Oct 28, 2025 39165061M ACTIVE CLASS - 2 OBSERVED AT EXP/#2 AT 38 STREET SIDE AT EXTERIOR OF THE BUILDING DUCT WORK IN PROGRESS. INSIDE THE BUILDING AT 1ST FL... $1,250 $630 Jan 6, 2026
Mar 17, 2022 35650840P RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.NOTED OBSERVEDAT FRONT OF BUILDING AT EXP1 AT FACADE SOME OF ... $625 $804 Jun 14, 2022
Dec 28, 2021 39053484H RESOLVE CLASS - 1 OBSERVED A STORAGE ROOM ÝFOR PROPANE TANKS¨ERECTED BEHIND MAIN ENTRY DOOR AT PUSH CART GARAGE OBSTRUCTING EGRESS TO T... $0 $0 Jul 19, 2022
Dec 28, 2021 39053486L RESOLVE CLASS - 1 OBSERVED MULTIPLE PARTITION WALLS CREATED THROUGHOUT GROUND FLOOR ÝCONSISTING OF WOOD, CEMENT BLOCK AND BOARD¨ WITH S... $0 $0 Jul 19, 2022
Dec 28, 2021 39053485J RESOLVE CLASS - 1 OBSERVED COMBUSTIBLE STORAGE OF PROPANE TANKS INSIDE A MAKESHIFT STORAGE ROOM CONSISTING APPROX 26 PROPANE TANKS., MA... $0 $0 Jul 19, 2022
Dec 9, 2021 35636253J RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT TIME OFINSPECTION,OBSERVED AT EXP1(FRONT)2(LEFT)AND 4(... $625 $625 Jun 14, 2022
Oct 19, 2021 35581315K RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER NOTED:ATOI OBSERVED GLASS BLOCK WINDOWS THERES MISSING BLOCKS@EXP1,2... $625 $625 Apr 5, 2022
Feb 13, 2018 38260564N RESOLVE CLASS - 2 70M07,70M07,100M07. 70M07:PROVIDE LOCK ON WALK IN PIT DOOR.PROVIDE WALK IN PIT DOOR SIGN.100M07:PROVIDE TOE GUARD ON ... $1,250 $0 Apr 3, 2018
Feb 13, 2018 38260565P RESOLVE CLASS - 1 42N11. 42N11:MOTOR FUSES ON CONTROLLER BYPASSED.REPLACE FUSES. $2,500 $0 Apr 3, 2018
Apr 17, 2017 35184460H RESOLVE CLASS - 3 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS. JOB#421359229 DWG DATED 8/29/16. NOTED: 1)SPRAY BOOTH ENCLO... $100 $0 Aug 22, 2017
Aug 28, 2013 35010261P RESOLVE CLASS - 2 SIDEWALK SHED DOES MEET CODE SPECIFICATIONS. NOTED: SIDEWALK HAS BEEN ERECTED AT EXP #1 (43 AVE) & EXP #2 (38 ST) & E... $2,400 $0 Nov 12, 2013
Aug 28, 2013 35010260N RESOLVE CLASS - 2 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS &/OR APPROVEDAMENDMENTS. NOTE: SIDEWALK SHED HAS BEEN INSTAL... $500 $0 Nov 12, 2013
Aug 28, 2013 35010259X RESOLVE CLASS - 2 FAILURE TO PROVIDE/POST SIGNS AT JOB SITE PURSUANT TO SUBSECTION. NOTESIDEWALK SHED HAS BEEN ERECTED AT EXP #1 (43 AV... $800 $0 Nov 12, 2013
