ECB violations
35 Street, Queens • Block 00377 • Lot 0013
67 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 9, 2026 | 39179637N | ACTIVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED IN MAIN ELECTRICAL ROOM IN BASE... | $24,000 | $24,000 | May 19, 2026 |
| Mar 9, 2026 | 39179638P | ACTIVE | CLASS - 1 | MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED IN MAIN ELECTRICAL ROOM THERE WAS WATER ... | $8,000 | $8,000 | May 19, 2026 |
| Mar 9, 2026 | 39179639R | ACTIVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... | $8,000 | $8,000 | May 19, 2026 |
| Mar 9, 2026 | 39179690M | ACTIVE | CLASS - 1 | OBSERVED IN THE BASEMENT WASTE AND GAS LINES PRESENT IN THE DEDICATED ELECTRICAL ROOM. WATER LEAKED FROM CELLING ONTO... | $12,500 | $12,500 | May 19, 2026 |
| Mar 9, 2026 | 39179691Y | ACTIVE | CLASS - 1 | OBSERVED GROUND FLOOR SPRINKLER HEAD OBSTRUCTED. IN BASEMENT SPRINKLER HEADS MISSING CAPS, SPRINKLER SYSTEM TO CAFE I... | $12,500 | $12,500 | May 19, 2026 |
| Mar 9, 2026 | 39179689P | ACTIVE | CLASS - 1 | OBSERVED IN HOT WATER HEATER ROOMS ON FLOORS 2 THROUGH 5 IMPROPER HOT WATER HEATERS EXHAUST PIPING. ON 5 FLOOR NO TEM... | $12,500 | $12,500 | May 19, 2026 |
| Mar 9, 2026 | 39179600J | ACTIVE | CLASS - 1 | CLASS 1: FIREFIGHTER SERVICE PHASE I INOPERATIVE - NO ELEVATOR RECALL, KEY CYLINDER ROTATES 360, REPAIR AND REQUEST R... | $6,250 | $6,250 | May 19, 2026 |
| Mar 9, 2026 | 39179601L | ACTIVE | CLASS - 1 | CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-9... | $6,250 | $6,250 | May 19, 2026 |
| Mar 9, 2026 | 39179602N | ACTIVE | CLASS - 2 | CLASS 2: EMERGENCY PHONE INOPERATIVE, PROVIDE 24-HOUR 2-WAY COMMUNICATION SERVICE. IN-CAR POSITION INDICATOR INOPERAT... | $3,125 | $3,125 | May 19, 2026 |
| Sep 24, 2024 | 39125629J | RESOLVE | CLASS - 2 | CORRECT CAR FROM RE-LEVELING. CORRECT CAR FROM SCRAPING ON THE LOWER LANDING. | $0 | $0 | Feb 4, 2025 |
| Sep 24, 2024 | 39125630R | RESOLVE | CLASS - 1 | : FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON IN... | $1,250 | $1,250 | Jul 15, 2025 |
| Sep 24, 2024 | 39126199N | RESOLVE | CLASS - 2 | OBSERVED EXCESSIVE COMBUSTIBLE STORAGE IN THE GAS METER ROOM. AS PER APPENDIX E 3 OF THE FGC GAS METER ROOMS, WHEN PR... | $310 | $310 | Dec 10, 2024 |
| Sep 24, 2024 | 39125696J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $625 | $625 | Aug 19, 2025 |
| Sep 24, 2024 | 39125697L | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. NON SELF CLOSING DOORS LOCATED IN UTILITY ROOMS THROUGHOUT BUILDING. POTENTIAL FIRE HAZAR... | $312 | $312 | Aug 19, 2025 |
| Sep 24, 2024 | 39125631Z | RESOLVE | CLASS - 2 | IN-CAR ALARM INOPERATIVE. IN-CAR EMERGENCY LIGHTING INOPERATIVE. | $625 | $625 | Sep 16, 2025 |
| Sep 24, 2024 | 39126197J | RESOLVE | CLASS - 1 | OBSERVED RUSTED AND CORRODE GAS PIPING TO HVACS AT ROOF LEVEL. AS PER 404.11 OF THE FGC PROTECTION AGAINST CORROSION.... | $1,250 | $1,250 | May 27, 2025 |
| Sep 24, 2024 | 39126198L | RESOLVE | CLASS - 2 | OBSERVED INCORRECT EXHAUST PIPING TO ALL OF THE WATER HEATERS THROUGHOUT BUILDING (EXCEPT 1 IN THE MECHANICAL ROOM ON... | $312 | $312 | May 27, 2025 |
