ECB violations
41-01-41-07 49 Street, Queens • Block 00134 • Lot 0025
12 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jul 21, 2010 | 32069135L | RESOLVE | CLASS - 1 | 50. 50- WEIL MCLAIN GAS HEATING BOILER INSTALLED W/O A PERMIT. OBTAIN A PERMIT TO LEGALIZE BOILER INSTALLATION | $0 | $0 | Feb 15, 2011 |
| Jul 21, 2010 | 32069136N | RESOLVE | CLASS - 2 | 36,15,16,50,50A,50B,34B. 36/50- BOILER NOT REGISTERED, NOT SIGNED OFF.50A- FRESH AIR DUCT TOO SMALL HAS NO FIRE DAMPE... | $500 | $0 | Feb 15, 2011 |
| Mar 13, 2007 | 32053263J | RESOLVE | Non-Hazardous | 9A/9B/48B/38/.9A-PROVIDE PROOF "R1"FORM FROM AUTHORIZED REPAIR FIRM FOR WELDED HAND HOLE RING ON BOILER.38-FRESH AIR ... | $0 | $0 | May 8, 2007 |
| Sep 21, 2004 | 32045634J | RESOLVE | Hazardous | CEASE USE 51/4A/19B 50-INSTALL THE RELIEF VALVE IN A VERTICAL POSSITIAN | $400 | $0 | Feb 1, 2005 |
| Sep 21, 2004 | 32045635L | RESOLVE | Hazardous | CEASE USE 46/51/50A/50B 50-BLR SEALED LOW WATER CUT OFF NOT WIRED IN 50A-THE FLUE PIPE IS LOOSE 50B-INSTALL A BOILER ... | $400 | $0 | Feb 1, 2005 |
| Sep 21, 2004 | 32045633H | RESOLVE | Non-Hazardous | 50A 50A-INSTALL THE RELIEF VALVE WITH THE SPINDLE VERTICAL | $180 | $0 | Feb 1, 2005 |
| Sep 21, 2004 | 32045632X | RESOLVE | Hazardous | 51/32A/19B/38/50A UTICA BOILER 51 CEASE USE NO LOW WATER CUT OFF 50A-PIPE DOWN THE RELIEF VALVE TO A SAFE POINT | $400 | $0 | Feb 16, 2005 |
| Sep 20, 2004 | 32045629P | RESOLVE | Non-Hazardous | BQ9/32A/50B/36/50A/50C 50A-CLEAN CHIMNEY UP TO ROOF 50B-PIPE DOWN THE RELIEF VALVE DISCHARGE 50C-SEAL THE HOLES IN TH... | $180 | $0 | Feb 1, 2005 |
| Sep 20, 2004 | 32045628N | RESOLVE | Hazardous | 51/3D/50A/50C/21A/50B 1988 FULTON NBD 55002 51)SEALED BOILER DUE TO OILLEAK AND PARTIALY CLOGGED CHIMNEY 50A-REPAIR T... | $400 | $0 | Nov 9, 2004 |
| Aug 14, 2000 | 32019250L | RESOLVE | Non-Hazardous | 36 49 18B 1).BOTTOM HAND HOLES WELDED RECEIPT BY CERTIFIED WELDER HOLDING "R" STAMP OR NYS AUTHORIZATION TO SUBMIT 2)... | $350 | -$350 | Feb 13, 2001 |
| Apr 13, 1992 | 34069619K | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. DEFECT IS: FIRE-RATED CONSTRUCTION REMOVED FROM BOTTOM & SIDE OF STAIRS AT LEFT/REAR OF 1ST FLOO... | $0 | $0 | May 26, 1992 |
| Apr 10, 1991 | 32007819Z | RESOLVE | Non-Hazardous | 32)PROPERLY SEAL FLUE PIPE TO BASE OF CHIMNEY | $85 | $0 | Oct 22, 1991 |