ECB violations

35 Street, Queens • Block 00377 • Lot 0013

67 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Mar 9, 2026 39179637N ACTIVE CLASS - 1 FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED IN MAIN ELECTRICAL ROOM IN BASE... $24,000 $24,000 May 19, 2026
Mar 9, 2026 39179638P ACTIVE CLASS - 1 MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED IN MAIN ELECTRICAL ROOM THERE WAS WATER ... $8,000 $8,000 May 19, 2026
Mar 9, 2026 39179639R ACTIVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... $8,000 $8,000 May 19, 2026
Mar 9, 2026 39179690M ACTIVE CLASS - 1 OBSERVED IN THE BASEMENT WASTE AND GAS LINES PRESENT IN THE DEDICATED ELECTRICAL ROOM. WATER LEAKED FROM CELLING ONTO... $12,500 $12,500 May 19, 2026
Mar 9, 2026 39179691Y ACTIVE CLASS - 1 OBSERVED GROUND FLOOR SPRINKLER HEAD OBSTRUCTED. IN BASEMENT SPRINKLER HEADS MISSING CAPS, SPRINKLER SYSTEM TO CAFE I... $12,500 $12,500 May 19, 2026
Mar 9, 2026 39179689P ACTIVE CLASS - 1 OBSERVED IN HOT WATER HEATER ROOMS ON FLOORS 2 THROUGH 5 IMPROPER HOT WATER HEATERS EXHAUST PIPING. ON 5 FLOOR NO TEM... $12,500 $12,500 May 19, 2026
Mar 9, 2026 39179600J ACTIVE CLASS - 1 CLASS 1: FIREFIGHTER SERVICE PHASE I INOPERATIVE - NO ELEVATOR RECALL, KEY CYLINDER ROTATES 360, REPAIR AND REQUEST R... $6,250 $6,250 May 19, 2026
Mar 9, 2026 39179601L ACTIVE CLASS - 1 CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-9... $6,250 $6,250 May 19, 2026
Mar 9, 2026 39179602N ACTIVE CLASS - 2 CLASS 2: EMERGENCY PHONE INOPERATIVE, PROVIDE 24-HOUR 2-WAY COMMUNICATION SERVICE. IN-CAR POSITION INDICATOR INOPERAT... $3,125 $3,125 May 19, 2026
Sep 24, 2024 39125629J RESOLVE CLASS - 2 CORRECT CAR FROM RE-LEVELING. CORRECT CAR FROM SCRAPING ON THE LOWER LANDING. $0 $0 Feb 4, 2025
Sep 24, 2024 39125630R RESOLVE CLASS - 1 : FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON IN... $1,250 $1,250 Jul 15, 2025
Sep 24, 2024 39126199N RESOLVE CLASS - 2 OBSERVED EXCESSIVE COMBUSTIBLE STORAGE IN THE GAS METER ROOM. AS PER APPENDIX E 3 OF THE FGC GAS METER ROOMS, WHEN PR... $310 $310 Dec 10, 2024
Sep 24, 2024 39125696J RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $625 $625 Aug 19, 2025
Sep 24, 2024 39125697L RESOLVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING. NON SELF CLOSING DOORS LOCATED IN UTILITY ROOMS THROUGHOUT BUILDING. POTENTIAL FIRE HAZAR... $312 $312 Aug 19, 2025
Sep 24, 2024 39125631Z RESOLVE CLASS - 2 IN-CAR ALARM INOPERATIVE. IN-CAR EMERGENCY LIGHTING INOPERATIVE. $625 $625 Sep 16, 2025
Sep 24, 2024 39126197J RESOLVE CLASS - 1 OBSERVED RUSTED AND CORRODE GAS PIPING TO HVACS AT ROOF LEVEL. AS PER 404.11 OF THE FGC PROTECTION AGAINST CORROSION.... $1,250 $1,250 May 27, 2025
Sep 24, 2024 39126198L RESOLVE CLASS - 2 OBSERVED INCORRECT EXHAUST PIPING TO ALL OF THE WATER HEATERS THROUGHOUT BUILDING (EXCEPT 1 IN THE MECHANICAL ROOM ON... $312 $312 May 27, 2025
