ECB violations
1023-1039 Brighton Beach Avenue, Brooklyn • Block 08709 • Lot 0060
93 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 15, 2014 | 35039223N | RESOLVE | CLASS - 1 | EC230.72,SERVICE SWITCHES ARE NOT GROUPED.REM:COMPLY W/ EC CODE/OBTAINPERMIT. | $0 | $0 | Jul 17, 2015 |
| Sep 30, 2014 | 35097799L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED: AT EXPOSURE#2OBSERVED HE METAL FRAME FIRE ESCAPE TO BE IN PO... | $200 | $0 | Feb 11, 2015 |
| Sep 30, 2014 | 35074549R | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE BLDG DEPT RECORDS. NOTED: BLDG DEPT RECORDS. NOTED:BLDG DEPT RECORDS (JOB#3... | $800 | $0 | Feb 9, 2015 |
| Sep 24, 2014 | 35039212H | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS.GROUNDING IS NOT IN EACH SCK SW.REM:PROVIDE GROUNDING/OBTAIN PERMIT. | $4,800 | $0 | May 2, 2016 |
| Sep 24, 2014 | 35039211X | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT.1-600 A SCK SW.FEDDERS FROM BSMT TO SECOND FL.APP 3B302700 DOES NOT COVER ADDITIONAL WOR... | $1,600 | $0 | May 3, 2016 |
| Sep 24, 2014 | 35039213J | RESOLVE | CLASS - 1 | FAILURE TO PROPERTY BOND ELECTRICAL SYSTEM.SERVICE ENT & NEUTRAL IS NOT BONDED.REM:PROVIDE PROPER BONDING/OBTAIN PERMIT. | $3,000 | $0 | May 2, 2016 |
| Sep 24, 2014 | 35039214L | RESOLVE | CLASS - 1 | EC TAB 250.66. BONDING IS NOT OF PROPER SIZE FOR 2-4 #500 MCM TO TWO 600 A SER SW. TAB 250.66. #2 BONDING USED FOR 2-... | $1,600 | $0 | Apr 7, 2015 |
| Sep 24, 2014 | 35039215N | RESOLVE | CLASS - 1 | EC TAB 250.122. EQUIPMENT GROUND IS NOT OF MIN SIZE AS PER TAB 250.122. #2 EQUIPMENT GROUND USED FOR 600 A USE. SEE A... | $1,600 | $0 | Apr 6, 2015 |
| Sep 15, 2014 | 35074533M | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED: AT TIME OF INSPECTION OBSERVED THE EMERGENCY EXITS FROM THE 1... | $1,200 | $0 | Nov 5, 2014 |
| Sep 15, 2014 | 35074532K | ACTIVE | CLASS - 2 | ALTERED/CHANGED BLDG OCCUPIED W/O A VALID C OF O. NOTED: OBSERVED AT TIME OF INSPECTION THE BLDG TO BE OCCUPIED ON 1S... | $1,250 | $0 | May 27, 2015 |
| Sep 15, 2014 | 35074534Y | RESOLVE | CLASS - 2 | OWNER FAILURE TO COMPLY W/THE COMM'S ORDER TO FILE A C OF C W/THE DOB'S FOR ECB VIOLATIONS #35090753Y;35085108P;35066... | $800 | $0 | Mar 23, 2015 |
| Aug 26, 2014 | 35097630X | ACTIVE | CLASS - 2 | ALTERED/CHANGE BLDG OCCUPIED W/O A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1 - 28-118.3.2. NOTE: PERMIT #30041... | $2,500 | $0 | Oct 20, 2014 |
| Jun 4, 2014 | 35090389R | RESOLVE | CLASS - 2 | FAIL TO PROVIDE APPROVED/ACCEPTED PLANS AT JOB SITE AT TIME OF INSP.WORK IN PROGRESS THROUGHOUT NO APPROVED PLANS FOR... | $0 | $0 | Jul 21, 2014 |
| May 15, 2014 | 35066490L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER:LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED.@ THE SECON... | $500 | $0 | Dec 15, 2014 |