| Sep 24, 2024 | 39126211R | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS IN THE HALLWAYS AND COMMON AREAS THE FAILURE TO PROVIDE TAMPER RESISTANT RECEPTACLES AS REQU... | $400 | $400 | May 27, 2025 |
| Sep 24, 2024 | 39126212Z | RESOLVE | CLASS - 1 | I OBSERVED IN ALL ELECTRICAL CLOSETS AND THE MAIN ELECTRICAL ROOM EXCESSIVE STORAGE OF MATERIALS, BUILDING EQUIPMENT,... | $1,250 | $1,250 | May 27, 2025 |
| Sep 24, 2024 | 39126213K | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS THE MECHANICAL ROOMS ON THE A & B SIDES, THE FAILURE TO INSTALL REMOTE SHUT DOWN AT THE POIN... | $2,500 | $2,500 | May 27, 2025 |
| Sep 24, 2024 | 39126210P | RESOLVE | CLASS - 2 | I OBSERVED THE INSTALLATION OF AN ELECTRIC HEATER IN THE 4TH FLOOR STAIRWAY WITH NO SERVICE DISCONNECT WITHIN 5 FEET ... | $0 | $0 | May 27, 2025 |
| Sep 24, 2024 | 39126214M | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS THE INSTALLATION OF DATA WIRING AND EQUIPMENT, ELECTRICAL CLOSETS ARE DEDICATED TO ELECTRICA... | $0 | $0 | May 27, 2025 |
| Sep 24, 2024 | 39125698N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED EXCESSIVE CRACK LOCATED BENEATH STAIRCASE IN THE ELEC... | $1,250 | $0 | Feb 4, 2025 |
| Mar 21, 2013 | 34984271H | RESOLVE | CLASS - 2 | RCNY REFERENCE STANDARD#5. FAILURE TO ADHERE TO REFERENCE STANDARD#5 OF NYC BUILDING CODE FOR SUSPENDED CEILING (DROP... | $0 | $0 | May 7, 2013 |
| Aug 9, 2012 | 34948877Y | RESOLVE | CLASS - 1 | SEC. 3303.11 FAILURE TO MAINTAIN (OR TO PROVIDE ADEQUATE ALTERNATIVES TO) REQUIRED EGRESS DURING ALTERATION WORK TO E... | $1,600 | $0 | Jan 29, 2013 |
| Aug 9, 2012 | 34948876M | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BUILDING DEPT RECORDS. DURING INSPECTION IT WAS SEEN THAT SLEEP Q... | $2,400 | $0 | Sep 25, 2012 |
| Jul 23, 2012 | 34959095N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT. MANNER "INOPERABLE SPRINKLER SYSTEM" AT THE TIME OF INSPECTION I OBSERVED... | $1,000 | $0 | Sep 11, 2012 |
| Jul 23, 2012 | 34935048Y | RESOLVE | CLASS - 2 | FULL SWO - ISSUED PURSUANT TO 28-207.2 AND POSTED AT PREMISES. WORK W/O A PERMIT. (SPRINKLER SYSTEM REMOVED FROM 2,3,... | $800 | $0 | Sep 11, 2012 |
| Jul 19, 2012 | 34956552X | RESOLVE | CLASS - 2 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. AT 3RD FLR 1 WORKER SMOKING INSIDE B... | $1,200 | $0 | Nov 13, 2012 |
| Oct 19, 2011 | 34897812X | RESOLVE | CLASS - 1 | 3307.6.5 CONSTRUCTION OF SIDEWALK SHED UNLESS THE TOP DECK OF THE SIDEWALK SHED IS BUILT SOLIDLY AGAINST THE FACE OF ... | $4,000 | $0 | Mar 20, 2012 |
| Oct 19, 2011 | 34897811Y | RESOLVE | CLASS - 2 | SIDEWALK SHED DOES NOT MEET CODE SPECIFICATION NOTED AT EXP #3 APPX 10FT OF PARAPET IS LOOSE BULKING TOWARDS STREET F... | $2,400 | $0 | Mar 20, 2012 |
| Aug 28, 2010 | 34871859H | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER.RESPONDENT FAILED TO CORRECT THE CONDITIONS CITED ON ... | $2,400 | $0 | Sep 13, 2011 |
| Apr 5, 2010 | 34840099M | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/COMM'S ORDER TO CORRECT VIO #34818633M FOR WORK W/O PERMIT @ 4TH FLR, SUBDIVIDED BY INSTALLED FUL... | $2,400 | $0 | Oct 5, 2010 |
