| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jul 28, 2010 | 32068815K | ACTIVE | CLASS - 3 | 50A/50B/50C/HURST V.T BOILER,NB 5346,HP STM,GAS 1998/50A-BAROMETRIC DAMPER ASSEMBLY ON FLUE PIPE CORRODED.REPLACE DEF... | $500 | $0 | Sep 20, 2010 |
| Jul 25, 2008 | 32060282K | ACTIVE | CLASS - 3 | 6A, HURST VT BOILER GAS FIRED 1998 6A, CONTNUOUS STEAM LEAKAGE AT THE SAFETY VALVE INSTALL AN ASME APPROVED REPLACEME... | $500 | $0 | Sep 22, 2008 |
| Jun 24, 2008 | 32056769K | ACTIVE | Hazardous | 1 50A 50B CARBON MONOXIDE SPILLAGE FROM DRAFT STAT 200PPM BOILER WAS OOPERATING AGAIN DOB CEASE USE. 50B BOILER WAS C... | $2,500 | $0 | Aug 18, 2008 |
| Jun 13, 2008 | 32056762H | ACTIVE | Hazardous | 27-127 50A,32A,51,50B,50C,50D,38,50E,24B,50F,48 50A CARBON MONOXIDE SPILLAGE FROM DRAFT STAT LVLS OF 320 PPM READINGS... | $2,500 | $0 | Aug 4, 2008 |
| Jun 13, 2008 | 32056763J | ACTIVE | Hazardous | 27-127 50A,51 50A CORRODED FLUE PIPE ECHAUST FROM HOT WATR HEATER SPILLING CARBON MONOXIDE LVLS OF 156 PPM WAS READIN... | $2,500 | $0 | Aug 4, 2008 |
| Sep 27, 2006 | 32051077R | ACTIVE | Hazardous | CEASE USE 3-B/50A/50B/50C/50D/50E/50A-COMBUSTION GAS SPILLAGE @ DRAFT REGULATOR/50B-CHIMNEY BASE NOT SEALED/50C-SEAL ... | $2,500 | $0 | Nov 6, 2006 |
| Feb 19, 2005 | 32047179X | ACTIVE | Non-Hazardous | 50A/50C/50B HURST V.T BOILER 10HP NB 5346 GAS 1998 50A- DISLOCATED CEILING TILES ABOVE BOILER RESTORE FIREPROOF CEILI... | $2,500 | $0 | Oct 3, 2005 |
| Oct 10, 1998 | 32016515Y | RESOLVE | Non-Hazardous | 16,36. 16-BOILER NUMBER/INSPECTION CAR NOT DISPLAYED. 36-BOILER NOT REGISTERED. (BQ9) (27-147) BOILER INSTALLED W/O W... | $0 | $0 | Jan 11, 1999 |