ECB violations
30-01 40 Avenue, Queens • Block 00400 • Lot 0001
34 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 26, 2026 | 39193909Z | RESOLVE | CLASS - 1 | ATOI OBSERVED OBSTRUCTED SPRINKLER HEADS THROUGHOUT BUILDING. WHICH ARE PAINTED TO CEILINGS. PER FGC 903.3.3 OBSTRUCT... | $2,500 | $2,500 | Sep 1, 2026 |
| Jun 26, 2026 | 39193896Z | ACTIVE | CLASS - 1 | CLASS 1 C/U: FIREFIGHTER SERVICE PHASE I INOPERATIVE AS PER ASME A17.1/CSA B44. THIS REMOVES REQUIRED FIRE SERVICE CO... | $1,250 | $1,270 | Sep 1, 2026 |
| Jun 26, 2026 | 39193940R | ACTIVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE PBX / IT RM INSTALLATION OF HUNG A/C BLOWER, IN STAIRWAY A AND B NE... | $2,500 | $2,500 | Sep 1, 2026 |
| Nov 7, 2022 | 39073591L | RESOLVE | CLASS - 2 | I OBSERVED IN DOB RECORDS NO COMPLIANCE OF VIOLATIONS 39064351H ISSUED ON 06/17/2022 AND VIOLATIONS 39047096P AND 390... | $1,250 | $0 | Apr 4, 2023 |
| Nov 7, 2022 | 39073590J | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOFTOP 4 GFCI OUTLETS INOPERABLE, NO REMOTE SHUTDOWN SWITCH FOR THE GAS FIRED SYSTEMS IN THE MECHA... | $2,000 | $0 | Aug 22, 2023 |
| Nov 7, 2022 | 39073583L | RESOLVE | CLASS - 2 | OBSERVED: EXISTING EMERGENCY LIGHT AT 4TH FL, STAIR A, 3RD FL STAIR A, 2ND FL STAIR A&B, FIRST FL STAIR A & CELLAR LE... | $1,563 | $0 | Apr 4, 2023 |
| Nov 7, 2022 | 39073592N | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP MECHANICAL ROOM AND THE IN THE MAIN ELECTRICAL ROOM THE USE OF ROMEX WIRING FROM THE AQUAST... | $2,400 | $0 | Aug 22, 2023 |
| Nov 7, 2022 | 39073589M | RESOLVE | CLASS - 2 | I OBSERVED IN THE 3RD FLOOR ELECTRICAL CLOSET THE INSTALLATION OF A NEW ELECTRICAL PANEL FEEDER CONDUCTORS AND BRANCH... | $800 | $0 | Aug 22, 2023 |
| Nov 7, 2022 | 39073546M | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). | $1,250 | $0 | Dec 27, 2022 |
| Jun 17, 2022 | 39064350X | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP MECHANICAL ROOM GAS FIRED WATER HEATERS WITH NO REMOTE SHUT-DOWN INSTALLED AT THE POINT OF ... | $3,125 | $0 | Aug 2, 2022 |
| Jun 17, 2022 | 39064351H | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP MECHANICAL ROOM BX CABLES UNSUPPORTED AND ALONG THE ROOFTOP PARAPET WALL FLEXIBLE METAL RAC... | $4,000 | $0 | Aug 2, 2022 |
| Apr 21, 2022 | 39060748H | RESOLVE | CLASS - 2 | I OBSERVED EXCESSIVE COMBUSTIBLE STORAGE IN THE MECHANICAL ROOM LOCATED ON ROOF. NO STORAGE SHALL BE KEPT IN THE MECH... | $625 | $0 | Jun 7, 2022 |
| Apr 21, 2022 | 39060747X | RESOLVE | CLASS - 2 | GAS METER ROOM LOCATED IN THE BASEMENT IMPROPERLY VENTED. GAS METER ROOM IS BEING VENTED INTO 2 OTHER ROOMS. HOWEVER,... | $312 | $0 | Jan 31, 2023 |
| Apr 21, 2022 | 35651073H | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.OBSERVED AT 3RD FLOOR STAIRWAY B DOOR,2ND FLOOR STAIRWAY A,DOOR AT FIRST FLOOR EXTERIOR DO... | $625 | $0 | Aug 16, 2022 |
| Apr 21, 2022 | 35651074J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER ... | $625 | $0 | Aug 16, 2022 |
| Apr 21, 2022 | 35654850R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.PROVIDE REQUIREDCORRIDOR WIDTH PER BC1016.2;27-369.OBSERVED AT ... | $625 | $0 | Jul 19, 2022 |
