ECB violations
641-669 62 Street, Brooklyn • Block 05793 • Lot 0052
46 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 4, 2025 | 39169253P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED AT REAR OF BUILDING AT EXPOSURE 3 THERE IS EXCESSIVE D... | $5,000 | $0 | Feb 11, 2026 |
| Apr 25, 2024 | 39112633J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED : OBSERVED AT REAR OF BUILDING AT EXPOSURE 3 THERE IS EX... | $1,250 | $0 | Feb 10, 2025 |
| Apr 25, 2024 | 39112630Y | ACTIVE | CLASS - 2 | WORK WITHOUT A PERMIT. NOTED : OBSERVED AT REAR OF BUILDING, AT EXPOSURE 3 A CANOPY WAS ERECTED ,THERE IS NO JOB FILI... | $1,250 | $0 | Aug 7, 2024 |
| Jun 23, 2022 | 39064647R | ACTIVE | CLASS - 3 | THE GAS BOILER AND GAS HOT WATER HEATER WERE REMOVED WITHOUT THE WATER PIPE AND THE GAS PIPE AND THE CHIMNEY AND THE ... | $500 | $0 | Oct 26, 2022 |
| Apr 19, 2022 | 39060539L | ACTIVE | CLASS - 1 | I OBSERVED IN COMMERCIAL SPACE MARKED 641F AN ILLEGAL BOILER INSTALLATION AND WATER HEATER SEVERAL GAS FLEXES INSTALL... | $625 | $0 | Aug 24, 2022 |
| Apr 19, 2022 | 39060540Z | ACTIVE | CLASS - 1 | I OBSERVED IN COMMERCIAL AREA OF 641F BUILDING GAS BOILER INSTALLED WITH ALL GAS, WATER AND FLU PIPING AND NO PERMITS... | $2,500 | $0 | Aug 24, 2022 |
| Apr 19, 2022 | 39060544X | ACTIVE | CLASS - 1 | FOUND GAS HOT WATER HEATER(UNKNOWN MAKE AND MODEL#) HAD TO CEASE USE WATER HEATER DUE TO HEATER BEING MOUNTED ON COMB... | $1,250 | $0 | Aug 24, 2022 |
| Apr 19, 2022 | 39060541K | ACTIVE | CLASS - 1 | I OBSERVED IN COMMERCIAL BUILDING MARKED 641F BOILER INSTALLED WITHOUT ANY PERMITS ON FILE; THEREFORE NO PROPER TESTI... | $1,250 | $0 | Aug 24, 2022 |
| Apr 19, 2022 | 39060797Y | ACTIVE | CLASS - 2 | FOUND H B SMITH(MODEL# 5210 S/W5) GAS FIRED BOILER IN REAR OF FACTORY NOT REGISTERED, MAINTAIN BOILER; REGISTER BOILE... | $625 | $0 | Sep 28, 2022 |
| Apr 19, 2022 | 39060536X | ACTIVE | CLASS - 1 | FOUND H B SMITH(MODEL#5210S/W5) GAS FIRED BOILER HAD TO CEASE USE BOILER DUE TO BOILER BEING MOUNTED ON A COMBUSTIBLE... | $1,250 | $0 | Aug 24, 2022 |
| Apr 19, 2022 | 39060538J | ACTIVE | CLASS - 1 | I OBSERVED IN COMMERCIAL BUILDING MARKED 641F BOILER INSTALLED WITHOUT ANY PERMITS ON FILE; THEREFORE NO PROPER GAS A... | $5,000 | $0 | Aug 24, 2022 |
| Aug 12, 2016 | 32077504H | RESOLVE | CLASS - 2 | 3A,50A,50B. FULTON YT BOILER, 15HP, NB67249, HP STM, GAS, 1993. 3A) SURFACE CORROSION ON SECTIONS OF THE FILE PIPE RU... | $250 | $0 | Nov 16, 2016 |
| Aug 12, 2016 | 32077500K | RESOLVE | CLASS - 1 | CEASE USE. 50A,51. FULTON VT BER, 15HP NB64456, HP STM, GAS, 1992 50(A)REFERENCED BOILER WAS FOUND IN OPERATION W/ A ... | $1,000 | $0 | Nov 16, 2016 |
| Aug 11, 2009 | 32066711R | RESOLVE | CLASS - 3 | 48B,50A,50B 50A- REMOVE COOPER SOLDERED PIPES ON BOILER FEED PUMP AND INSTALL THREADED APPROVED TIRE PIPING. 50B- INS... | $0 | $0 | Oct 5, 2009 |