| Mar 1, 2014 | 35090753Y | RESOLVE | CLASS - 2 | ALTERED/CHANGED BLDG ARRANGER FOR OCCUPANCY W/O A VALID C OF O AS PER 28-118.3.1 & 28-118.3.2 NOTE: ALT 3300418536-01... | $500 | $0 | Apr 21, 2014 |
| Feb 8, 2014 | 35038689K | RESOLVE | CLASS - 2 | UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS DEVICES APPLIANCES OR WIRING IN USE. DEFECTIVE ELECTRICAL... | $4,000 | $0 | Apr 7, 2014 |
| Feb 6, 2014 | 35085107N | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. CORNER STORE HAS APPROX 70FT LONG AWNING & ENCLOSURE INSTALLED W/O PERMIT TO ACCOMIDATE SALE OF PR... | $0 | $0 | Mar 24, 2014 |
| Feb 6, 2014 | 35085108P | RESOLVE | CLASS - 2 | SEC. 32-411 COMMERCIAL USE BEYOND COMPLETELY ENCLOSED BLDG. INTERNATIONAL QUALITY FUIT STORE SALE OF PRODUCE BEYOND E... | $400 | $0 | Mar 24, 2014 |
| Feb 3, 2014 | 35009079K | RESOLVE | CLASS - 2 | FAILURE TO PAINT DEDICATED STANDPIPE/VALVES THROUGHOUT ALL FLRS STANDPIPE IS NOT PROPERLY PAINTED RED.RELATED TO LOCA... | $800 | $0 | Mar 24, 2014 |
| Feb 3, 2014 | 35009078Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: LACK OF A SYSTEM OFAUTOMATIC SPRINKLERS WHERE REQUIRED. ON THE 2ND... | $1,000 | $0 | May 5, 2014 |
| Jan 31, 2014 | 35038644R | RESOLVE | CLASS - 2 | FAILURE TO PROPERLY SECURE SUPPORT ELECTRICAL METALLIC TUBING (EMT). 1/2" PIPE W/#12 WIRES HANGING IN FRONT OF BLDG. ... | $2,500 | $0 | Apr 7, 2014 |
| Nov 6, 2013 | 35021941M | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT-ELECTRICAL WIRING OF TWO LIGHT BOXES OUTSIDE IN FRONT OF BLDG.NOTE:@3PM OBS ARMOURED... | $800 | $0 | Dec 23, 2013 |
| Apr 8, 2013 | 35012736Z | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. INSTALLED ACCESSORY BOX SIGN APPROX SIZE 3 X 15 & READING "LAW OFFICE 718 615 2933" FACING BRIGHTO... | $400 | $0 | Aug 19, 2013 |
| Mar 10, 2012 | 34925342X | RESOLVE | CLASS - 1 | PA CONTRARY TO APPROVED DOCUMENTS: PA PLAN SHOWN TABLES THROUGHOUT CENTER AREA OF 1ST FLR (PA PLAN #300418536PO28) AT... | $1,000 | $0 | Jan 28, 2013 |
| Mar 10, 2012 | 34947445X | RESOLVE | CLASS - 2 | ALTERED/CHANGED BLDG W/O A VALID C/O AS PER 28-118.5.1 - 28-118.3.2. NOTED: C/O #300418536T028 EXPIRED ON 12.14.11. R... | $0 | $0 | Apr 30, 2012 |
| Jun 3, 2011 | 34913439Y | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY IN THAT EXIT PASSAGEWAY LEADING FROM EAST SIDE OF BLDG IS BEING OBSTR... | $800 | $0 | Nov 14, 2011 |
| Jun 3, 2011 | 34913438M | RESOLVE | CLASS - 2 | OPERATION OF A PA W/O A CURRENT C/O. REMEDY: OBTAIN A PA C/O. | $0 | $0 | Jul 18, 2011 |
| Oct 21, 2006 | 34537172H | RESOLVE | Non-Hazardous | ALTERED BLDG OCCUPIED W/O A VALID C OF O JOB #300418536-17 EXPIRED 8/26/04. REMEDY: OBTAIN VALID C OF O. | $2,500 | $0 | Sep 17, 2007 |
| Nov 13, 2002 | 34368723K | ACTIVE | Non-Hazardous | WORK DOES NOT CONFORM TO APPROVED PLANS.JOB#300418536 FOR ALT TYPE 1 AT 1ST FLOOR EATING AND DRINKING AREA AND 2ND FL... | $250 | $0 | Jul 14, 2003 |
