ECB violations
1806-1816 Ocean Avenue, Brooklyn • Block 06748 • Lot 0016
40 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Aug 4, 2026 | 39199009K | ACTIVE | CLASS - 2 | 1) PROVIDE IN MR GUARDING TO ELEVATOR PIT. 2) UNSECURED HOIST MACHINE/HOIST MOTOR PROVIDE COVER. 3) SEAL/PATCH HOIST ... | $625 | $625 | Oct 14, 2026 |
| Jul 17, 2026 | 39196638J | ACTIVE | CLASS - 2 | INOPERATIVE PHONE (2.27.1.1.3.). ADJUST FLOOR STOPS. MISALINGED CAB MIRROR(B3 3001.6). REMOVE ALL ITEMS FROM THAT ARE... | $625 | $625 | Sep 23, 2026 |
| Jun 30, 2026 | 39194243X | ACTIVE | CLASS - 2 | A8 OBSERVED AT EXPOSURE 4 SIDE OF BUILDING A VERTICAL SECTIONS OF MISSING MORTAR, REPAIR AND/OR REPLACE | $1,250 | $1,250 | Sep 9, 2026 |
| Feb 17, 2026 | 39177504K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 2 ITEMS: 1) MOTOR ROOM INACCESSIBLE, PROVIDE ACCESS. 2) ... | $3,125 | $3,125 | May 6, 2026 |
| Sep 19, 2025 | 39160992H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION IN CELLAR I OBSERVED ILLEGAL GAS FLEXIBL... | $6,250 | $6,250 | Nov 26, 2025 |
| Sep 19, 2025 | 39160993J | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC... | $12,500 | $12,500 | Nov 26, 2025 |
| Sep 14, 2025 | 39160335H | ACTIVE | CLASS - 1 | AT TIME OF INSPECTION OBSERVED AT CELLAR LEVEL LAUNDRY ROOM WHERE NO INGRESS/EGRESS EXCEPT ELEVATOR (ALL THREE DOORS ... | $2,500 | $2,500 | Jul 27, 2026 |
| Sep 12, 2025 | 39160181Y | RESOLVE | CLASS - 2 | INOPERATIVE CAR PHONE. ADJUST FLOOR STOPS. WORN CAR SADDLE. MUTED ALARM BELL. MISALIGNED CAB MIRROR. LABEL EMERGENCY ... | $0 | $0 | Nov 19, 2025 |
| Apr 9, 2025 | 39144433L | RESOLVE | CLASS - 1 | CEASE USE ITEMS: 1) ZONE LOCK RESTRICTOR REMOVED. 2) GAP BETWEEN RIGHT BRAKE PAD AND DRUM APPROXIMATELY 40%. REMEDY: ... | $3,125 | $3,125 | Jun 18, 2025 |
| Feb 12, 2024 | 39105836Y | ACTIVE | CLASS - 1 | CLASS 1: CEASE USE ITEMS: REPAIR IN-CAR EMERGENCY PHONE., REPAIR IN-CAR ALARM SYSTEM (NO AUDIBLE ON THE IN-CAR EMERGE... | $12,500 | $12,500 | Apr 17, 2024 |
| Dec 28, 2023 | 39102403P | ACTIVE | CLASS - 1 | CEASE USE ITEMS: 1) NON WORKING PHONE AND MUTED ALARM BELL. 2) MISSING SELECTOR CHAIN SWITCH PER K3. 3) WORN/MISALING... | $1,250 | $1,250 | Apr 17, 2024 |
| Sep 12, 2022 | 39069848X | ACTIVE | CLASS - 2 | FOUND FEDERAL DUAL FUEL BOILER MODEL FST-60 ACTIVE WITH DEFECTS. GAS TRAIN NEEDS TO BE PROPERLY SUPPORTED. SIGNS OF F... | $3,125 | $3,125 | Jan 18, 2023 |
| Sep 9, 2020 | 39028364Z | ACTIVE | CLASS - 1 | 1) DOOR ZONE RESTRICTOR IS NOT WORKING (CEASE USE) 2) NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATE... | $1,280 | $0 | Jan 13, 2021 |