| Aug 11, 2009 | 32066713K | RESOLVE | CLASS - 3 | 18B | $0 | $0 | Oct 5, 2009 |
| Aug 11, 2009 | 32066712Z | RESOLVE | CLASS - 2 | 18B,50A,50B 50A- LOWER LEFT HAND HOLE AREA COMPLETELY COVERED WITH CEMENT UNABLE TO INSPECT CONDITION OF HANDHOLE AND... | $500 | $0 | Oct 5, 2009 |
| Jul 24, 2009 | 32066702P | RESOLVE | CLASS - 3 | 18B.48B.50A 50A REPLACE CORRODED NIPPLE ON BOILER FEED LINE | $500 | $0 | Sep 14, 2009 |
| May 30, 2008 | 32056468R | RESOLVE | Hazardous | 50A50B. 50A DISCHARGE PIPE CAUSING STRESS ON SAFETY VALVE. 50B INSTALLSTRUCTURAL SUPPORT FOR FLUE PIPE (CHANNEL & THR... | $0 | $0 | Jul 21, 2008 |
| May 30, 2008 | 32056466N | RESOLVE | Non-Hazardous | 3850A50B24C. 38 FRESH AIR BLOCKED. 50A INSTALL STRUCTURAL SUPPORT FOR PIPE CHANNEL AND THREADED ROD. 50B CLEAN BOILER... | $0 | $0 | Jul 21, 2008 |
| May 30, 2008 | 32056470X | RESOLVE | Hazardous | 18A18B50A48A48B. 50A INSTALL STRUCTURAL SUPPORT ON FLUE PIPE. (CHANNEL& THREADED ROD) | $0 | $0 | Jul 21, 2008 |
| May 30, 2008 | 32056471H | RESOLVE | Hazardous | 18A18B50A. 50A INSTALL STRUCTURAL SUPPORT ON FLUE PIPE. (CHANNEL & THREADED ROD) | $0 | $0 | Jul 21, 2008 |
| May 30, 2008 | 32056467P | RESOLVE | Hazardous | 50A18B50B. 50A LARGE AMOUNT OF DEBRIS AND STORAGE IN BOILER. 50B INSTALL PROPER SUPPORT FOR FLUE PIPE (CHANNEL & THRE... | $2,500 | $0 | Feb 9, 2009 |
| May 30, 2008 | 32056469Z | RESOLVE | Hazardous | 18B50A50B24B. 50A LOW WATER RESET SWITCH DISCONNECTED. 50B INSTALL STRUCTURAL SUPPORT ON FLUE PIPE (CHANNEL & THREADE... | $0 | $0 | Jul 21, 2008 |
| Oct 4, 2006 | 32051096M | RESOLVE | Non-Hazardous | 50A/50B/48B/44C/50C/50A-SAFETY VALVE LEAKING/50B-WATER COLUMN LEAKING/50C-CLEAN BOILER RM REMOVE DEBRIS | $0 | $0 | Nov 20, 2006 |
| Oct 4, 2006 | 32051095K | RESOLVE | Non-Hazardous | 18A/18B/48B/50A/50B/50C/50A-REVERSE BLOWDOWN VALVE TO HAVE SLOW OPENING VALVE TERMINATE LAST/50B-CLEAN DEBRIS FROM BO... | $0 | $0 | Nov 20, 2006 |
| Oct 4, 2006 | 32051094Z | RESOLVE | Non-Hazardous | 18A/18B/48B/50A/50A-FEEDLINE TO BOILER LEAKING | $0 | $0 | Nov 20, 2006 |
| Feb 28, 2005 | 32047200L | RESOLVE | Non-Hazardous | 50A/50B 50C FULTON V.T. BOILER, 15HP, NB 43713, GAS, 1983 50A) IMPROPER ARRANGEMENT OF THE BLOWDOWN VALVES. INSTALL S... | $2,500 | $0 | May 10, 2006 |
| Feb 28, 2005 | 32047199N | RESOLVE | Non-Hazardous | 50A/48AB FULTON V.T. BOILER, 15HP, NB64480, GAS, 1992 50A) IMPROPER ARRANGEMENT OF THE BLOWDOWN VALVES. INSTALL A SCR... | $0 | $0 | Apr 18, 2005 |
| Feb 28, 2005 | 32047201N | RESOLVE | Non-Hazardous | 50 FULTON V.T. BOILER, 15HP, NB64478, GAS 1992 50 NO SECONDARY SCREW TYPE (SLOW) SHUT OFF VALVE ON THE BLOWDOWN LINE. | $0 | $0 | Apr 18, 2005 |
| Feb 28, 2005 | 32047198L | RESOLVE | Non-Hazardous | 50A/50B 50C/50D 50E FULTON V.T. BOILER, 15HP, NB66456, GAS, 1992 50A) NO DISCHARGE PIPE ON THE SAFETY VALVE. 50B) NO ... | $2,500 | $0 | Apr 18, 2005 |
