ECB violations
12 Street, Queens • Block 00472 • Lot 0642
31 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 3, 2025 | 39159089N | RESOLVE | CLASS - 2 | OBSERVED ON THE ROOF FIRE PUMP GAGE IS READING ALMOST AT ZERO. ON THE 9TH FLOOR IN MECHANICAL ROOM HOT WATER HEATER E... | $0 | $0 | Nov 18, 2025 |
| Sep 11, 2024 | 39124567Z | RESOLVE | CLASS - 1 | GAS LEAK FOUND ON ELBOW FITTING ON GAS PIPE. CON-ED TECH FOUND THE LEAK AND SHUT THE GAS TO THE APPLIANCE. AS PER 102... | $1,250 | $0 | Dec 31, 2024 |
| Sep 11, 2024 | 39124564N | RESOLVE | CLASS - 1 | OBSERVED IMPROPER VENTILATION IN THE MECHANICAL ROOM LOCATED IN THE CELLAR. THE MECHANICAL ROOM WHICH HOUSES A GAS FI... | $1,280 | $0 | Nov 19, 2024 |
| Sep 11, 2024 | 39124536X | RESOLVE | CLASS - 1 | I OBSERVED IN THE HALLWAYS THE FAILURE TO INSTALL TAMPER RESISTANT OUTLETS AS REQUIRED BY LL 39/2015. THIS SI AN IMME... | $1,630 | $0 | Nov 19, 2024 |
| Sep 11, 2024 | 39124537H | RESOLVE | CLASS - 2 | I OBSERVED ON THE 9TH AND 1ST FLOORS THE FAILURE TO INSTALL A REMOTE SHUTDOWN FOR THE GASFIRED UNITS IN THE MECHANICA... | $0 | $0 | Nov 19, 2024 |
| Sep 11, 2024 | 39124566R | ACTIVE | CLASS - 2 | OBSERVED THROUGHOUT BUILDING TEMPORARY CAPS( RED) ON THE STANDPIPE HOSE VALVE. AS PER 3308 OF THE NEW YORK FIRE CODE ... | $0 | $0 | Dec 31, 2024 |
| Sep 11, 2024 | 39124540Z | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF LEVEL IN THE ELEVATOR AND FIRE PUMP ROOMS THE UNPERMITTED USE OF EMT THROUGH CONCRETE. AS PER ... | $800 | $0 | Dec 31, 2024 |
| Sep 11, 2024 | 39124569M | RESOLVE | CLASS - 2 | OBSERVED ACTIVE WATER LEAK IN THE WATER METER ROOM LOCATED IN CELLAR, AS PER 102.3 OF THE PLUMBING CODE INSTALLATIONS... | $0 | $0 | Nov 19, 2024 |
| Sep 11, 2024 | 39124568K | RESOLVE | CLASS - 1 | OBSERVED EXCESSIVE COMBUSTIBLE STORAGE IN THE MECHANICAL ROOM LOCATED ON THE 9TH FLOOR WHICH HOUSES 3 GAS FIRED WATER... | $1,250 | $0 | Dec 31, 2024 |
| Sep 11, 2024 | 39124528X | ACTIVE | CLASS - 2 | UNPERMITTED FOAM USED AT FIRE-STOP TO SEAL HOLE PENETRATIONS LOCATED THROUGHOUT BUILDING., PROVIDE/MAINTAIN FIRE STOP... | $0 | $0 | Dec 31, 2024 |
| Sep 11, 2024 | 39124538J | RESOLVE | CLASS - 1 | I OBSERVED THE MAIN ELECTRICAL ROOM WITH EXCESSIVE STORAGE OF FURNITURE, BUILDING EQUIPMENT, APPLIANCES AND MATERIALS... | $1,200 | $0 | Dec 31, 2024 |
| Apr 12, 2021 | 39039197Y | RESOLVE | CLASS - 1 | I OBSERVED ON THE ROOF AREA WHERE THE GRAVITY TANK IS INSTALLED. INSIDE THE TANK. UNAPPROVE MATERIAL INSTALLED A BAG ... | $3,125 | $0 | Jun 1, 2021 |
