ECB violations
Stuart Street, Brooklyn • Block 08496 • Lot 0100
63 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 1, 2026 | 35732962M | ACTIVE | CLASS - 2 | RE-ISSUE 35721270H. AT THE TIME OF INSPECTION, THE DOORS WERE NOT SELF-CLOSING:-302, 305, 303A, 309, CORRIDOR DOOR NE... | $3,125 | $0 | May 27, 2026 |
| May 1, 2026 | 35732967L | ACTIVE | CLASS - 2 | RE-ISSUE 35721269K. AT THE TIME OF INSPECTION, THE OIL TANK ROOM HAD ACRACK IN CONCRETE WALL THAT HAD WATER TRICKLING... | $3,125 | $0 | May 27, 2026 |
| May 1, 2026 | 35732966J | ACTIVE | CLASS - 2 | RE-ISSUE 35721272L. AT THE TIME OF INSPECTION, BULKHEAD "C" WALL HAS SPALLED, HOWEVER THE REPAIRED AREAS HAD BUBBLING... | $3,125 | $0 | May 27, 2026 |
| May 1, 2026 | 35732965H | ACTIVE | CLASS - 2 | RE-ISSUE 35721268Z. AT THE TIME OF INSPECTION, THE GAS AND ELECTRICAL METER ROOMS HAD CEILING/WALL PENETRATIONS, GAS ... | $3,125 | $0 | May 27, 2026 |
| May 1, 2026 | 35732964X | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS P... | $1,250 | $0 | May 27, 2026 |
| May 1, 2026 | 35732963Y | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371... | $1,250 | $0 | May 27, 2026 |
| Jul 22, 2025 | 35721272L | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.CRACK IN BULKHEAD AND DOWN THE STAIRS FROM WATER LEAKS COMING F... | $1,250 | $0 | Sep 3, 2025 |
| Jul 22, 2025 | 35721269K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OIL TANK ROOM CRACK IN WALL LEAKING AND OIL TANK SUPPORT ONE SI... | $1,250 | $0 | Sep 3, 2025 |
| Jul 22, 2025 | 35721268Z | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NO FIRESTOPPING PER BC 712.3;27-345.LARGE OPEN HOLES IN ELECTRI... | $1,250 | $0 | Sep 3, 2025 |
| Jul 22, 2025 | 35721266P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. CRACKS IN RETAINING WALL IN REAR BY PARK AND ON SIDE OF SCHOOL... | $1,250 | $0 | Sep 8, 2025 |
| Jul 22, 2025 | 35721271J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ROOF LEVEL MUCH OF ROOFING MATERIAL LIFTING UP AND CRACKING AND... | $1,250 | $0 | Sep 3, 2025 |
| Jul 22, 2025 | 35721270H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.CLASSROOM DOOR NOT SELF CLOSING MISSING HARDWARE IN ROOM 202,20... | $1,250 | $0 | Sep 3, 2025 |
| Jul 1, 2024 | 35682872X | RESOLVE | CLASS - 2 | REISSUE #35672611Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXIT, EXIT DISCHARGES AND... | $1,562 | $0 | Aug 16, 2024 |
| Mar 20, 2023 | 35672611Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION EXIT,EXIT DISCHARGES & PUBLIC CORRIDOR PER BC 1006... | $625 | $0 | Jun 21, 2023 |
| May 27, 2021 | 35561595X | RESOLVE | CLASS - 2 | REISSUE #35495850L DATE OF ISSUE:06.02.2020 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EX... | $1,562 | $0 | Oct 27, 2021 |
| May 27, 2021 | 35561596H | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING PROPERLY AT BASEMENT LEVEL LUNCH ROOM ONE EXIT DOOR(EXIT WAY TO YEARD)EXIT DOOR NOT SELF C... | $625 | $0 | Oct 27, 2021 |
| May 27, 2021 | 35561597J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER BC 712.3;27-345.IN BASEMENT LEVEL ELECTRIC... | $1,250 | $0 | Oct 27, 2021 |
