ECB violations
2200-2224 Avenue V, Brooklyn • Block 07381 • Lot 0201
56 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 13, 2026 | 35722489R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT 2ND FL STAIR D,E HALLWAY SMOKE DOOR NEAR RM 256,GYM 3R... | $1,250 | $0 | Apr 20, 2026 |
| Mar 13, 2026 | 35722488P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT ROOF LEVEL BULKHEAD STAIR C/D BASEMENT GAS METER RM WI... | $1,250 | $0 | Apr 20, 2026 |
| Mar 13, 2026 | 35722487N | RESOLVE | CLASS - 2 | REISSUE ECB#35692115H FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AN... | $1,562 | $0 | Apr 20, 2026 |
| Mar 20, 2025 | 35692115H | RESOLVE | CLASS - 2 | REISSUE #35672610R; FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AN... | $3,125 | $0 | May 1, 2025 |
| Jun 27, 2024 | 35677329H | RESOLVE | CLASS - 2 | REISSUED #35672610R. FAIL TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATING EXIT DISCHARGE OF PUBLIC CORRID... | $1,562 | $0 | Aug 16, 2024 |
| May 16, 2023 | 39086345Z | ACTIVE | CLASS - 2 | MISSING BOLTS & DOGS ON BOILER DOORS,NEED VALVE ON OIL SUCTION LINE B/4 ANTI SYPHON VALVE | $625 | $0 | May 29, 2023 |
| May 16, 2023 | 39086346K | RESOLVE | CLASS - 2 | MISSING BOLTS & DOGS ON BOILER DOORS ,LEAK ON LEFT SIDE OF BOILER BY HAND HOLD GASKET | $625 | $0 | May 29, 2023 |
| Mar 15, 2023 | 35672610R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER B... | $625 | $0 | Jun 7, 2023 |
| May 12, 2022 | 35655173N | RESOLVE | CLASS - 2 | RE-ISSUE #35560964H(5/4/2021)EXIT DOOR NOT SELF-CLOSING:3 EXTERIOR EXIT DOORS.NOT SELF-CLOSING WHEN TESTED AT 1ST FL ... | $1,562 | $0 | Oct 26, 2022 |
| May 12, 2022 | 35655172L | RESOLVE | CLASS - 2 | RESERVE #35560967N(5/4/2021)FAILURE TO MAINTAIN BLDG IN CODE COMPLIANTMANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES &... | $1,562 | $0 | Oct 26, 2022 |
| May 4, 2021 | 35560967N | RESOLVE | CLASS - 2 | REISSUE35495130N DOI5.6.20 FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES&PU... | $1,562 | $0 | Sep 22, 2021 |
| May 4, 2021 | 35560964H | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELFCLOSING PROPERLY@1FL@EXITF OUTSIDE 1EXIT DOOR NOT SELFCLOSING PROPERLY@TIME OF INSP.REPAIR &/OR REP... | $625 | $0 | Sep 22, 2021 |
| May 6, 2020 | 35495130N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC... | $625 | $0 | Oct 14, 2020 |
| May 24, 2019 | 354149501 | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.STAIRCASE 3 AND 4 ROOF LEVEL BULKHEAD,WATER COMING IN PARTS OF ... | $0 | $0 | Oct 28, 2019 |
| May 24, 2019 | 35414950L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT-MANNER,STAIRCASE 3&4 ROOF LEVEL BUKLHEAD,WATER COMING IN,PARTS OF CEILING ... | $625 | $0 | Dec 29, 2021 |
| Apr 5, 2018 | 35325622H | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT LEVEL 2 ABOVE AUDITORIUM ENTRANCE, WATER PENETRATION... | $0 | $0 | Jul 16, 2018 |
| May 25, 2017 | 35272129H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. 125 GALLONS OF POINT ARE BEING STORED IN THE BOILER ROOM. REMEDY: ... | $0 | $0 | Aug 21, 2017 |
