ECB violations
1287-1299 Ocean Avenue, Brooklyn • Block 07548 • Lot 0006
52 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jul 20, 2026 | 39196709H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVE AT EXPOSURE 2(LEFT) & 3(BACK) FL... | $1,250 | $1,250 | Sep 23, 2026 |
| Jul 20, 2026 | 39196708X | ACTIVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. AT TIME OF INSPECTION OBSERVED AT EXPOSURE 3(BACK) 2-6 FLOORS FIRE E... | $2,500 | $2,500 | Sep 23, 2026 |
| Jul 17, 2026 | 39196586R | RESOLVE | CLASS - 2 | ONLY ELEVATOR IN A MULTIPLE DWELLING OUT OF SERVICE. THIS CONDITION AFFECTS NUMEROUS TENANTS, INCLUDING THOSE WITH SP... | $0 | $0 | Sep 23, 2026 |
| Jun 15, 2026 | 39192645J | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED AT EXPOSURE#1 FIRE ESCAPE DROP ... | $2,500 | $2,500 | Aug 26, 2026 |
| Apr 17, 2026 | 39185057H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 2 ITEMS: 1) THE IN-CAR EMERGENCY COMMUNICATION SYSTEM IS... | $0 | $0 | Jun 24, 2026 |
| Mar 11, 2026 | 39180088H | ACTIVE | CLASS - 1 | ONLY ELEVATOR IN A MULTIPLE DWELLING OUT OF SEVRICE. THIS CONDITION AFFECTS NUMEROUS TENANTS, INCLUDING THOSE WITH SP... | $6,250 | $6,250 | May 20, 2026 |
| Feb 18, 2026 | 39177633R | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS.... | $6,250 | $6,250 | May 6, 2026 |
| Dec 16, 2025 | 39170551L | ACTIVE | CLASS - 1 | 1) REPAIR ALARM BELL 2) THE DRIVE SHEAVE IS EXTREMELY WORN AND MUST BE REPLACED ASAP. 3) THE BRASS GEAR OF THE MACHIN... | $6,250 | $6,250 | Feb 1, 2027 |
| May 9, 2023 | 39085849H | ACTIVE | CLASS - 1 | AT TIME OF INSPECTION OBSERVED. AT EXP#2 FIRE ESCAPE EXIT PASSAGEWAY TO STREET (OCEAN AVENUE) OBSTRUCTED BY VEHICLE N... | $1,250 | $1,250 | Jun 4, 2025 |
| Mar 30, 2021 | 35528947X | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#39028848P ISSUED ON 9/17/2020 AND TO F... | $0 | $0 | Mar 24, 2022 |
| Nov 25, 2020 | 39032544H | RESOLVE | CLASS - 2 | LABEL HOISTWAY DOORS WHERE NEEDED. INOPERATIVE PHONE. WORN OVERHEAD DOOR SIGN. GOV MISSING DATA PLATE. GOV MISSING SE... | $625 | $0 | Apr 14, 2021 |
| Nov 18, 2020 | 35494154N | RESOLVE | CLASS - 2 | UNAPPROVED UNSAFE UNSUITABLE ELCTRICAL EQUIPMENT DEVICES APPARATUS APPLIANCES MATERIALS OR WIRING N USE DEFECTIVE FIX... | $400 | $400 | Mar 31, 2021 |
| Nov 18, 2020 | 35494155P | RESOLVE | CLASS - 2 | FAILURE TO PROPERLY CONNECT CONDUCTORS TO TERMINALS LIGHTING FIXTURES THROUGHOUT BASEMENT NOT PROPERLY TERMINATED PRO... | $600 | $0 | Mar 31, 2021 |
| Nov 18, 2020 | 35494153L | RESOLVE | CLASS - 2 | FAIL TO RPVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS ENCLOSURES CABLE ARMOR HALLWAY LIGHTING RACEWAY ON ... | $600 | $0 | Mar 31, 2021 |
| Nov 18, 2020 | 39032190J | RESOLVE | CLASS - 1 | I OBSERVED IN CELLAR FOR GAS METER MARKED FOR SUPERS APARTMENT GAS PIPING TAPPED OFF OTHER GAS PIPING INSTALLED FOR I... | $2,500 | $2,500 | Aug 6, 2021 |
| Nov 18, 2020 | 35494149Z | RESOLVE | CLASS - 2 | FAILURE TO SECURE SUPPORT RACEWAYS CABLE ASSEMBLES BOXES CABINETS FITTINSG LIGHTING RACEWAY REAR OF BUILDING NOT PROP... | $400 | $0 | Mar 31, 2021 |
