ECB violations

21-10 Borden Avenue, Queens • Block 00068 • Lot 0002

25 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jan 12, 2026 39173509L ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. DETECTED GAS LEAK AT BOILER ROOM. LOCATED ON FIRST FLOOR., REP... $2,500 $0 Feb 6, 2026
Jan 12, 2026 39173501R ACTIVE CLASS - 2 OBSERVED ON THE GROUND FLOOR SPRINKLER HEAD OBSTRUCTED ALSO NO FIRE STOP PROTECTION AROUND PIPE PENETRATION. WATER FO... $1,250 $0 Feb 6, 2026
Jan 12, 2026 39173500P ACTIVE CLASS - 2 OBSERVED NOT HAVING PROPER GAS APPLIANCE SHUT OFF VALVES FOR COOKING EQUIPMENT AND HOT WATER HEATERS. VENTS TO HOT WA... $1,250 $0 Feb 6, 2026
Oct 25, 2022 39072650H RESOLVE CLASS - 2 AT EXPOSURE # 2 (KITCHEN EMERGENCY EXIT WAY ) , DISPLACEMENT OF THE LAST THREE COURSES OF BRICK IN THE UPPER PART OF ... $1,250 $0 Oct 31, 2022
Sep 27, 2021 39048199M RESOLVE CLASS - 2 GAS LINE TO REGULATOR TO BE HARD PIPED,FLUEPIPE TO BE WELDED (FEDERAL BLR) REMOVE STOPPER ON BAROMETRIC DAMPER ,INTER... $625 $0 Oct 15, 2021
Sep 27, 2021 39048200K ACTIVE CLASS - 2 DRAFT IND.CANNOT RUN CONTINOUS MUST BE NTERLOCKED ,AND COMBUSTION AIR FAN TO BE INTERLOCKED,THIS IS A WATER HTR WITH ... $625 $0 Oct 15, 2021
Sep 24, 2019 39009969H RESOLVE CLASS - 2 FEDERAL FST-150 BOILER. MOTORIZED VALVE ON TOP OF BOILER CORRODED. CORRECT VIOLATING CONDITIONS AND SUBMIT A CERTIFIC... $0 $0 Oct 4, 2019
Jan 24, 2019 35383622N RESOLVE CLASS - 2 FAILURE TO PROVIDE/MAINTAIN SUFFICIETN ACCESS/WORK SPACE ABOUT ELECTRICAL EQUIPMENT. OBSERVED IN GAS METER ROOM (2) C... $0 $0 Apr 16, 2019
Aug 10, 2018 35347380L RESOLVE CLASS - 2 FAILURE TO PROVIDE, MAINTAIN SUFFICIENT ACCESS, WORK SPACE ABOUT ELECTRICAL EQUIPMENT. OBSERVED IN GAS METER ROOM. TW... $0 $0 Dec 11, 2018
Jul 24, 2018 35342349K ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: FAILURE TO COM PLY WITH LAW FOR DRAINAGE SYSTEM PER PC 702.1: ... $0 $0 Oct 2, 2018
Jul 24, 2018 35342348Z RESOLVE CLASS - 1 GAS PIPING NOT LABELED. OBSERVED ON 7/24/18 AT ABOVE ADDRESS GAS PIP ING IN CEILING FROM BOILER ROOM THROUGH CORRIDOR... $0 $0 Oct 2, 2018
Jul 11, 2018 32097354J ACTIVE CLASS - 2 24B,50A,50B,50C-AO SMITH MODEL HW1340 LP HOT WATER BOILER. 50A)MISSING MANUAL RESET LOW WATER CUT-OFF. 50B)FRESH AIR ... $0 $0 Oct 9, 2018
Jul 11, 2018 32097355L RESOLVE CLASS - 2 4A,24B,50A,50B,50C,50D,50E-FEDERAL FST-150 HEATING BOILER GAS-FIRED. 50A)DRAFT REGULATOR MISSING. 50B)SPILL SWITCH MI... $0 $0 Oct 9, 2018
Mar 29, 2018 35313030X RESOLVE CLASS - 1 UNLAWFUL ACTS FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER.RECORDSINDICATE BI APPLICATION WAS MADE TO CORRECT AND... $0 $0 May 29, 2018
Jan 8, 2018 35274563J RESOLVE CLASS - 1 FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35272091L ISSUED ON 07/11/2017 AND TO ... $0 $0 Oct 23, 2018
Aug 18, 2017 35277052L ACTIVE CLASS - 1 FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#35272426Y ISSUED ON 07-11-17 AND TO FILE A ... $0 $0 Nov 21, 2017
Jul 11, 2017 35272426Y ACTIVE CLASS - 1 WORK W/OUT A PERMIT. OBSERVED IN LAUNDRY ROOM ON MAIN FLR (1 STORY) GAS PLUMBING CONNECTIONS MADE TO DRYERS W/OUT PER... $0 $0 Sep 5, 2017
Jul 11, 2017 35272091L RESOLVE CLASS - 1 FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED @ WATER MAIN PIPE: MAIN GROUNDING CONDUCTOR FOR BLDGS ELECTRICAL SYSTE... $0 $0 Dec 26, 2017
Jul 11, 2017 35272427X ACTIVE CLASS - 1 FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED FROM DOB RECORDS THAT NO TEST WAS PERFORMED ON PLUMBI... $0 $0 Sep 5, 2017
Jan 13, 2017 35226476P ACTIVE CLASS - 1 RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPEMTN. AT TIME OF MY INSPECTION I OBSERVED IN THE LAUNDRY ROOM COMMERCIAL... $0 $0 Apr 4, 2017
Jul 28, 2016 35200998R RESOLVE CLASS - 2 OPERATING A PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERATION (PACO) NOTED: CAFETERIA/DINING ROOM WITH 13 TABL... $0 $0 Sep 13, 2016
Feb 24, 2016 35171278Z RESOLVE CLASS - 2 OPERATING A PLACE OF ASSEMBLY W/O A CURRENT CERT OF OPERATION. NOTE: CAFETERIA/DINING ROOM W/TABLES AND CHAIRS ARRANG... $0 $0 Apr 5, 2016
Aug 5, 2003 32042763M RESOLVE Hazardous 4A,19B $0 $0 Dec 16, 2003
Aug 5, 2003 32042769N RESOLVE Non-Hazardous 50. 50)MANHOLE AT TOP OF BOILER IS LEAKING. $0 $0 Dec 16, 2003
Jul 18, 1990 34042675P RESOLVE Non-Hazardous ALTERED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY.EX-PIRED CERTIFICATE OF OCCUPANCY #C.O. Q211603 UN... $0 $0 May 7, 1991