ECB violations
33-17-33-21 Greenpoint Avenue, Queens • Block 00307 • Lot 0010
38 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 4, 2025 | 39159148Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE ) 27-345 711.2.4 ( 20... | $0 | $0 | Nov 18, 2025 |
| Sep 4, 2025 | 39159147M | RESOLVE | CLASS - 2 | OBSERVED OUTSIDE IN THE STREET FIRE DEPARTMENT CONNECTION BLOCKED BY TREES. CRACK ON STORM DRAIN AND NOT USING THE PR... | $0 | $0 | Nov 18, 2025 |
| Sep 3, 2025 | 39159111K | ACTIVE | CLASS - 1 | CLASS 1 C/U ITEM: DOOR LOCK MONITORING SYSTEM INOPERABLE, REPAIR AND EMAIL THE ELEVATOR DIVISION AT EIR@BUILDINGS.NYC... | $1,250 | $1,250 | Jun 4, 2026 |
| May 8, 2025 | 39147460K | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION # 39125354J, FILE A CERTIFICATE OF CORRECTION | $1,280 | $1,280 | Dec 15, 2026 |
| Sep 19, 2024 | 39125354J | RESOLVE | CLASS - 1 | OBSERVED EXCESSIVE HOLES PENETRATION THROUGHOUT THE BUILDING. LOCATED IN STORAGE ROOMS AND MECHANICAL ROOM ON TOP FLO... | $2,500 | $2,500 | Nov 26, 2024 |
| Nov 7, 2022 | 39073559L | RESOLVE | CLASS - 1 | I OBSERVED IN THE STORAGE ROOM NEAR ROOM 302, THE STAFF BREAKROOM AND LOCKER ROOM ON THE 2ND FLOOR, THE USE OF FLEXIB... | $1,600 | $1,600 | May 23, 2023 |
| Nov 7, 2022 | 39073550P | RESOLVE | CLASS - 1 | OBSERVED: FROM SECOND FL TO 5TH FL EXIT CORRIDORS ARE BEING OBSTRUCTED BY MATERIALS SUCH AS GARBAGE CANS, DESKS, CHAI... | $312 | $312 | Jan 24, 2023 |
| Nov 7, 2022 | 39073552Z | RESOLVE | CLASS - 2 | OBSERVED: AT 5TH FL, ROOMS UNDER THE ROOF AS STORAGE RM/MECHANICAL RM, ELEVATOR RM, STORAGE RM FROM 5TH FL TO 2ND FL ... | $625 | $625 | Jan 24, 2023 |
| Nov 7, 2022 | 39073554M | RESOLVE | CLASS - 2 | OBSERVED: AT EXPOSURE #1,2,3 &4, BRICK FACADE/ CHIMNEY WITH MANY CRACKS, LOSS OF MORTAR. DAMAGE AND LOSS OF GUTTERS/M... | $625 | $625 | Jan 24, 2023 |
| Nov 7, 2022 | 39073560Z | RESOLVE | CLASS - 2 | I OBSERVED IN THE LAUNDRY, THE METAL RACEWAY SUPPLYING POWER TO THE DRYER BROKEN WITH EXPOSED WIRES AND THE SHUT-OFF ... | $400 | $400 | Jan 24, 2023 |
| Nov 7, 2022 | 39073561K | RESOLVE | CLASS - 2 | I OBSERVED THROUGHOUT THE CORRIDORS AND THE STAIRWELLS THE REPLACEMENT OF EXISTING EMERGENCY LIGHTS. NO ACTIVE PERMIT... | $400 | $400 | Jan 24, 2023 |
| Sep 19, 2022 | 39070284H | RESOLVE | CLASS - 2 | DIRTY PIT , CLEAN / WORN RELEASE ROLLERS , REPLACE / CLUTCH SCRAPING AGAINST FACIA , ADJUST / MCP LOG BOOK NOT CURREN... | $312 | $312 | Nov 15, 2022 |
| Sep 30, 2021 | 39048456Y | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $27 | Nov 16, 2021 |
| Sep 27, 2021 | 39048178N | RESOLVE | CLASS - 2 | SAFETY VALVE DISCHARGE IS MISSING AIR GAP FUNNEL INTO MANIFOLDED DRAIN PIPE TO SUMP/MINIMUM 8X8 ACCESS DOOR MISSING A... | $0 | $0 | Nov 16, 2021 |
| Sep 27, 2021 | 39048179P | RESOLVE | CLASS - 2 | THE SAFETY VALVE DISCHARGE IS MISSING AIR GAP FUNNEL INTO MANIFOLDED DRAIN PIPE TO SUMP;CORRECT VIOLATION AND SUBMIT ... | $0 | $0 | Nov 16, 2021 |
| Feb 3, 2020 | 39016754X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLAINT MANNER, I OBSERVED IN THE BOILER ROOM LOCATED AT FIRST FLOOR LEVEL WAT... | $1,563 | $0 | Aug 25, 2020 |
| Sep 25, 2019 | 35429763H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#39006367R ISSUED ON 07-25-19 & TO FILE A C OF C PURSUAN... | $1,250 | $0 | Dec 13, 2019 |
| Jul 25, 2019 | 39006355J | RESOLVE | CLASS - 2 | OBSERVED IN ELEVATOR MOTOR ROOM, 5TH FLOOR WEST STORAGE ROOM THE USE OF FLEXIBLE CORDS AS PERMANENT WIRING FOR LIGHTI... | $2,000 | $0 | Mar 9, 2021 |