| Nov 5, 2009 | 34818633M | RESOLVE | CLASS - 1 | WORK W/O A PERMIT - WORK NOTED: AT 4TH FLR FACTORY. FULL HEIGHT SHEET ROCK PARTITIONS ERECTED FROM (FINISH) FLR THROU... | $1,600 | $0 | Oct 5, 2010 |
| Sep 17, 2009 | 34804007H | RESOLVE | CLASS - 2 | SIDEWALK SHED AT EXP 1 ERECTED UNDER PERMIT #420071825 DOES NOT MEET D.O.B. CODE SPECIFICATIONS. OBSERVED SIDEWALK SH... | $2,400 | $0 | Oct 18, 2011 |
| Sep 1, 2009 | 34793943J | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. WORK NOTED: ON 3RD & 4TH FLRS ERECTED FULL HEIGHT PARTITIONS CREATED ARTIST STUDIOS. REMEDY: OBTAI... | $0 | $0 | May 4, 2010 |
| Sep 1, 2009 | 34793944L | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO DEPT OF BUILDINGS RECORDS. DOB'S RECORDS INDICATE PREMISES AS FACTORY. ILLEGAL OCCUPANCY NOTED:... | $1,200 | $0 | Oct 5, 2010 |
| May 18, 2009 | 34765340M | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE REQUIRED SIGNAGE & INFORMATION ON SIDEWALK SHED.NOTED:MISSING PERMIT #41057510 MISSING EXPIRATION ... | $0 | $0 | Feb 9, 2010 |
| Jan 26, 2009 | 38198770J | RESOLVE | CLASS - 3 | 98BB05.52B12.98BB05 PERFORM & FILE 5YR TEST 52B12 RESHACKLE ROPES | $200 | $0 | Mar 24, 2009 |
| Jan 26, 2009 | 38198771L | RESOLVE | CLASS - 3 | 98BB05.98BB05 PERFORM & FILE 5YR TEST | $200 | $0 | Mar 24, 2009 |
| Dec 26, 2008 | 34741185P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES IN THAT CONCRETELINTELS LOCATED ABOVE 2ND & 1ST FLRS ALONG 36 S... | $1,000 | $0 | Feb 17, 2009 |
| Aug 7, 2008 | 34693120K | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY @ REAR OF BLDG THERE IS AN EGRESS DOOR & STAIRWAY BEING COVERED UP W/... | $0 | $0 | Jun 16, 2009 |
| Aug 7, 2008 | 34693119N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES DEFECTS NOTED @ TIME OF INSPECTION THERE IS CONCRETE SPALLING OFF O... | $1,000 | $0 | Feb 17, 2009 |
| Aug 22, 2007 | 34591626K | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BLDG-HAZARDOUS.DEFECTS NOTED:THERE ARE NUMEROUS CRACKS THROUGHOUT THE BLDG FACADE.THERE ... | $800 | $0 | Dec 18, 2007 |
| Jan 3, 2007 | 32050240N | RESOLVE | Non-Hazardous | B4A/48B/50A/50B/50C/50D/.50A-NEED SUPPORT ON FLUE PIPE.50B-NEED BOILERROOM FOR BOILER W/24HR FIRE RATING.50C-INDUEER ... | $180 | $0 | Dec 11, 2007 |
| Jan 3, 2007 | 32050239X | RESOLVE | Non-Hazardous | B4A/9A/9B/44A/50A/.NOTE:9A-NO EVIDENCE OF R1 FORM BY LICENSED WELDER FOR WELDED REPAIR ON HANDLEHOLE.50A-SAFETY OR RE... | $180 | -$2,320 | Jul 17, 2007 |
| Dec 10, 2003 | 38143387Z | RESOLVE | Non-Hazardous | 25Q11,38Y02,55Y13,66Y02,39#10. 39-#-10-SECURE STEPS TO MOTOR ROOM | $0 | $0 | Jan 27, 2004 |
| Jul 29, 2003 | 32042154R | RESOLVE | Non-Hazardous | BQ9, 16, 38, 50A, 50B FUCTION VT BOILER NB63812 10PP, GAS 1992 INSTALLED 5/9/03 REPLACEMENT BOILER INSTALLED WITH NO ... | $12,500 | $0 | Sep 14, 2004 |
| Jul 29, 2003 | 32042156K | RESOLVE | Non-Hazardous | 18AB, 50A, 50B FUCTION VT BOILER NB60320 10HP GAS FIRED 1990 50A REPLACE EXISTING SECONDARY BLOW DOWN VALVE WITH A SL... | $180 | $0 | Dec 16, 2003 |
| Jul 29, 2003 | 32042155Z | RESOLVE | Non-Hazardous | 50A, 50B FUCTION VT BOILER NB53854 15HP GAS FIRED 1988 50A REARRANGE BLOWDOWN VALVE ON THE BOILER PRIMARY VALVE SHOWE... | $0 | $0 | Sep 16, 2003 |