| May 25, 2017 | 35272127Y | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING,FIRE DOOR NOT SELF CLOSING NEAR RM#412,NOT SELF CLOSING DOORS: NEAR STAIRS OPPOSITE SIDE O... | $0 | $0 | Aug 21, 2017 |
| May 25, 2017 | 35272128X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLAINT MANNER. ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC... | $0 | $0 | Aug 21, 2017 |
| Jun 21, 2013 | 35023319L | RESOLVE | CLASS - 2 | DEFECTIVE FLOORS AT ROOM 504, MISSING / HOLE IN FLOORING / SUB FLOORING IN CORNER OF ROOM. REMEDY: REPAIR FLOOR | $0 | $0 | Aug 19, 2013 |
| Jun 21, 2013 | 35023318J | RESOLVE | CLASS - 2 | DEFECTIVE DOORS AT 3 FL CORRIDOR DOOR. DOORS SWING TOO FAST AND HITTING EACH OTHER. REMEDY : REPAIR DOOR | $0 | $0 | Aug 19, 2013 |
| Jun 21, 2013 | 35023320Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXIT SIGN AT CAFETERIA NORTHSIDE, EVIDENT SIGN ONEWAS THERE ALSO AS PER APPLICATION DATE IN 1983 ... | $0 | $0 | Aug 19, 2013 |
| Apr 18, 2012 | 34953915M | RESOLVE | CLASS - 2 | DOORS NOT CLOSING AT 4TH STY STAIR H. REMEDY: REPAIR/REPLACE DOOR NOTED. | $0 | $0 | Jun 18, 2012 |
| Sep 20, 2011 | 34928006K | RESOLVE | CLASS - 2 | NO A/C WINDOW SUPPORT AT 2FL ALONG EAST 22 STREET A/C WINDOW UNIT INSTALLED W/O METAL SUPPORT BRACKET REM: PROVIDE A/... | $0 | $0 | Dec 5, 2011 |
| Sep 20, 2011 | 34928005Z | RESOLVE | CLASS - 2 | MISSING FIRE STOP AT CELLAR ELECTRIC ROOM NO FIRE STOP AT CEILING CONDUIT PENETRATIONS REM: PROVIDE FIRE STOP | $0 | $0 | Dec 5, 2011 |
| Sep 20, 2011 | 34928001L | RESOLVE | CLASS - 2 | RACKED DOORS THE FIRE PROOF DOORS ARE RACKED TO FRAME AT 5FL STAIRWAY F G ROOF STORAGE ROOM REM: REPAIR IF FEASIBLE O... | $2,500 | $0 | Dec 5, 2011 |
| Sep 20, 2011 | 34928002N | RESOLVE | CLASS - 2 | BROKEN DOOR CHECKS THE FIRE PROOF DOORS NOT SELF CLOSING AT 3FL STAIRWAY C SMOKE DOORS ADJACENT TO ROOM 256 REM: REPL... | $2,500 | $0 | Dec 5, 2011 |
| Sep 20, 2011 | 34928003P | RESOLVE | CLASS - 2 | PLEXI VISION PANELS AT 4TH FL VARIOUS ROOMS THROUGHOUT PLEXI THERMOPLASTIC VISION PANELS INSTALLED REM: PROVIDE CODE ... | $0 | $0 | Dec 5, 2011 |
| Sep 20, 2011 | 34928004R | RESOLVE | CLASS - 2 | SPALLING PLASTER SPALLING PLASTER AT EXIT 10 VESTIBULE WALL & CEILING AUDITORIUM STAGE REAR CEILING REPAIR PLASTER SU... | $0 | $0 | Dec 5, 2011 |
| Sep 20, 2011 | 34928000J | RESOLVE | CLASS - 2 | REISSUE #34854963N SPALLING PLASTER CONCRETE SPALLING PLASTER WALLS AND/OR CEILING AT 5FL ROOMS 501 507 511 AND ROOF ... | $0 | $0 | Dec 5, 2011 |
| Jun 3, 2010 | 34854964P | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN ADEQUATE FIRESTOPPING OBSERVED. SEVERAL OPEN PENETRATIONS AROUND CONDUITS PASSING THRU CEILING OF RO... | $0 | $0 | Aug 2, 2010 |
| Jun 3, 2010 | 34854963N | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN. SPALLING PLASTER ON WALLS & CEILING RMS. 501,507,511. AT ROOFTOP STOREROOM BY STAIR 6 EXPOSED REBAR... | $0 | $0 | Aug 2, 2010 |
| Jun 3, 2010 | 34854961J | RESOLVE | CLASS - 2 | REISSUE 34792244X FAIL TO MAINTAIN. MISSING/DEFECTIVE DOOR CLOSES AT EXIT 6 1ST FL 2 CLOSERS. EXIT C1 LUNCHROOM. REME... | $0 | $0 | Aug 2, 2010 |
| Jun 3, 2010 | 34854962L | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN. RACKED, BINDING FPSC DOORS AT STAIR 6 5TH FL EXIT DRRM 105. REMEDY: MAINTAIN BLDG | $0 | $0 | Aug 2, 2010 |