| Jul 25, 2019 | 39006367R | ACTIVE | CLASS - 1 | OBSERVED FALSE DOCUMENTS SUBMITTED FOR ECB #35383929H STATING THAT THE VIOLATING CONDITIONS WERE CORRECTED BY JAI AMB... | $5,000 | $0 | Jun 22, 2021 |
| Jul 25, 2019 | 39006366P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDERS AS PER ECB #35383929H ISSUED ON 02/04/2019, FILE A CERTIFICATE OF CORRECTION | $0 | $0 | Mar 23, 2021 |
| Jul 25, 2019 | 39006361X | RESOLVE | CLASS - 2 | OBSERVED IN BOILER ROOM ,GREENFIELD RACEWAY NOT CONNECTED TO MOTOR TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY., PROVI... | $1,200 | $0 | Mar 9, 2021 |
| Jun 4, 2019 | 35434203X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER.OBSERVED AT THE SIDE OF THE BUILDING LOCATED ON THE GREENPOINT AV... | $312 | $0 | Aug 28, 2019 |
| Apr 20, 2019 | 35415055J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED:SHEET METAL CLADDING ON FACADE FOR EXISTING CORNICE PULLING A... | $3,155 | $0 | Nov 10, 2020 |
| Apr 6, 2019 | 35392788H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35381119R ISSUED ON 2/4/19 AND TO FILE A... | $1,280 | $0 | Jun 11, 2019 |
| Apr 6, 2019 | 35415210K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. OSBERVED ON THE SIDE OF THE BUILDING LOCATED ON GREENPOINT A... | $3,155 | $0 | Jun 11, 2019 |
| Feb 4, 2019 | 35381116L | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. OBSERVED IN BASEMENT THE BALL DRIP FOR THE FIRE DEPT CONNECTION ... | $250 | $0 | Apr 16, 2019 |
| Feb 4, 2019 | 35381119R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED GAS PIPING AT GAS METER LOCATED OUTDOOR NOT PAINTED TO BE... | $3,125 | $0 | Apr 16, 2019 |
| Feb 4, 2019 | 35381120Y | RESOLVE | CLASS - 1 | SEC. 411.1 MISC VIOLATIONS: RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED IN LAUNDRY ROOM ON 1ST FL RES... | $6,250 | $0 | Apr 16, 2019 |
| Feb 4, 2019 | 35383930P | RESOLVE | CLASS - 2 | ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED THE INSTALLATION OF SHELVING FOR ... | $1,500 | $0 | Apr 16, 2019 |
| Feb 4, 2019 | 35383931R | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERUPTER PROTECTION (GRI) AS REQUIRED.OBSERVED IN SPRINKLER CONTROL ROOM AN... | $5,000 | $0 | Apr 16, 2019 |
| Feb 4, 2019 | 35383929H | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS DEVICES,APPLIANCES OR WIRING IN USE. OBSERVED I... | $830 | $0 | May 21, 2019 |
| Feb 4, 2019 | 35379976Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRE STOPPINGPER BC 712.3;27-345. HOLES IN WALL,CABLES AND P... | $3,125 | $0 | Apr 16, 2019 |
| Feb 4, 2019 | 35379977K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. CRACKS AND MORTAR MISSING IN MANY AREAS ON EXP 1-4 THROUGHOUT ... | $3,125 | $0 | Apr 16, 2019 |
| Feb 4, 2019 | 35381115J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. OBSERVE ON SIDE OF BLDG LOCATED AT GREENPOINT AVE(EXP#2)FIRE DEP... | $3,125 | $0 | Apr 16, 2019 |
| Feb 4, 2019 | 35379978M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. SHEET METAL CLADDING ON FACADE FOR EXISTING CORNICE PULLING AW... | $3,125 | $0 | Apr 16, 2019 |
| Feb 4, 2019 | 35381117N | RESOLVE | CLASS - 2 | SEC. 903.6 FAILURE TO PAINT DEDICATED SPRINKLER PIPING/VALVES IN ACCORDANCE W/SECTION. OBSERVED ON ALL FLOOR DEDICATE... | $3,125 | $0 | Apr 16, 2019 |
| Feb 4, 2019 | 35381118P | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON ALL FLOORS IN THE STAIRWELLS NO PRESSURE GAUGES INSTAL... | $250 | $0 | Apr 16, 2019 |
| Sep 19, 2008 | 38191015Y | RESOLVE | CLASS - 2 | 02X10.38R11.35Q07.60Q07.39Q07. 02X10 INSIDE CAR PHONE DOESN'T WORK 38R11 EXTENSION CORD FOR TRAVELER 35Q07 MISSING EL... | $500 | $0 | Mar 9, 2010 |