| May 8, 2020 | 35495136Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1... | $625 | $0 | Oct 14, 2020 |
| May 15, 2019 | 35402216Z | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN REISSUE #35328668R FAILURE TO MAINTAIN BUILDING INCODE-COMPLIANT MANNER. MULTIPLE AREAS OF ROOF F... | $0 | $0 | Sep 23, 2019 |
| Apr 16, 2018 | 35328668R | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT ROOF LEVEL,NORTHSIDE,MULTIPLE AREAS OF ROOF MEMBRANE B... | $0 | $0 | Jul 30, 2018 |
| May 16, 2017 | 35267503M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: USE OF PROHIBITED DOOR &/OR HANDWARE PER BC 1008.1.8, 27-371(J). O... | $0 | $0 | Aug 7, 2017 |
| May 16, 2017 | 35267504Y | RESOLVE | CLASS - 2 | SEC: 28-301.1. UNLAWFUL PLACEMENT OF FURNISHINGS, DECORATIONS OR OTHEROBJECTS @ EXITS THAT OBSTRUCT ACCESS TO EGRESS ... | $0 | $0 | Aug 7, 2017 |
| May 16, 2017 | 35267505X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES & PUBLIC CORRIDORS PER BC ... | $0 | $0 | Aug 7, 2017 |
| May 16, 2017 | 35267506H | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. OBSERVED @ 3RD FLR EXIT STAIRCASE 'D' & EXIT H, 1ST FLR EXITS G & F, BASEMENT EXIT A & B ... | $0 | $0 | Aug 7, 2017 |
| Jul 23, 2014 | 35101221Y | RESOLVE | CLASS - 2 | RE-ISSUE ECB# 35023312Z THE FOLLOWING DOORS ARE RACKED AND NOT CLOSINGPROPERLY : 3RD FL STAIR D, CROADD CORRIDOR DOOR... | $0 | $0 | Sep 29, 2014 |
| Jun 19, 2013 | 35023312Z | RESOLVE | CLASS - 2 | REISSUE 34953916Y DEFECTIVE DOORS AT 3RD FLR STAIR D,CORRIDOR DOOR NEAR 315, 2 FLOOR STAIR A,B,C, 1FLR STAIR G,F. RMD... | $2,500 | $0 | Aug 19, 2013 |
| Apr 19, 2012 | 34953917X | RESOLVE | CLASS - 2 | WATER DAMAGED/DISPLACED CONCEALED SPLINE CEILING. AT: 3RD STY ROOM 304APPROX 26 SF OF CEILING TILE DELAMINATED/DISLOD... | $0 | $0 | Jun 18, 2012 |
| Apr 19, 2012 | 34953916Y | RESOLVE | CLASS - 2 | DOORS NOT CLOSING. AT: VARIOUS LOCATIONS THROUGHOUT ALL STAIRS AND LEVELS. AT: BASEMENT CROSS CORRIDOR DOOR NEAR RM B... | $0 | $0 | Jun 18, 2012 |
| Oct 4, 2011 | 34896356R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.FAILURE TO COMPLY W/LAW FOR DRAINAGE SYSTEM PER PC702.1.OBSERVE IN ... | $0 | $0 | Dec 5, 2011 |
| Sep 16, 2011 | 34927575X | RESOLVE | CLASS - 2 | RACKED DOORS THE FIRE PROOF DOORS ARE RACKED TO FRAME AND/OR DRAG ON FLOOR AT 1FL STAIRWAY A & B GYM 2FL STAIRWAY C S... | $0 | $0 | Dec 5, 2011 |
| Sep 16, 2011 | 34927574Y | RESOLVE | CLASS - 2 | SEC. 3301.9.5;28-105.11 FAILURE TO POST A READILY VISIBLE SIGN W/PERMIT # ON SIDEWALK SHED. AT P.S.278 ID #K278 SIDEW... | $400 | $0 | Nov 21, 2011 |
| Sep 16, 2011 | 34927577J | RESOLVE | CLASS - 2 | PROHIBITED HARDWARE AT AUDITORIUM LOBBY DOORS INSTALLED DOOR STOP LATCHES PREVENT PROPER OPERATION OF SELF CLOSING DO... | $0 | $0 | Dec 5, 2011 |
| Sep 16, 2011 | 34927576H | RESOLVE | CLASS - 2 | BROKEN DOOR CHECKS THE FIRE PROOF DOORS HAVE BROKEN DOOR CHECKS AND ARE NOT SELF CLOSING AT 3FL STAIRWAY C 2FL STAIRW... | $0 | $0 | Dec 5, 2011 |
| Sep 16, 2011 | 34927578L | RESOLVE | CLASS - 2 | MISSING FIRE STOP FIRE STOP MISSING AT CONDUIT AND PIPE PENETRATION AT CELLAR GAS METER ROOM CELLAR ELECTRIC ROOM CAF... | $0 | $0 | Dec 5, 2011 |
