ECB violations
71 Street, Brooklyn • Block 06180 • Lot 0001
60 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 9, 2026 | 35728632H | ACTIVE | CLASS - 2 | REISSUE: 35676261X-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE GAS, METER ROOM THERE'S WATER DAMAGE... | $3,125 | $0 | Mar 9, 2026 |
| Feb 20, 2024 | 35676261X | ACTIVE | CLASS - 2 | REISSUE#35657631K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT CELLAR GAS METER ROOM WITHOUT IN FUTRATED ... | $1,562 | $0 | May 2, 2024 |
| Feb 20, 2024 | 35676262H | RESOLVE | CLASS - 2 | REISSUE#35657630Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:AT 1ST FLOOR EXIT#5 NOT CLOSE PROPERLY DUE TO... | $1,562 | $0 | May 2, 2024 |
| Feb 20, 2024 | 35676260Y | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING.C 18FLOOR#4 & 5 NOT SELF CLOSED.REISSUE#35657632M.REM:REPAIR/REPLACE DOOR. | $1,562 | $0 | May 2, 2024 |
| Jan 19, 2023 | 35657631K | ACTIVE | CLASS - 2 | RE-ISSUE #35591686Z FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:OBSERVED AT CELLAR LEVEL IN GAS METER... | $1,562 | $0 | Apr 12, 2023 |
| Jan 19, 2023 | 35657630Z | RESOLVE | CLASS - 2 | RE-ISSUE #35591687K FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:OBSERVED ON 1ST FL AT EXIT #5 DOOR NO... | $1,562 | $0 | Apr 12, 2023 |
| Jan 19, 2023 | 35657632M | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.NOTED:OBSERVED ON 1ST FL EXIT #4 DOORS NOT CLOSING PROPERLY BECAUSE DOORS HITTING ON DOOR ... | $625 | $0 | Apr 12, 2023 |
| Jul 19, 2022 | 39066175R | ACTIVE | CLASS - 2 | CORRODED RETURN LINE, CORRORDED HAND HOLES, MANUAL RESET LOW WATER CUT OFF MISSING, CONTROLS NOT ON STEAM HEADER PIPING. | $625 | $0 | Jul 27, 2022 |
| Apr 6, 2022 | 35591687K | RESOLVE | CLASS - 2 | REISSUE#35548383H.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED EXIT 4 ON THE FIRST FLOOR,EXIT C ON THE... | $1,562 | $0 | Sep 21, 2022 |
| Apr 6, 2022 | 35591686Z | ACTIVE | CLASS - 2 | REISSUE#35548384J.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED OBSERVED AT GAS METER ROOM AT BASEMENT ... | $625 | $0 | Sep 21, 2022 |
| May 28, 2021 | 35556753X | RESOLVE | CLASS - 2 | FAILRUE TO MAINTAIN/DISPLAY ON SITE DOCUMENTS BY BC CHAPTER 33. AT TIME OF INSPECTION OF AN PROPOSED STAND ALONG 1 ST... | $0 | $0 | Oct 6, 2021 |
| Mar 26, 2021 | 35548384J | ACTIVE | CLASS - 2 | REISSUE35495744H FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTE:OBSERVED IN GASMETERRM WALLS HAVE DAMAGE DUE T... | $1,562 | $0 | Sep 1, 2021 |
| Mar 26, 2021 | 35548383H | RESOLVE | CLASS - 2 | REISSUE35495745J FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTE:OBSERVED STAIRWAY FIREPROOF SELFCLOSING DOOR@3... | $1,562 | $0 | Sep 1, 2021 |
| Mar 26, 2021 | 35548382X | RESOLVE | CLASS - 2 | REISSUE35495749P FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTE:OBSERVED@1FLRM 102,103A,106,106A(SCHOOL AIDE R... | $1,562 | $0 | Sep 1, 2021 |
| May 26, 2020 | 35495745J | RESOLVE | CLASS - 2 | REISSUE#35423319Y FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NOTED: OBSERVED STAIRWAY FIRE PROOF SELF CLOSING... | $1,562 | $0 | Jul 6, 2020 |
| May 26, 2020 | 35495748P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:OBSERVED CLASSROOM DOORS AT 3RD FLOOR TWO ROOMS BY STAIR ... | $625 | $0 | Jul 6, 2020 |