Aug 5, 2013 35005980P RESOLVE CLASS - 2 WORK W/O A PERMIT. WORK NOTED: INSTALLED SIDEWALK SHED AT EXPOSURE 1,2& 4 UNDER APPL #440095111-ALT3. NO PERMITS IS I... $400 $0 Sep 24, 2013
Jul 6, 2013 35015598N RESOLVE CLASS - 1 FAILUR TO MAINTAIN BLDG WALL(S) OR APPURTENANCES:AT S/W CORNER OF BLDGSECTION OF MASONRY PLASTER APPRX 8SQ IN DISLODG... $1,000 $0 Oct 8, 2013
May 2, 2010 34853075K RESOLVE CLASS - 2 FAILURE TO SAFEGUARD PUBLIC AND PROPERTY. CONSTRUCTION OPS AT 4TH FL. REMOVED GLASS BLOCK AND DEBRIS FELL TO STREET L... $6,000 $0 Jun 22, 2010
Feb 17, 2009 32065072P RESOLVE CLASS - 3 50A,B. FULTON V.T. BOILER,10HP,NB64720,GAS 1992.50A-STRUCTURE SPLIT INUPPER SECTION OF FLUE PIPE.BOILER NOT IN SERVIC... $0 $0 Apr 14, 2009
Dec 17, 2008 32065065R RESOLVE CLASS - 3 REIMERS MINIATURE ELECTRIC HP STEAM BOILER 20 KW; NB 64070. 36 REFERENCED HIGH PRESSURE PROCESS STEAM BOILER IN OPERA... $500 $0 Feb 10, 2009
Mar 13, 2007 32053266P RESOLVE Non-Hazardous 18A/18B/. $180 $0 May 8, 2007
Mar 13, 2007 32053267R RESOLVE Non-Hazardous 48B/18A/18B/50A/.50A-PIPE DOWN DISCHARGE PIPE FROM SAFETY VALVE. $0 $0 May 8, 2007
Mar 13, 2007 32053265N RESOLVE Non-Hazardous 48B/38/9A/.9A-PROVIDE PROOF OF"R1"FORM FOR WELDED REPAIRS ON HAND HOLEFROM AUTHORIZED WELDING FIRM HOLDING AN "R"STAMP. $2,500 $0 May 8, 2007
Mar 13, 2007 32053264L RESOLVE Non-Hazardous 18A/18B/48B/50A/.50A-REMOVE STORAGE FROM BOILER ROOM. $350 $0 Feb 5, 2008
Apr 20, 2005 38152229H RESOLVE Non-Hazardous 11I11/31H10/25M07/21L10/24L10/83O02/84M07/18L10/12Q07/85U05/58A10/55Q06/41G11.(11) CAR OPERATING HANDLE.(21) PROVIDE ... $0 $0 Jun 7, 2005
Apr 6, 2005 32047601M RESOLVE Non-Hazardous 50. 50)REVERSE THE VALVES IN THE BOTTOM BLOWDOWN LINE SO THAT THE QUICK CLOSING VALVE IS CLOSEST TO THE BOILER FOLLOW... $180 $0 May 24, 2005
Apr 6, 2005 32047602Y RESOLVE Non-Hazardous BQ9/36/50A/50B/50C/48B. 1992 FULTON NB 63922. 50A)REVERSE THE VALVES ON THE BOTTOM BLOW DOWN LINE. 50B) PIPE THE SAFE... $680 $0 Aug 16, 2005
May 14, 2001 32025347Z RESOLVE Non-Hazardous RIHTSIDE OF BOILER NOT ACCESSIBLE FOR INSPECTION 2-WAILER MAKE UP FEED TANK ERRODED LEAKING 3- TWO BOTTOM HAND HOLES ... $350 $0 Oct 23, 2001
May 14, 2001 32025349M RESOLVE Non-Hazardous SUBMIT PROOF OF REGISTRATION FOR THIS BOILER 2 WATER COLUMN DRAINS IS REDUCED ..... RUN THE SAME SIZE AS ORIGIN $0 $0 Jul 3, 2001