| Feb 26, 2005 | 32047197J | RESOLVE | Non-Hazardous | 50A/50B 50C FULTON V.T. BOILER, 15HP, NB 67249, GAS, 1993 50A) SCREW THREADS FOUND AT THE OUTLET END OF SAFETY VALVE ... | $0 | $0 | Apr 11, 2005 |
| Feb 26, 2005 | 32047196H | RESOLVE | Non-Hazardous | 50 FULTON V.T. BOILER, 15HP, NB69390, GAS 1994 50 IMPROPER ARRANGEMENTOF THE BLOWDOWN VALVES INSTALL A SCREW-TYPE (SL... | $0 | $0 | Apr 11, 2005 |
| Jun 26, 2001 | 32025389R | ACTIVE | Non-Hazardous | 18A, 49, 16, 49)MUST RECONNECT 2ND LOW WATER CUTOFF CONTROL 49)WATER COLOR DRAIN LINE IS REDUCED MUST BE SAME SIZE PI... | $2,500 | $0 | Aug 20, 2001 |
| Jun 14, 2001 | 34296029K | ACTIVE | Non-Hazardous | ALTERED OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY UNDER JOB # 300304677-01A1 TO DIVIDE EXISTING BUILDING TO 6... | $350 | $0 | Aug 6, 2001 |
| May 21, 2001 | 34290505P | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT, NOTED:HAVING INSTALLED A MEZZANINE FLR. & DIVIDE EZXISTING BLDG. INTO 8TH SPACES.REM:OBTAIN PE... | $500 | $0 | Jul 9, 2001 |
| Feb 25, 1998 | 34171819X | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT. WORK NOTED, INSTALLATION OF A MEZZANINE FLOOR AND DIVIDING SPACE INTO EIGHT (8) SEPARATES ROOM... | $500 | $0 | Jun 9, 1998 |
| Jul 15, 1997 | 32014907Y | ACTIVE | Non-Hazardous | PROVIDE PROOF OF REGISTERATION OF THIS BOILER. | $400 | $0 | Dec 1, 1997 |
| Dec 15, 1995 | 34123389Z | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT.MEZZANINE FLOOR HAS BEEN CONSTRUCTED AND SUBDIVIDED EXISTING BLDG INTO SIX SPACE(641-A TO F)REM... | $0 | $0 | Mar 4, 1996 |
| Feb 15, 1994 | 34104784P | RESOLVE | Non-Hazardous | WORK WITOUT A PERMIT WORK NOTED HAVING INSTALLED A MEZZANINE FLOOR AND DIVIDE EXISTING BUILDING INTO EIGHT SPACES OTE... | $175 | $0 | May 2, 1994 |
| Feb 15, 1994 | 34104785R | ACTIVE | Hazardous | OCCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY #215370 STATES FOOD PRODUCTS PROCESSING (BAKERY) ... | $800 | $0 | Apr 18, 1994 |
| Feb 4, 1994 | 34105679H | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT ENTIRE BUILDING HAS BEEN SUB DIVIDED INTO SIX SEPERATE SECTIONS. REMEDY:OBTAIN ALL PERMITS. | $175 | $0 | Apr 18, 1994 |
| May 10, 1993 | 34091005R | ACTIVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE COFO#215370/77 BUILDING SUB DIVIDED INTO 8 DIFFERENCE OCCURPANCIES 641 62 S... | $1,000 | $0 | Aug 16, 1993 |
| May 6, 1993 | 34090684N | ACTIVE | Non-Hazardous | PLUMBING WORK WITHOUT PERMIT: SIX SETS OF TOILET ROOMS, SIX KITCHEN, AND H.P BOILERS. REMEDY: OBTAIN A PLUMBING PERMI... | $1,500 | $0 | Aug 16, 1993 |
| Jul 18, 1988 | 32000664L | RESOLVE | Non-Hazardous | CALL FOR REINSPECTION 312 8275 | $0 | $0 | Sep 12, 1988 |
| Jul 18, 1988 | 32000662H | RESOLVE | Non-Hazardous | CALL FOR REINSPECTION 312 8275 | $0 | $0 | Sep 12, 1988 |
| Jul 18, 1988 | 32000663J | RESOLVE | Non-Hazardous | CALL FOR REINSPECTION (212) 312 8275 | $0 | $0 | Sep 12, 1988 |