| May 26, 2020 | 35495746L | RESOLVE | CLASS - 2 | REISSUE#35423320L FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NOTED: OBSERVED HORIZONTAL CRACK IN THE WALL AT ... | $1,562 | $0 | Jul 6, 2020 |
| May 26, 2020 | 35495747N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATIONS FOR EXITS,EXIT DISCHARGE AND PUBLIC CORRIDORS PER... | $625 | $0 | Jul 6, 2020 |
| May 26, 2020 | 35495744H | ACTIVE | CLASS - 2 | REISSUE#35423317K FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NOTED: OBSERVED IN GAS METER ROOM WALLS & CEILIN... | $1,562 | $0 | Jul 6, 2020 |
| May 30, 2019 | 35423318M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.USE OF PROHIBITED DOOR AND OR HARWARE PER BC1008.1.8/27-371(J).... | $0 | $0 | Oct 7, 2019 |
| May 30, 2019 | 35423319Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT 2ND FLRSTAIRCASE D,E 1ST FLR STAIRCASE B,D,C EXITS 3,4... | $0 | $0 | Oct 7, 2019 |
| May 30, 2019 | 35423317K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT 3RD FLOOR STAIRCASE B,C,E BASEMENT GAS METER ROOM WITH... | $0 | $0 | Oct 7, 2019 |
| May 30, 2019 | 35423320L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER.NOTED:AT BASEMENT ELECTRICA METER ROOM WALLS AND CEILINGS WITH ... | $0 | $0 | Oct 7, 2019 |
| Mar 23, 2018 | 35325348Y | RESOLVE | CLASS - 2 | SEC. 28-301.1 UNLAWFUL DISPLAY OF ARTWORK IN CORRIDORS GREATER THAN 20% PER FDNY 2008 CODE;FC 803.3.2. NOTED: ARTWORK... | $0 | $0 | Jun 11, 2018 |
| Apr 28, 2017 | 35235412K | RESOLVE | CLASS - 2 | RE-ISSUE # 35207914M. EXIT DOOR NOT SELF CLOSING. NOTED: @ 1ST FL EXITDOOR "E" & @ 3RD FL SMOKE DOOR "D" DON'T CLOSE ... | $0 | $0 | Jul 17, 2017 |
| Apr 28, 2017 | 35235413M | RESOLVE | CLASS - 2 | B206,2,28-301.1. UNLAWFUL DISPLAY OF ARTWORK IN CORRIDORS GREATER THAN20% FOR FDNY 2008 CODE; FC803.3.2. NOTED: ARTWO... | $0 | $0 | Jul 17, 2017 |
| Apr 28, 2017 | 35235414Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: @ ELECTRICAL ROOM @ ... | $0 | $0 | Jul 17, 2017 |
| Oct 5, 2016 | 35207912Z | RESOLVE | CLASS - 2 | RESSIUE #351218828K FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED:DEFECTIVE FLR @TRANSPORTABLE CLASSROOMS (... | $0 | $0 | Jan 9, 2017 |
| Oct 5, 2016 | 35207913K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER:NO FIRE STOPPING PERBC 712.3;27-345NOTED: @GAS METER ROOM 2"-4" HOL... | $0 | $0 | Jan 9, 2017 |
| Oct 5, 2016 | 35207914M | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING.NOTED:EXIT DOOR "E" @1ST FLR AND SMOKE DOOR"D" @3RD FLR DO OT CLOSE PROPERTY DUE TO DEFECT... | $0 | $0 | Jan 9, 2017 |
| Jun 5, 2015 | 35128828K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.SAGGING FLOORS REISSUE ECB 35094345N IN TRANSPORTABLES 1 + 2 FLOORS... | $0 | $0 | Aug 3, 2015 |
| Apr 28, 2014 | 35094344L | RESOLVE | CLASS - 2 | SPALLING PLASTER WALL. AT RM 306, SPALLING PLASTER WALL BEHIND RADIATORS. REMEDY: REPAIR SPALLING PLASTER WALLS. | $0 | $0 | Jun 16, 2014 |
| Apr 28, 2014 | 35094345N | RESOLVE | CLASS - 2 | RE-ISSUE # 34918118X. SAGGING FLOOR. THE FLOORS, IN VARIOUS SPOTS, ARE SASGGING AND CAUSING TILES TO CRACK AND POP OF... | $0 | $0 | Jun 16, 2014 |