| Jun 23, 2009 | 34792243Y | RESOLVE | CLASS - 3 | STANDING WATER - 1- S.W. CORNER REAR YARD APPROX 20' X 40'. 2- BASEMENT FLOOD AT OLD COAL SHUTE. REMEDY: MAINTAIN/CON... | $0 | $0 | Sep 14, 2009 |
| Jun 23, 2009 | 34792448H | RESOLVE | CLASS - 2 | REISSUE 34698106R 1ST FL LUNCH RM OCCUPANCY OVER 300 PERSONS EXIT DOORS SWING AGAINST FLOW OF EGRESS | $0 | $0 | Nov 16, 2009 |
| Jun 23, 2009 | 34792244X | RESOLVE | CLASS - 2 | HARDWARE DEFECTIVE. 1- GATE TO ROOF 5/F CHAINED PADLOCKED. 2- ROOF - EXTERIOR 5/6 HDWR. NOT FUNCTIONAL. 3- STWY- 3/4 ... | $0 | $0 | Sep 14, 2009 |
| Jun 23, 2009 | 34792245H | RESOLVE | CLASS - 2 | DEFECTIVE DOORS AND FRAMES. 1- ALL EXTERIOR BULKHEAD ROOF DOORS, & FRAMES & SADDLES ROTTED. 2- EXIT #9 GROUND FLR - S... | $0 | $0 | Sep 14, 2009 |
| Feb 20, 2009 | 34753227M | RESOLVE | CLASS - 2 | SHED DOESN'T MEET BUILDING CODE SPECIFICATIONS NOTED: THERE ARE MISSING VERTICAL ENCLOSURES (PARAPETS) 24' ALONG E 22... | $10,000 | $0 | Jul 26, 2010 |
| Aug 20, 2008 | 34698106R | RESOLVE | CLASS - 1 | REISSUE: 34570097L. HAZARDOUS. 1ST FLOOR LUNCH ROOM OCCUPANCY OF OVER 300 PERSONS EXIT DOOR SWING AGAINST FLOW OF EGR... | $0 | $0 | Nov 17, 2008 |
| Aug 20, 2008 | 34698105P | RESOLVE | CLASS - 3 | DEFECTIVE DOORS, GYM DOOR ON 5TH FLOOR & CORRIDOR DOOR ON 3 FLOOR NEARROOM 354. DOORS DRAGGING ON FLOOR & NOT OPENING... | $0 | $0 | Nov 17, 2008 |
| May 17, 2007 | 34570098N | RESOLVE | Hazardous | REISSUE # 34504804X:NOTED: WOOD FL @ ROOMS 503 APPROX 3' X 8' IS DEFECTIVE,ROTTEN & TRIP HAZARD.REMEDY:REPAIR/ REPLAC... | $0 | $0 | Jul 16, 2007 |
| May 17, 2007 | 34570097L | RESOLVE | Hazardous | REISSUE # 34504806J.NOTED: 1ST FL LUNCH ROOM OCCUPANCY OF OVER 300,OLD WOOD DOORS OPEN INTO LUNCH ROOM FROM HALL.REME... | $0 | $0 | Jul 16, 2007 |
| Feb 17, 2006 | 34504805H | RESOLVE | Hazardous | REISSUE #344752882 WATER PENETRATION THROUGH EXTERIOR WALLS EFFECTING CLASS ROOMS #407, 452, 405, 403, 401, 501, 503,... | $0 | $0 | Apr 17, 2006 |
| Feb 17, 2006 | 34504806J | RESOLVE | Hazardous | EXIT DOORS SWING AGAINST THE FLOW OF EGRESS. LOCATION: 1ST FLOOR LUNCHROOM OCCUPANCY OF OVER 300 (SMALL KIDS AND TEAC... | $0 | $0 | Apr 17, 2006 |
| Feb 17, 2006 | 34504804X | RESOLVE | Hazardous | REISSUE #34475289K. WOOD FLOOR AT RM #503, SECTION APPX. 3'X 8' IS DEFECTIVE, ROTTEN AND A TRIP HAZARD. REMEDY: MAKE ... | $0 | $0 | Apr 17, 2006 |
| Apr 27, 2005 | 34475288Z | RESOLVE | Non-Hazardous | WATER PENETRATION THROUGH WALLS INTO CLASSROOM #407,452,405,403,401,501,503,505,552,507,AND STAIR 3/4 AT 5TH FL.REMED... | $0 | $0 | Aug 15, 2005 |
| Apr 27, 2005 | 34475290H | RESOLVE | Non-Hazardous | PLASTER SPALLING,CRACKED,MISSING IN CLASSROOMS #407,452,501,503,505,507.REMEDY:REPAIR PLASTER | $0 | $0 | Aug 15, 2005 |
| Apr 27, 2005 | 34475289K | RESOLVE | Non-Hazardous | WOOD FLOOR ROTTEN 3'X 8' SECTION IN RM# 503.REMEDY:REPAIR WOOD FLOOR IN RM #503 | $0 | $0 | Aug 15, 2005 |
| Mar 4, 2004 | 34427835M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN NOTE EXTERIOR STAIRWAY EXIT # 9 LEADING TO PLAYGROUND IS MISSING HANDRAIL REMEDY:INSTALL HANDRAIL | $0 | $0 | May 3, 2004 |