Sep 24, 2024 39126211R RESOLVE CLASS - 1 I OBSERVED ON ALL FLOORS IN THE HALLWAYS AND COMMON AREAS THE FAILURE TO PROVIDE TAMPER RESISTANT RECEPTACLES AS REQU... $400 $400 May 27, 2025
Sep 24, 2024 39126212Z RESOLVE CLASS - 1 I OBSERVED IN ALL ELECTRICAL CLOSETS AND THE MAIN ELECTRICAL ROOM EXCESSIVE STORAGE OF MATERIALS, BUILDING EQUIPMENT,... $1,250 $1,250 May 27, 2025
Sep 24, 2024 39126213K RESOLVE CLASS - 1 I OBSERVED ON ALL FLOORS THE MECHANICAL ROOMS ON THE A & B SIDES, THE FAILURE TO INSTALL REMOTE SHUT DOWN AT THE POIN... $2,500 $2,500 May 27, 2025
Sep 24, 2024 39126210P RESOLVE CLASS - 2 I OBSERVED THE INSTALLATION OF AN ELECTRIC HEATER IN THE 4TH FLOOR STAIRWAY WITH NO SERVICE DISCONNECT WITHIN 5 FEET ... $0 $0 May 27, 2025
Sep 24, 2024 39126214M RESOLVE CLASS - 1 I OBSERVED ON ALL FLOORS THE INSTALLATION OF DATA WIRING AND EQUIPMENT, ELECTRICAL CLOSETS ARE DEDICATED TO ELECTRICA... $0 $0 May 27, 2025
Sep 24, 2024 39125698N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED EXCESSIVE CRACK LOCATED BENEATH STAIRCASE IN THE ELEC... $1,250 $0 Feb 4, 2025
Mar 21, 2013 34984271H RESOLVE CLASS - 2 RCNY REFERENCE STANDARD#5. FAILURE TO ADHERE TO REFERENCE STANDARD#5 OF NYC BUILDING CODE FOR SUSPENDED CEILING (DROP... $0 $0 May 7, 2013
Aug 9, 2012 34948877Y RESOLVE CLASS - 1 SEC. 3303.11 FAILURE TO MAINTAIN (OR TO PROVIDE ADEQUATE ALTERNATIVES TO) REQUIRED EGRESS DURING ALTERATION WORK TO E... $1,600 $0 Jan 29, 2013
Aug 9, 2012 34948876M RESOLVE CLASS - 1 OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BUILDING DEPT RECORDS. DURING INSPECTION IT WAS SEEN THAT SLEEP Q... $2,400 $0 Sep 25, 2012
Jul 23, 2012 34959095N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT. MANNER "INOPERABLE SPRINKLER SYSTEM" AT THE TIME OF INSPECTION I OBSERVED... $1,000 $0 Sep 11, 2012
Jul 23, 2012 34935048Y RESOLVE CLASS - 2 FULL SWO - ISSUED PURSUANT TO 28-207.2 AND POSTED AT PREMISES. WORK W/O A PERMIT. (SPRINKLER SYSTEM REMOVED FROM 2,3,... $800 $0 Sep 11, 2012
Jul 19, 2012 34956552X RESOLVE CLASS - 2 FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. AT 3RD FLR 1 WORKER SMOKING INSIDE B... $1,200 $0 Nov 13, 2012
Oct 19, 2011 34897812X RESOLVE CLASS - 1 3307.6.5 CONSTRUCTION OF SIDEWALK SHED UNLESS THE TOP DECK OF THE SIDEWALK SHED IS BUILT SOLIDLY AGAINST THE FACE OF ... $4,000 $0 Mar 20, 2012
Oct 19, 2011 34897811Y RESOLVE CLASS - 2 SIDEWALK SHED DOES NOT MEET CODE SPECIFICATION NOTED AT EXP #3 APPX 10FT OF PARAPET IS LOOSE BULKING TOWARDS STREET F... $2,400 $0 Mar 20, 2012
Aug 28, 2010 34871859H RESOLVE CLASS - 1 UNLAWFUL ACTS.FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER.RESPONDENT FAILED TO CORRECT THE CONDITIONS CITED ON ... $2,400 $0 Sep 13, 2011
Apr 5, 2010 34840099M RESOLVE CLASS - 1 FAILURE TO COMPLY W/COMM'S ORDER TO CORRECT VIO #34818633M FOR WORK W/O PERMIT @ 4TH FLR, SUBDIVIDED BY INSTALLED FUL... $2,400 $0 Oct 5, 2010