| Nov 18, 2020 | 35494151H | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT OBSERVED AT 9 15 AM BRANCH WIRING CIRCUIT INSTALLED IN APARTMENT 3A ALSO INSTALATION... | $800 | $0 | Mar 31, 2021 |
| Nov 18, 2020 | 35494152J | RESOLVE | CLASS - 2 | ORIVUDE FAILURE TO COVER FACE PLATE LAMPFOLDER LUMINAIRE CANOPY FOR ELECTRICAL OUTLET SPLICE BOX COVERS MISSING THROU... | $250 | $0 | Mar 31, 2021 |
| Nov 18, 2020 | 35494150X | RESOLVE | CLASS - 1 | UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT DEVICES APPARATUS MATERIALS OR WIRING IN USE (EXPORTED ELECTRICAL F... | $1,600 | $0 | Mar 31, 2021 |
| Nov 18, 2020 | 39032188K | RESOLVE | CLASS - 1 | I OBSERVED IN CELLAR FOR GAS METER MARKED FOR SUPERS APARTMENT GAS PIPING TAPPED OFF OTHER GAS PIPING INSTALLED FOR I... | $2,500 | $2,500 | Aug 6, 2021 |
| Nov 18, 2020 | 39032186R | RESOLVE | CLASS - 1 | I OBSERVED IN CELLAR FOR GAS METER MARKED FOR SUPERS APARTMENT GAS PIPING TAPPED OFF OTHER GAS PIPING INSTALLED FOR I... | $5,000 | $5,000 | Aug 6, 2021 |
| Nov 18, 2020 | 39032189M | RESOLVE | CLASS - 1 | I OBSERVED IN CELLAR FOR GAS METER MARKED FOR SUPERS APARTMENT GAS PIPING TAPPED OFF OTHER GAS PIPING INSTALLED FOR I... | $1,250 | $1,250 | Aug 6, 2021 |
| Oct 19, 2020 | 35537472X | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. NOTED:AT TIME OF INSPECTION,OBSERVATION WAS MADE INAPT 5C AT ABOVE PREMISES 2-3 WORKERS PERFORMING... | $2,500 | $0 | Mar 3, 2021 |
| Oct 19, 2020 | 35537471Y | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. NOTED:AT TIME OF INSPECTION,OBSERVATION WAS MADE IN APT 5C AT ABOVE PREMISES NEW ELECTR... | $800 | $0 | Mar 3, 2021 |
| Oct 3, 2020 | 35537170K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED AT 1299 OCEAN AVE BKLYN 1)A/C W... | $1,250 | $0 | Feb 10, 2021 |
| Oct 1, 2020 | 39029690Z | RESOLVE | CLASS - 1 | REPAIR EMERGENCY IN -CAR PHONE., CEASE USE ITEM: REPLACE WORN BRAKE PADS.... TO RETURN DEVICE TO SERVICE CONTACT NYCD... | $1,250 | $0 | Feb 3, 2021 |
| Sep 17, 2020 | 39028848P | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT. OBSERVED ALTERATION IN APT 5H IN PROGRESS BY 3 WORKERS ON SITE. RENOVATIONS INCLUDED NEW PARTI... | $2,500 | $0 | Jan 20, 2021 |
| Sep 6, 2016 | 38246426Y | RESOLVE | CLASS - 2 | 05B07,24L10,40P16,56O02,64B07,67X10,70O02,99BB05. 05B07-PROVIDE A ZONELOCK DEVICE. 24L10-6TH FLOOR INDICATOR DEFECTIV... | $530 | $0 | Apr 4, 2017 |
| Jun 16, 2015 | 38235680X | RESOLVE | CLASS - 2 | 97L10 RETURN DEVICE TO SERVICE. | $0 | $0 | Aug 3, 2015 |
| Aug 22, 2014 | 38230972P | RESOLVE | CLASS - 2 | 37M07 40M07. 37M,40M-PROVIDE KEYS TO THE M.R. & OVER-HEAD MACHINE SPACE. | $0 | $0 | Oct 6, 2014 |
| Apr 2, 2013 | 32073339P | RESOLVE | CLASS - 3 | B354,15,32A,34B,50A,B. 50A- COIL PLATE CORRODED AND LEAKING. 50B- BOILER ROOM NOT A STORAGE ROOM. | $100 | $0 | Jun 24, 2013 |
| Jun 27, 2011 | 38217453R | RESOLVE | CLASS - 2 | 41S11. FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER TO FILE C/C W/THE DOB. RESPONDENT FAILED TO COMPLY W/THE COMMISSI... | $800 | $0 | Apr 25, 2012 |
| Jun 27, 2011 | 38217452P | RESOLVE | CLASS - 1 | 41S11. RESPONDENT FILED A C/C ON MAR 16, 2011. FOR NOV 38213542K. UPONINSPECTION FOUND THAT THE CONDITION WHICH RESPO... | $0 | -$4,800 | Nov 28, 2011 |