May 14, 2001 32025348K RESOLVE Non-Hazardous THE STEAM CONNECTION IN SAFETY VALUE LINE TO BE REMOVED AND SAFETY VALUE BE REPLACED DIRECTLY COTED TO THE BOILER WIT... $0 $0 Jul 3, 2001
Jan 6, 2001 38110047L RESOLVE Non-Hazardous 39H08,03I11,02X11,73O02. $0 $0 Feb 20, 2001
Jan 6, 2001 38110046J RESOLVE Non-Hazardous 39H08,73O02,3507,35I12,74X11,15R09,74M07. 35-M-07-GRILLE FOR SMOKE HOLE, 35-I-12-WINDOW PANES, 74-X-11-EMERGECY PHONE... $2,500 $0 May 9, 2001
Aug 4, 2000 32019238Z RESOLVE Non-Hazardous 49. HAND HOLES BOTTOM ONLY WELDED RECEIPT BY A CERTIFIED WELDER HOLDING R STAMO OR NYS AUTHORIZATION TO SUBMIT. $0 $0 Sep 19, 2000
Aug 27, 1999 38089397H RESOLVE Non-Hazardous 37H 570 37H 12 MAIN LINE CONTACTS $2,500 $0 Oct 12, 1999
Jul 15, 1998 38075920X RESOLVE Non-Hazardous 57,O02,58O02,59O02.35P07,74I11, 74I11 REPAIR CAR HANDEL. $0 $0 Jan 5, 1999
Jul 15, 1998 38075919Z RESOLVE Non-Hazardous 30O02,35P07,74O02 $0 $0 Jan 5, 1999
Dec 23, 1997 38067967N RESOLVE Non-Hazardous 75U,40B,14I,16H,09H,02B, 40-PROVIDE UP OVER SPEED TRIPPING SWITCH AND CERTIFY TO PROPER CALIBRATION AS PER ANSI A:17.... $0 $0 Feb 10, 1998
Dec 19, 1997 38068453K RESOLVE Non-Hazardous 75U57O16D11D 75-PERFORM 5 YEAR TEST & TAG 18-PROVIDE COVERS ON INTERLOCKS. $0 $0 Feb 10, 1998
Jun 30, 1997 32014884K RESOLVE Non-Hazardous $400 $0 Jan 13, 1998
Jan 4, 1995 34119356K RESOLVE Non-Hazardous WORK WITHOUT A PERMIT. WORK NOTED: ON 2ND FLOOR OF PREMISES A SHEET-ROCK METAL STUD WALL HAS BEEN ERECTED, SUB DIVIDI... $0 $0 Apr 25, 1995
Dec 30, 1994 38046122Z RESOLVE Non-Hazardous 14I,57O,35I,36I.35-WINDOWS 36-HANDLE. $1,000 $0 Mar 14, 1995
Dec 30, 1994 38046121R RESOLVE Non-Hazardous 15R,57O. 15-LOCKS. $0 $0 Apr 26, 1995
Aug 1, 1994 32012903H RESOLVE Non-Hazardous BLOW DOWN LINE FROM THE BOILER CONNECTED TO THE SEWER DRAIN TO REMOVE IT. INSALL A BLOW DOWN TANK, 48B,49 $350 $0 Nov 1, 1994
Apr 27, 1992 32009474L RESOLVE Hazardous 3A, $170 $0 Jun 30, 1992
Feb 19, 1991 38006200Z RESOLVE Non-Hazardous 15R,14L,(15)UNATHORIZED LOCK FROM BSMT&1ST FLOOR HOISTWAY DOORS. $1,000 $0 May 7, 1991
Feb 19, 1991 38006199K RESOLVE Non-Hazardous 03L,17L,(03)TELPHONE IN CAB. (17)CAR DOOR $0 $0 Apr 2, 1991
Sep 4, 1990 32006690M RESOLVE Hazardous 3A, FLUE PIPE CORRODED IN BETWEEN THE FAN & THE WINDOW. $170 $0 Oct 23, 1990