| Mar 14, 2002 | 34295458Y | RESOLVE | Hazardous | WORK DOES NOT CONFORM TO APPROVED PLANS. NOTED: STEEL FRAMED GLASS STRUCTURE CONSTRUCTION ON 3RD FL. ROOF SIZAPPROX. ... | $1,250 | $0 | Jul 1, 2002 |
| Mar 14, 2002 | 34295427L | RESOLVE | Non-Hazardous | FILING A FALSE CERTIFICATION OF CORRECTION WITH THE NYC DEPART. OF BLDGS. PURSUANT TO SECTION 26-126.2, RESPONDENT FI... | $2,500 | $0 | Jul 1, 2002 |
| Jan 24, 2002 | 34312547H | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING HAZARDOUS DEFECT NOTED AT CONNER STORE SUSPENPED LATHE PLASTER CEILING WITH ADDITIONAL A... | $800 | $0 | Mar 11, 2002 |
| Nov 22, 1999 | 34222308L | RESOLVE | Non-Hazardous | ALTERED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY. TCO #246215 ISSUED 10/07/99 WHICH EXPIRED 10/07/9... | $0 | $0 | Jul 17, 2000 |
| Mar 11, 1998 | 34173243L | RESOLVE | Hazardous | WORK WITHOUT A PERMIT CREATING A HAZARDOUS CONDITION ABSERVATION A STEEL FRAME AND GLASS ENCLUSURE HAS BEEN ERECTED A... | $800 | $0 | Jul 6, 1998 |
| May 21, 1996 | 34133831L | RESOLVE | Non-Hazardous | PLUMBING WORK WITHOUT A PERMIT. NEW PLUMBING WORK BEING DONE THROUGH-OUT BUILDING, SUCH AS BATHROOMS & GAS PIPING NO ... | $350 | $0 | Jul 8, 1996 |
| Mar 2, 1995 | 34122594N | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE APPROVED PLANS AT PREMISES AT TIME OF INSPECTION. REMEDY: PROVIDE AND MAINTAIN APPROVED PLANS AT P... | $0 | $0 | Apr 17, 1995 |
| Jan 17, 1995 | 34120428Z | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT. WORK NOTED: EXCAVATION COMMENCED THROUGH FIRST STORY NORTH SECTION FLOOR APPROMIXATELY 4 TO 10... | $0 | $0 | Mar 6, 1995 |
| Jan 12, 1995 | 34120175J | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE APPROVED PLANS AT PREMISES AT TIME OF INSPECTION. REMEDY: PROVIDE APPROVED PLANS AT PREMISES DURIN... | $0 | $0 | Mar 6, 1995 |
| May 18, 1989 | 34026288P | RESOLVE | Non-Hazardous | PA CONTRARY TO APPROVED PLAN WALL ERECTED AT REAR AT THEATRE BY PROJECTION BOOTH AND TOILETS. | $200 | $0 | Jul 5, 1989 |
| May 18, 1989 | 34026287N | RESOLVE | Non-Hazardous | PA CONTRARY TO APPROVED PLANS WALL ELECTED AT PROJECTION BOOTH FOUR DOOR INSTALLED CREATING LOBBY. USE OF PROHIBITED ... | $400 | $0 | Jul 5, 1989 |
| May 18, 1989 | 34026291X | RESOLVE | Non-Hazardous | FAILURE TO POST APPROVED CAPACITY SIGN. EXIT DOOR BOT SIGN CLOSING. EXIT SIGN NOT ILLUMINATED . | $125 | $0 | Jul 5, 1989 |
| May 18, 1989 | 34026290Y | RESOLVE | Non-Hazardous | EXIT SIGN NOT ILLUMINATED FRM THEATRE #4 TO FIRE PASSAGE. SECONDARY FIRE ESCAPE PASSAGE HAS LOCK ON SCREEN DOOR. | $150 | $0 | Jul 5, 1989 |
| May 18, 1989 | 34026289R | RESOLVE | Non-Hazardous | NO EMERGENCY LIGHT IN EXIT PASSAGE FROM FROM THEATRE #3 USE OF PROHIBITED DOOR AT COURT YARD EXIT CYCLONE TYPE 8' HIG... | $300 | $0 | Jul 5, 1989 |