Skip to content

ECB violations

Harden Street, Brooklyn • Block 07867 • Lot 0005

5 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jul 20, 2009 32066625K RESOLVE CLASS - 2 50A.50B 50A OIL VENT LINE 1" MUST BE MIN 1 1/4" AS PER CODE 50B CEILING IN FRONT OF BOILER NOT FIRE PROOF $250 $0 Dec 7, 2009
Nov 6, 2006 32050210M RESOLVE Non-Hazardous 50A,B,C,D. FULTON V.T BOILERS, 3HP, NB 35105, OIL 1978. 50A-DISLOCATEDFURNACE CEMENT AT FLUE PIPE/ CHIMNEY BASE. RE-S... $0 $0 Dec 18, 2006
Jan 15, 2005 32044998X RESOLVE Non-Hazardous 1 1)YOU ARE IN VIOLATION OF OPERATING A SEALED BOILER W/OUT A REINSPCTION BY THE BLDG DEPT THE BOILER IS A(HIGH PRESS... $0 $0 Feb 28, 2005
Jan 8, 2005 32044981J ACTIVE Non-Hazardous 51/48B/11A/50A/50B/50C 1978 FULTON NBD35105 51)CASING CRACKED EXPOSINGTHE PRODUCTS OF COMBUSTING TO THE BLDG 50A)COVE... $800 $0 Feb 28, 2005
Apr 25, 2000 32018850K ACTIVE Non-Hazardous 49- -HAND HOLES WELDED RECEIPT BY CERTIFIED WELDER HOLDING "R' STAMP SUBMIT FOR ALL THREE OF THEM 2-MANUAL RESET LOW ... $350 $0 Jun 19, 2000