ECB violations

182 Bay Ridge Avenue, Brooklyn • Block 05870 • Lot 0033

8 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jun 11, 2008 32056759R RESOLVE Non-Hazardous 50A 50A-SPILLAGE OF CARBON MONXIDE FROM GAS FIRED HOT WATER HEATERS LEVEL OF 100PPM IN BOILER ROOM CLEAN AND ADJUST F... $400 $0 Aug 4, 2008
Sep 27, 2006 32051079K RESOLVE Hazardous 50A/50B/50C/50D/B4B/50A-COMBUSTION GAS SPILLAGE @ DRAFT REGULATOR/50B-CONDENSATE TANK LEAKAGE/50C-WATER COLUMN CONNEC... $800 $0 Nov 6, 2006
Feb 19, 2005 32047182R RESOLVE Non-Hazardous 50/48B COLUMBIA V.T .BOILER 15HP MN 130260 GAS 1991 50 NO DISCHARGE ONTHE SAFTEY VALVE 48B LEAKING GAUGE GLASS $180 $0 Apr 4, 2005
Oct 5, 2001 32025740P RESOLVE Non-Hazardous 16-36-49 MUST INSTALL A DISCHARGE PIPE ON SAFETY VALVE & ON SITE GLASS FLU PIPE IS NOT SCALED INTO CHIMNEY BQ9-27-147... $430 $0 Dec 12, 2001
Oct 2, 2001 32026102P RESOLVE Non-Hazardous 19B-21B-49A-49B. 49A-INSTALL BACK FLOW PREVENTOR CHECK VALUE ON BOILER COLD WATER FEED LINE. 49B-PIPE DOWN SAFTY VALU... $180 $0 Nov 19, 2001
Oct 16, 2000 32021094L RESOLVE Non-Hazardous 48C/49 WATER COLUMN STOP VALUE HANDLE MISSING 2 MC DONALD MILLER LOW WATER CUT OUT MANUAL RESET MECHANISM MISSING. $180 $0 Dec 4, 2000
Oct 10, 1998 32016511R RESOLVE Hazardous 3B,49. 3B-FLUE PIPE FUMES. 49-FLUE PIPE FROM THE BOILER NOT SEAL GASTIGHT IN CHIMNEY BASE. $400 $0 Dec 28, 1998
Dec 14, 1992 32009760M RESOLVE Non-Hazardous 36,32. 32 FLUE PIPE NOT PROPERLY AND CORRECTLY ATTACHED WITH THE BREECHING FROM THE OTHER BOILER. $200 $0 Feb 22, 1993