| Jun 10, 2013 | 35022737J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER (INTERIOR). NOTED: DEFECTIVE FLRING - SOFT SAGGING SPOTS. RE-ISSUE ... | $0 | $0 | Aug 19, 2013 |
| May 31, 2013 | 35022729J | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. NOTED: 1) EXIT DOOR STAIR 'B'. 2) NW EXIT DOOR TO EXTERIOR (DOUBLE-DOOR). BOTH 1 & 2. REM... | $0 | $0 | Aug 19, 2013 |
| May 31, 2013 | 35022731Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. NOTED: TOOLS,BICYCLE,PAINTS,ADHESIVE,CLEANING FLUIDS & FURNITURE B... | $0 | $0 | Aug 19, 2013 |
| May 31, 2013 | 35022730R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: PIPE INSULATIONS AT BOILER ROOM ARE TORN AND/OR MISSING. RE... | $0 | $0 | Aug 19, 2013 |
| May 31, 2013 | 35022732K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. NOTED: CHAIN LINK FENCE, APPROX 18' LONG X 10' HIGH IS MISSHAPEN &... | $0 | $0 | Aug 19, 2013 |
| May 31, 2013 | 35022733M | RESOLVE | CLASS - 2 | SEC. 27-766. FRESH AIR IN GAS METER ROOM. NOTED: FRESH AIR VENT NOT WORKING. REMEDY: REPAIR/REPLACE. | $0 | $0 | Aug 19, 2013 |
| Mar 30, 2012 | 34949906Z | RESOLVE | CLASS - 2 | CRACKED VCT FLOOR TILE,SOFT,DETERIORATED SUB-FLOORING. AT: TRANSPORTABLE CLASSROOMS DESIGNATED T-1 & T-2 VARIOUS LOCA... | $0 | $0 | Jun 4, 2012 |
| Jun 28, 2011 | 34918118X | RESOLVE | CLASS - 2 | DEFECTIVE FLOORING IN T-1 NOTED:SOFT SAGGING SPOTS THROUGHOUT.REM:REPAIR FLOORING | $0 | $0 | Sep 12, 2011 |
| Jun 28, 2011 | 34918117Y | RESOLVE | CLASS - 2 | MISSING MORTAR JOISTS THROUGHOUT PARAPET WALL.REM:MAKE REPAIRS | $0 | $0 | Sep 12, 2011 |
| Apr 22, 2010 | 34847861R | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN OBSERVED AT ROOF PARAPET 71ST SIDE APP 8'LF ROOF FLASHING MISSING ABOVE BASE OF PARAPET REM: REPL... | $0 | $0 | Jul 19, 2010 |
| Apr 22, 2010 | 34847862Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN OBSERVED GAS & ELECTRIC METER RMS USED FOR STORAGEOF SCHOOL MAIN TENANCE SUPPLIES AND EQUIPMENT | $0 | $0 | Jul 19, 2010 |
| Apr 22, 2010 | 34847863K | RESOLVE | CLASS - 2 | 28-301.1 BC1001.3 FAILURE TO MAINTAIN EGRESS CLEAR AND UNOBSTRUCTED OBSERVED AT EXIT CORRIDORS ADJACENT AUDITORIUM ST... | $0 | $0 | Jul 19, 2010 |
| Mar 2, 2006 | 34509944K | RESOLVE | Non-Hazardous | GAS METER ROOM AND ELECTRICAL ROOM IN THE BASEMENT HAS STORAGE OF CHAIRS, COMPUTERS, CARDBOARD BOXES (WITH LAMPS) FIL... | $0 | $0 | Apr 17, 2006 |
| Feb 24, 2003 | 34387296Z | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE PANIC HARDWARE WEHRE REQUIRED BY ALW LOCATION ; CAFETERIA / GYM ( SAME AREA ) EXIT DOORS # 2, 3, 4... | $0 | $0 | Jun 9, 2003 |
| Feb 24, 2003 | 34387297K | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. NOTED ROOF DRAINS LEAK AROUND SEAL CAUSING WATER TO SEEP INTO CLASSROOM CIELINGS NO VICIBLE WATE... | $0 | $0 | Jun 9, 2003 |
| Feb 24, 2003 | 34387298M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN NOTED, HEAVY WATER ENTERING THROUGH ASH ROOM, HOIST DOORS LEAK DURING RAIN OR SNOW MELTING. LEAKI... | $0 | $0 | Jun 9, 2003 |
| Feb 24, 2003 | 34387299Y | RESOLVE | Hazardous | FAILURE TO MAINTAIN. NOTED MAIN ENTRANCE STEPS ( CONCRETE ) BROKEN, LOOSE, CRACKED NOTED AT TIME OF INSPECTION, SECTI... | $0 | $0 | Jun 9, 2003 |