| Oct 28, 2019 | 39011833L | RESOLVE | CLASS - 2 | NO BOILER ROOM ACCESS SIGN POSTED WHICH IS LEGIBLE & VISIBLE FROM THE FRONT DOOR.CORRECT VIOLATING CONDITION& SUBMIT ... | $1,562 | $1,562 | Mar 4, 2020 |
| Dec 6, 2014 | 38233673Z | RESOLVE | CLASS - 1 | CU-05L01,CU-59L01,69M07,05M07,05L10,05M07,R-40M07,39G02,R70O02,R71L10,R67M07. 05-CAR DOOR GAP TO LARGE (CLOSE DOOR ST... | $2,500 | $0 | Mar 2, 2015 |
| Feb 3, 2014 | 38230052M | ACTIVE | CLASS - 2 | 67M07,60Q07,09V01,70O02,70B07. 67M- NO TWO WAY COMMUNICATION (PHONE) 60Q- MOTOR ROOM LIGHT UNGUARDED. 09V- CAR IS OF ... | $500 | $0 | Mar 24, 2014 |
| Jun 1, 2010 | 38211038M | RESOLVE | CLASS - 2 | 05J10,37B10,99M07,69M07. 05J- CAR DOOR GAP FROM WHEN CLOSED. 37B- MAKEDOOR TO OVERHEAD SELF CLOSING SELF LOCKING SEAL... | $250 | $0 | Jul 26, 2010 |
| Oct 27, 2009 | 38207270P | RESOLVE | CLASS - 2 | 35Q3.42A1.60Q3.56Y10.100H11.35Q EXPOSED WIRES UNDER CAR 42A CAR DOOR TIMING 77M UNDER CAR LIGHT 58E DRY 100H CLOTH CO... | $0 | $0 | Dec 21, 2009 |
| Sep 12, 2008 | 38189673N | RESOLVE | CLASS - 3 | 56Y13.56O02.68M07.56 OIL LEAK MAIN MACHINE 56 CLEAN MAIN MACHINE 68 PROVIDE MAINTENANCE LOG | $200 | $0 | Nov 3, 2008 |
| Aug 3, 2007 | 38167755J | RESOLVE | Non-Hazardous | 55Y13.66O02.64Q03.64M07.59Q03.09I10.85U05.86U05.05O02.29B10.08A01.55-OIL LEAK MAIN MACHINE.66-CLEAN PIT.64-GUARD PIT ... | $180 | $0 | Sep 24, 2007 |
| Sep 1, 2004 | 32044189X | RESOLVE | Non-Hazardous | 34A 50D 44A 50E 32A 50F 50A 50B 50C 44A-STEAM GAUGE MUST READ TO 30 PSI 32A-WIRES ON OIL BURNER ARE EXPOSED IN SEVERA... | $0 | $0 | Oct 18, 2004 |
| Feb 12, 2004 | 38144798H | RESOLVE | Non-Hazardous | 05,J,01 09,D,06 55,Y,13 55,Y,02 39,Y,02 39,Q,08 05J TO PULLY CLOSE 09D MOLDING PIECE BY DOOR SADDLE LOOSE SCREWS MISS... | $0 | $0 | Mar 29, 2004 |
| Nov 13, 2003 | 38143099Y | RESOLVE | Non-Hazardous | 21L01/38O02/66O02/69L06/39O02/55O02/55Y13/59L10 21L BASE DOOR BREAKS CONTACT 69L COUNTER WEIGHT BUFFER SPRING LAYING ... | $350 | $0 | Jan 26, 2004 |
| Aug 20, 2003 | 34394472Y | RESOLVE | Hazardous | WORK WITHOUT A PERMIT. NOTED: ILLEGAL APT CONSTRUCTED IN CELLAR AT WEST SIDE OF BUILDING. W/ ONE BED ROOM BATHROOM AN... | $800 | $0 | Feb 2, 2004 |
| Aug 20, 2003 | 34394471M | RESOLVE | Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY #64100 NOTED: ILLEGAL APT CREATED IN THE CELLAR IN... | $800 | $0 | Feb 2, 2004 |