| Sep 7, 2021 | 35635951M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN COMPLIANT MANNER.I OBSERVED IN BSMT1 CELLAR FLEXIBLE DUCT HOSE INSTALLED THRU ELECTRICAL ... | $625 | $0 | Apr 19, 2022 |
| Sep 7, 2021 | 39047097R | RESOLVE | CLASS - 2 | I OBSERVED ON THE 5TH , 3RD FLOOR CLOSETS AND MAIN ELECTRICAL ROOM EXCESSIVE STORAGE OF MATERIALS NOT RELATED TO ELEC... | $2,000 | $0 | Dec 28, 2021 |
| Sep 7, 2021 | 35592060L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER.I OBSERVED IN BASEMENT/CELLAR NEWLY INSTALLED DUCTWORK SPANNING... | $0 | $0 | Dec 7, 2021 |
| Sep 7, 2021 | 39047096P | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOFTOP THE IMPROPER USE OF A YELLOW FLEXIBLE EXTENSION CORD AS PERMANENT WIRING TO A DOWN-LIGHT. E... | $2,000 | $0 | Dec 28, 2021 |
| Aug 10, 2021 | 39045787P | RESOLVE | CLASS - 1 | EXCESSIVE OIL LEAK IN THE PIT PERFORM NECESSARY REPAIR FAILED DRIFT TEST (CU). BETWEEN LOBBY FLOOR AND FIRST FLOOR TH... | $1,280 | $0 | Sep 28, 2021 |
| Jul 27, 2018 | 35337013K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIO# 35311611P ISSUED ON 2/15/18 & TO FILE A C OF ... | $3,125 | $0 | Sep 25, 2018 |
| May 22, 2018 | 35338931Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/COMM'S ORDER CONTAINED IN SUMM/VIO#35311611P ISSUED ON 02/15/18 AND TO FILE A COFC PURSUANT TO 28... | $3,125 | $0 | Jul 10, 2018 |
| Mar 7, 2018 | 38261418J | RESOLVE | CLASS - 1 | CU-05A10F,CU-05A10R; 42X10CU 05A10-FRONT AND REAR DOOR ZONE RESTRICTOR IS NOT OPERATIVE; THIS IS A SAFETY DEVICE. 42X... | $1,250 | $0 | Apr 24, 2018 |
| Feb 15, 2018 | 35284325N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35297826Y ISSUED ON 01/03/18 & TO FIL... | $2,000 | $0 | Apr 3, 2018 |
| Feb 15, 2018 | 35311611P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED @ FIRE DEPARTMENT CHECK VALVE,BALL DRIP INSTALLED IN V... | $10,000 | $0 | Apr 3, 2018 |
| Feb 2, 2018 | 38260954Z | RESOLVE | CLASS - 2 | 2X10 ALARM SYSTEM INOPERATIVE REPAIR | $250 | $0 | Mar 20, 2018 |
| Jan 3, 2018 | 35297828H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED BALL DRIP ON THE FIRE DEPT CHECK VALVE INSTALLED IN THE V... | $2,500 | $0 | Feb 20, 2018 |
| Jan 3, 2018 | 35297827X | RESOLVE | CLASS - 1 | SEC: FGC 403.8. UNPAINTED GAS PIPING NOT PROTECTED FROM THE ELEMENTS & CORROSION. OBSERVED ON ROOF GAS SUPPLY PIPING ... | $1,630 | $0 | Feb 20, 2018 |
| Jan 3, 2018 | 35297449H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTED: OBSERVED THROUGHOUT ROOF @ VARIOUS LOCATIONS, LOOSE, DETACH... | $530 | $0 | Feb 20, 2018 |
| Jan 3, 2018 | 35311255H | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE /MAINTAIN ACCESS/WORK SPACE ABOUT ELECTRICAL EQUIP MENT.OBSERVED IN LAUNDRY ROOM SERVICE SWITCHES ... | $530 | $0 | Feb 20, 2018 |
| Jan 3, 2018 | 35297826Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED EXCESSIVE STORAGE IN MECHANICAL ROOM LOCATED @ ROOF LEVEL... | $1,030 | $0 | Feb 20, 2018 |
| May 20, 2011 | 38216387N | RESOLVE | CLASS - 2 | 02X10 67X10. 02X10-ALARM BELL INOPERATIVE (ALSO W/STOP SWITCH). 67X10-IN CAR EMERGENCY PHONE INOPERATIVE. | $1,250 | -$1,250 | Jul 5, 2011 |
| Nov 17, 2009 | 38204567M | RESOLVE | CLASS - 2 | 40B7.40B FAN IN MACHINE RM ON BUT NOT TAKING FMES OUT | $250 | $0 | Jan 12, 2010 |