FLR. & DIVIDE EZXISTING BLDG. INTO 8TH SPACES.REM:OBTAIN PE... $500 $0 Jul 9, 2001
Feb 25, 1998 34171819X RESOLVE Non-Hazardous WORK WITHOUT A PERMIT. WORK NOTED, INSTALLATION OF A MEZZANINE FLOOR AND DIVIDING SPACE INTO EIGHT (8) SEPARATES ROOM... $500 $0 Jun 9, 1998
Jul 15, 1997 32014907Y ACTIVE Non-Hazardous PROVIDE PROOF OF REGISTERATION OF THIS BOILER. $400 $0 Dec 1, 1997
Dec 15, 1995 34123389Z RESOLVE Non-Hazardous WORK WITHOUT A PERMIT.MEZZANINE FLOOR HAS BEEN CONSTRUCTED AND SUBDIVIDED EXISTING BLDG INTO SIX SPACE(641-A TO F)REM... $0 $0 Mar 4, 1996
Feb 15, 1994 34104784P RESOLVE Non-Hazardous WORK WITOUT A PERMIT WORK NOTED HAVING INSTALLED A MEZZANINE FLOOR AND DIVIDE EXISTING BUILDING INTO EIGHT SPACES OTE... $175 $0 May 2, 1994
Feb 15, 1994 34104785R ACTIVE Hazardous OCCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY #215370 STATES FOOD PRODUCTS PROCESSING (BAKERY) ... $800 $0 Apr 18, 1994
Feb 4, 1994 34105679H RESOLVE Non-Hazardous WORK WITHOUT A PERMIT ENTIRE BUILDING HAS BEEN SUB DIVIDED INTO SIX SEPERATE SECTIONS. REMEDY:OBTAIN ALL PERMITS. $175 $0 Apr 18, 1994
May 10, 1993 34091005R ACTIVE Non-Hazardous OCCUPANCY CONTRARY TO THAT ALLOWED BY THE COFO#215370/77 BUILDING SUB DIVIDED INTO 8 DIFFERENCE OCCURPANCIES 641 62 S... $1,000 $0 Aug 16, 1993
May 6, 1993 34090684N ACTIVE Non-Hazardous PLUMBING WORK WITHOUT PERMIT: SIX SETS OF TOILET ROOMS, SIX KITCHEN, AND H.P BOILERS. REMEDY: OBTAIN A PLUMBING PERMI... $1,500 $0 Aug 16, 1993
Jul 18, 1988 32000664L RESOLVE Non-Hazardous CALL FOR REINSPECTION 312 8275 $0 $0 Sep 12, 1988
Jul 18, 1988 32000662H RESOLVE Non-Hazardous CALL FOR REINSPECTION 312 8275 $0 $0 Sep 12, 1988
Jul 18, 1988 32000663J RESOLVE Non-Hazardous CALL FOR REINSPECTION (212) 312 8275 $0 $0 Sep 12, 1988