| Jul 28, 2003 | 38140749N | RESOLVE | Non-Hazardous | 51H14,08V07,09##,30Q03,21L07,16L01,21L#,38O02,38O02,66O02,39P07. 51H/ SHORTERN HOIST POPES. 09/# CAR URINATED D.21/L ... | $350 | $0 | Sep 15, 2003 |
| Jun 23, 2003 | 38139418K | RESOLVE | Non-Hazardous | 83,X,10 83X RESTORE DEVICE TO SERVICE SO THAT A COMPLETE INSPECTION CAN BE MADE | $350 | $0 | Dec 15, 2003 |
| Jun 2, 2003 | 38138849H | RESOLVE | Non-Hazardous | 33,Z,10 84,I,11 69,M,07 51,H,14,15,M,07 12,Q,03 08,V,01 84-1 REPLACE BROKEN SKYLIGHT OVER HATCHWAY 69-M CWT BUFFER 51... | $350 | $0 | Jan 12, 2004 |
| May 13, 2003 | 38137544M | RESOLVE | Non-Hazardous | 15M07,14O02,08V01,12Q03,62O02,19L11,16A01,16J11,16I14,05B01,29J01,48H15,65M07,55X11,21J11,80I11. 19-L SHAKING 3 FL ST... | $880 | $0 | Dec 15, 2003 |
| Mar 6, 2003 | 34391072L | RESOLVE | Hazardous | FAILURE TO MAINTAIN BLDG. -HAZARDOUS- NOTED:AT EXTERIOR BLDG 2ND FLR APT. 2D(SOUTH) 1. HEAVY LEAK ALL AREA APARTMENT ... | $800 | $0 | Dec 15, 2003 |
| Dec 23, 2002 | 34389718Z | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDNG : NOTE : IN APT. 2D BULDGING CEILING AND PEELING POINT AT VARIOUS LOCATIONS IN LIVING ROO... | $180 | $0 | Oct 27, 2003 |
| Jul 23, 2002 | 34325985K | RESOLVE | Hazardous | FAILURE TO MAINTAIN(HAZARDOUS) NOTED: BATHROOM WALL AND CEILING IN APT 2D PARTIALLY COLLAPSED IN DANGER OF FUTHER COL... | $800 | $0 | Apr 7, 2003 |
| Jan 15, 2002 | 38111196J | RESOLVE | Non-Hazardous | 57O02-11Q03-75B05-31Q06-35I11-74B11-35P17. 31-Q 3 FLOOR PUT WIRING IN GREENFIELD TO INTERLOCK 35-I WHEEL HOUSE ROOM R... | $0 | $0 | Mar 4, 2002 |
| Jul 11, 2001 | 38117112K | RESOLVE | Non-Hazardous | 75U05, 57O02, 35P07 | $180 | $0 | Oct 15, 2001 |
| Aug 27, 2000 | 34231398Z | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL.DEFECT IS:1.AIR CONDITIONING UNITS AT FRONT FASCADE VARIOUS LOCATIONS THRU... | $0 | $0 | Oct 16, 2000 |
| Jan 20, 1999 | 38083011Z | RESOLVE | Non-Hazardous | 75#5,35P7,31Q7,57O2. 75-5 YR TEST PAST DUE. 31-THRU OUT. | $180 | $0 | Mar 8, 1999 |
| Apr 9, 1996 | 38056258R | RESOLVE | Non-Hazardous | 46K,47K,46H,47H. | $1,000 | $0 | Jul 22, 1996 |
| Apr 3, 1996 | 34135550Y | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECT IS : SLATE ROOFING TILES HAVE DISENLARGED FROM FRONT OF BUILDING AN... | $800 | $0 | Jul 29, 1996 |
| Jun 25, 1994 | 38042823N | RESOLVE | Non-Hazardous | 11B,22D,35P,55X,57O,74M (35) UNABLE TO GAIN ACESS TO COMPLETE INSPECTION (74) TOE GUARD. | $100 | $0 | Sep 26, 1994 |
| Jan 8, 1991 | 38003829M | RESOLVE | Non-Hazardous | 9H,11Q,14B,21X,26Q,28H,33O,35O,37G,57O,73B | $0 | $0 | Apr 15, 1991 |