| May 12, 2010 | 34847993Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN ADEQUATE FIRE STOPPING OBSERVED: AT GAS & ELECTRICROOMS,OPEN(GRILLS) ON ENTRANCE DOORS TO ROOMS,U... | $0 | $0 | Sep 13, 2010 |
| May 12, 2010 | 34847990N | RESOLVE | CLASS - 2 | SEC. 28-301.1 REISSUE 34792384H FAILURE TO MAINTAIN OBSERVED AT SCHOOLROOF,STANDING/POUNDINGS WATER,BUBBLES UNDER ROO... | $0 | $0 | Sep 13, 2010 |
| May 12, 2010 | 34847994K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN OBSERVED: OPEN HOLES IN CORRIDORS,STAIRWELLS,AROUND ELECTRICAL CONDUIT INSTALLED FOR CAMERA SYSTE... | $0 | $0 | Sep 13, 2010 |
| May 12, 2010 | 34847992R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN OBSERVED: IN GAS METER ROOM - STANDARD TOGGLE LIGHT SWICH LOCATED IN UNVENTED ROOM. REMEDY: MAINT... | $0 | $0 | Sep 13, 2010 |
| May 12, 2010 | 34847995M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN OBSERVED: AT ENTRANCE TO ELECTRIC ROOM,TRIP HAZARDCREATED BY 4" CHANGE IN FLOOR ELEVATION. POTENT... | $0 | $0 | Sep 13, 2010 |
| May 12, 2010 | 34847991P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN OBSERVED: NO FRESH AIR VENTILATION GAS METER ROOM.REMEDY: PROVIDE VENTILATION. | $0 | $0 | Sep 13, 2010 |
| Jun 24, 2009 | 34792386L | RESOLVE | CLASS - 2 | DOOR OVERHANG - DEFECTIVE - EXIT #3 - GROUND FLR - CONCRETE OVERHANG 8' HORIZONTAL CRACKS AT EXTERIOR. REMEDY: REPAIR... | $0 | $0 | Sep 14, 2009 |
| Jun 24, 2009 | 34792384H | RESOLVE | CLASS - 2 | DEFECTIVE ROOFING - POOLING AND BUBBLES THROUGHOUT 3RD FLR ROOFS. REMEDY: REPAIR/REPLACE ACCORDING TO CODE. | $0 | $0 | Sep 14, 2009 |
| Jun 24, 2009 | 34792383X | RESOLVE | CLASS - 2 | REISSUE - 34698109M. PLASTER DAMAGE IN FOLLOWING AREAS - ROOM 315, 329,330,333 SPALLING AT BULKHEADS: D/E, C, H 2ND F... | $0 | $0 | Sep 14, 2009 |
| Jun 24, 2009 | 34792385J | RESOLVE | CLASS - 2 | FIRE DOOR INTERIOR - DEFECTIVE AND/OR MISSING - 1- 2ND FLR - FIRE DOORS MISSING AT T. REMEDY: INSTALL FIRE DOORS AS P... | $0 | $0 | Sep 14, 2009 |
| Jun 24, 2009 | 34792388P | RESOLVE | CLASS - 1 | BOILER ROOM/FUEL OIL TANK ROOM DEFECTIVE CONCRETE BLOCK AND/OR MISSINGBLOCK. 1- BOILER ROOM - OVER ENTRANCE - DEFECTI... | $0 | $0 | Sep 14, 2009 |
| Jun 24, 2009 | 34792387N | RESOLVE | CLASS - 2 | SEC. 1017.1;27-369. CORRIDOR WIDTH DECREASED AUDITORIUM - RIGHT EXIT DOOR PARTIALLY BLOCKED W/SCHOOL DRAMA PROPS AND ... | $0 | $0 | Sep 14, 2009 |
| Aug 20, 2008 | 34698109M | RESOLVE | CLASS - 3 | PLASTER DAMAGE IN CLASSROOM 315 ON REAR WALL, ALSO STAIRWAY D BULKHEADWALL. REMEDY: REPAIR PLASTER. | $0 | $0 | Nov 17, 2008 |
| Feb 25, 2008 | 32055820M | RESOLVE | Non-Hazardous | 50A,B. FITZGIBBON FTFB BOILER, LPSION, OK. 50A ORIGINAL SAFETY VALVES MOUNTED ON THE REFERENCED BOILER ARE OBSOLETE N... | $0 | $0 | Apr 21, 2008 |
| Feb 25, 2008 | 32055822X | RESOLVE | Non-Hazardous | 50A,50B. FITZGIBBON FTFB BOILER, LPSION, OIL. 50A. ORIGINAL SAFETY VALVES MOUNTED ON THE REFERENCED BOILER ARE OBSOLE... | $0 | $0 | Apr 21, 2008 |
| Feb 25, 2008 | 32055821Y | RESOLVE | Non-Hazardous | 50A,B. FITZGIBBON FTFB BOILER, LP SION, OIL. 50A. ORIGINAL SAFETY VALVES MOUNTED ON THE REFERENCED BOILER ARE OBSOLET... | $0 | $0 | Apr 21, 2008 |