| Jun 27, 2011 | 38216508K | RESOLVE | CLASS - 1 | CU10L11,05K11,RC41S11,35R09.(10L)CEASE USE 7 DEFECTIVE GIB CAR DOOR OUT OF SADDLE.(41S)WOOD DOOR BUCK FOR MR.DOOR MUS... | $1,000 | $0 | Apr 25, 2012 |
| Apr 14, 2011 | 38215907N | RESOLVE | CLASS - 1 | 97X10,16E10,59L10.(97X)ONLY ELEVATOR IN A MULTIPLE DWELLING OUT OF SERVICE.CREATING DANGER TO HUMAN LIFE.(16E)6TH FLR... | $1,000 | $0 | Aug 1, 2011 |
| Feb 19, 2011 | 34895209M | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER IN THAT AT FRONT & SIDE OF BLDG METAL CHAIN LINK FENCE IS IN DISREP... | $0 | $0 | Jun 13, 2011 |
| Nov 8, 2010 | 38213542K | RESOLVE | CLASS - 1 | 97X10 97X17 41S11 40B07 34Q07 34T07 97X-SINGLE ELEVATOR IN MULTIPLE DWELLING OUT OF SERVICE CREATING DANGER TO HUMAN ... | $1,000 | $0 | Jan 3, 2011 |
| Sep 15, 2010 | 38212835J | RESOLVE | CLASS - 2 | 67L10,34Q07.(67L)CAR PHONE.(34Q)AS PER K-3 SEC 212 GUARD HOIST WAY WINDOWS PROVIDE OUTSIDE SIGNAGE SHAFTWAY & GUARDS ... | $250 | $0 | Apr 4, 2011 |
| Jan 5, 2010 | 38207819N | RESOLVE | CLASS - 1 | 20M7.08A01.32H10.70O2.77Q3.77M7.97M7.23D6.34## CEASE USE ITEM 20 2ND FFL VISION PANEL & GUARD MISSING PROVIDE CALL 21... | $1,000 | $0 | Mar 4, 2010 |
| Jun 19, 2009 | 38203772R | RESOLVE | CLASS - 2 | 05B10.56Y10.34R7.05B GAP TO SADDLE 1B 11L STICKING BUTTONS 20I 2FL 26R MAKE OPERATIONAL 35Q CAR TOP HOISTWAY M/R 35R ... | $500 | $0 | Aug 13, 2009 |
| Apr 2, 2007 | 38163822M | RESOLVE | Non-Hazardous | 8A1/14M7/59Q3/15M7/11D6/33O2/3I10/66O2/71Q3/71O2/55O2/5I10/84I10/83M7/SECOND OFFENSE ITEMS:8-ADJUST LEVELING.14-CAR M... | $1,000 | $0 | Feb 1, 2008 |
| May 23, 2006 | 38157464K | RESOLVE | Non-Hazardous | CEASE USE. HAZARDOUS. 21X10,85U05,15M07,14M07,59M07,08V01. 21-X 3 FL HOIST DOOR INTERLOCK INOPERATIVE. | $500 | $0 | Jul 10, 2006 |
| Mar 12, 2001 | 38115179X | RESOLVE | Non-Hazardous | 18Q03,11Q3,17M12,35P7,74P17,25P7,31Q3,3O2,57O2.74-PROVIDE ACCESS TO WHEEL HOUSE. | $2,500 | $0 | Apr 30, 2001 |
| Jul 12, 2000 | 34254209M | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT. CONCRETE PARKING PAD AND CURB CUT HAS BEEN CREATED IN FRONT LEFT SIDE OF PREMISES. NO PARKING ... | $0 | $0 | Aug 28, 2000 |
| Jun 11, 1999 | 38086406R | RESOLVE | Non-Hazardous | 17I7,17M7,57O2,57P17. -17 VISION GLASS MISSING. | $2,500 | $0 | Aug 2, 1999 |
| Mar 7, 1998 | 38071328Z | RESOLVE | Non-Hazardous | 08J,13M,18D,37Q,53M,57O,75U 18-DOOR LOCK COVER BASEMENT LEVEL MISSING 37-NUMEROUS WIRES NEEDING COVERING. | $0 | $0 | Apr 27, 1998 |
| Sep 9, 1995 | 38051203R | RESOLVE | Non-Hazardous | 46K,47L,08V,28H,33M,17L,35P,11Q. 33M SKYLIGHT GLASS. 17L 6 FLOOR GLASS/ | $0 | -$100 | Nov 27, 1995 |
| Jun 29, 1993 | 38034498Z | RESOLVE | Non-Hazardous | 73#. RESTORE ELEVATOR SERVICE FOR COMPLETE INSPECTION. | $0 | $0 | Sep 13, 1993 |
| Sep 2, 1992 | 38029121M | RESOLVE | Non-Hazardous | 05#,09H,28H,22D,57O,73#, 05.PROVIDE FULL LENGTH CAR DOOR SADDLE. 73. PERFORM 5 YEAR TEST AND FILE FORM ELEV. 3. | $1,000 | $0 | Oct 19, 1992 |
| Jul 3, 1991 | 38012833J | RESOLVE | Non-Hazardous | 05H,08V,14M,17L,21M,22D,35P,33P,55X,57O,58O,59O,(05) CAR DOOR SILL | $1,000 | $0 | Jan 27, 1992 |