Nov 5, 2009 34818633M RESOLVE CLASS - 1 WORK W/O A PERMIT - WORK NOTED: AT 4TH FLR FACTORY. FULL HEIGHT SHEET ROCK PARTITIONS ERECTED FROM (FINISH) FLR THROU... $1,600 $0 Oct 5, 2010
Sep 17, 2009 34804007H RESOLVE CLASS - 2 SIDEWALK SHED AT EXP 1 ERECTED UNDER PERMIT #420071825 DOES NOT MEET D.O.B. CODE SPECIFICATIONS. OBSERVED SIDEWALK SH... $2,400 $0 Oct 18, 2011
Sep 1, 2009 34793943J RESOLVE CLASS - 1 WORK W/O A PERMIT. WORK NOTED: ON 3RD & 4TH FLRS ERECTED FULL HEIGHT PARTITIONS CREATED ARTIST STUDIOS. REMEDY: OBTAI... $0 $0 May 4, 2010
Sep 1, 2009 34793944L RESOLVE CLASS - 2 OCCUPANCY CONTRARY TO DEPT OF BUILDINGS RECORDS. DOB'S RECORDS INDICATE PREMISES AS FACTORY. ILLEGAL OCCUPANCY NOTED:... $1,200 $0 Oct 5, 2010
May 18, 2009 34765340M RESOLVE CLASS - 2 FAILURE TO PROVIDE REQUIRED SIGNAGE & INFORMATION ON SIDEWALK SHED.NOTED:MISSING PERMIT #41057510 MISSING EXPIRATION ... $0 $0 Feb 9, 2010
Jan 26, 2009 38198770J RESOLVE CLASS - 3 98BB05.52B12.98BB05 PERFORM & FILE 5YR TEST 52B12 RESHACKLE ROPES $200 $0 Mar 24, 2009
Jan 26, 2009 38198771L RESOLVE CLASS - 3 98BB05.98BB05 PERFORM & FILE 5YR TEST $200 $0 Mar 24, 2009
Dec 26, 2008 34741185P RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES IN THAT CONCRETELINTELS LOCATED ABOVE 2ND & 1ST FLRS ALONG 36 S... $1,000 $0 Feb 17, 2009
Aug 7, 2008 34693120K RESOLVE CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY @ REAR OF BLDG THERE IS AN EGRESS DOOR & STAIRWAY BEING COVERED UP W/... $0 $0 Jun 16, 2009
Aug 7, 2008 34693119N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES DEFECTS NOTED @ TIME OF INSPECTION THERE IS CONCRETE SPALLING OFF O... $1,000 $0 Feb 17, 2009
Aug 22, 2007 34591626K RESOLVE Hazardous FAILURE TO MAINTAIN EXTERIOR BLDG-HAZARDOUS.DEFECTS NOTED:THERE ARE NUMEROUS CRACKS THROUGHOUT THE BLDG FACADE.THERE ... $800 $0 Dec 18, 2007
Jan 3, 2007 32050240N RESOLVE Non-Hazardous B4A/48B/50A/50B/50C/50D/.50A-NEED SUPPORT ON FLUE PIPE.50B-NEED BOILERROOM FOR BOILER W/24HR FIRE RATING.50C-INDUEER ... $180 $0 Dec 11, 2007
Jan 3, 2007 32050239X RESOLVE Non-Hazardous B4A/9A/9B/44A/50A/.NOTE:9A-NO EVIDENCE OF R1 FORM BY LICENSED WELDER FOR WELDED REPAIR ON HANDLEHOLE.50A-SAFETY OR RE... $180 -$2,320 Jul 17, 2007
Dec 10, 2003 38143387Z RESOLVE Non-Hazardous 25Q11,38Y02,55Y13,66Y02,39#10. 39-#-10-SECURE STEPS TO MOTOR ROOM $0 $0 Jan 27, 2004
Jul 29, 2003 32042154R RESOLVE Non-Hazardous BQ9, 16, 38, 50A, 50B FUCTION VT BOILER NB63812 10PP, GAS 1992 INSTALLED 5/9/03 REPLACEMENT BOILER INSTALLED WITH NO ... $12,500 $0 Sep 14, 2004
Jul 29, 2003 32042156K RESOLVE Non-Hazardous 18AB, 50A, 50B FUCTION VT BOILER NB60320 10HP GAS FIRED 1990 50A REPLACE EXISTING SECONDARY BLOW DOWN VALVE WITH A SL... $180 $0 Dec 16, 2003
Jul 29, 2003 32042155Z RESOLVE Non-Hazardous 50A, 50B FUCTION VT BOILER NB53854 15HP GAS FIRED 1988 50A REARRANGE BLOWDOWN VALVE ON THE BOILER PRIMARY VALVE SHOWE... $0 $0 Sep 16, 2003