| Feb 26, 2020 | 39018330L | RESOLVE | CLASS - 2 | THE EXTERIOR WALLS ON EXPOSURES #1 & #3 FROM 1ST. TO 9TH. FLOOR WERE INSTALLED WITHOUT 2" RIGID INSULATION CONTRARY T... | $3,125 | $0 | Nov 24, 2020 |
| Jul 18, 2019 | 35444239R | RESOLVE | CLASS - 2 | FAILURE TO SAFEGUARD ALL PERSONS AND PROPERTIES AFFECTED BY CONSTRUC TION OPERATIONS. AT TIME OF INSPECTION ON A 9STO... | $5,000 | $0 | Oct 1, 2019 |
| May 23, 2019 | 35421424R | RESOLVE | CLASS - 1 | WORK NOT DOES NOT CONFORM TO APPROVED DOCUMENTS/PLANS. AT THE TIME OF INSPECTION OF A 9 STORY BUILDING ACTIVE JOB SIT... | $2,500 | $0 | Aug 13, 2019 |
| Apr 20, 2019 | 35405175P | RESOLVE | CLASS - 1 | BC-3303.8 STANDPIPE NOT IN STATE OF READINESS. AT TIME OF INSPECTION ON AN ACTIVE JOBSITE OF A 9 STORY BUILDING,TOPPE... | $2,500 | $0 | Aug 13, 2019 |
| Jan 17, 2019 | 35381921Y | RESOLVE | CLASS - 2 | JOBSITE FENCE NOT CONSTRUCTED OR MAINTAINED PURSUANT TO SUBSECTION. ATTHE TIME OF MY INSPECTION OF A PROPOSED 9 STORY... | $0 | $0 | Mar 26, 2019 |
| Jan 17, 2019 | 35381922X | RESOLVE | CLASS - 2 | (PB)SIGNS. SIDEWALK SHED PARAPET PANEL SIGN NOT PROVIDED OR NOT COMPLIANCE W/ SECTION. NOTED:AT TIME OF INSPECTION I ... | $0 | $0 | Mar 26, 2019 |
| Jan 17, 2019 | 35381923H | RESOLVE | CLASS - 2 | DAILY INSPECTION REPORT. A WRITTEN RECORD OF SUCH INSPECTIONS SHALL BEMAINTAINED BY THE CONTRACTOR. NOTED:AT TIME OF ... | $0 | $0 | Aug 13, 2019 |
| Jan 11, 2019 | 35380886N | RESOLVE | CLASS - 1 | BC3305.3.6.1.1 SHORES. AT TIME OF INSPECTION, I OBSERVED SHORES/RESHORES AT THE PERIMETER OF THE JOBSITE NOT ADEQUATE... | $2,500 | $0 | Apr 16, 2019 |
| Jan 11, 2019 | 35380884J | RESOLVE | CLASS - 1 | WORK CONTRARY TO DRAWINGS. AT TIME OF INSPECTION, I OBSERVED SHEAR WALL PLATFORMS LOCATED AT EXP #2 & #4 EXTERIOR. UP... | $2,500 | $0 | Apr 16, 2019 |
| Jan 11, 2019 | 35380885L | RESOLVE | CLASS - 1 | FAILURE TO INSTITUTE/MAINTAIN SAFETY EQUIPMENT MEASURES OR TEMPORARY CONSTRUCTION GUARDRAILS/NO TOE BOARDS. AT TIME O... | $2,500 | $0 | Apr 16, 2019 |
| Jan 11, 2019 | 35380889Z | RESOLVE | CLASS - 1 | BC3301.4 INSPECTION OF TEMPORARY CONSTRUCTION EQUIPMENT (SAFETY STRAP). AT TIME OF INSPECTION, I OBSERVED AN ACTIVE C... | $2,500 | $0 | Apr 16, 2019 |
| Jan 11, 2019 | 35380887P | RESOLVE | CLASS - 1 | NO DESIGN DRAWINGS. AT TIME OF INSPECTION, I OBSERVED TEMPORARY PLATFORMS LOCATED ON THE ELEVATOR SHAFTS. UPON REQUES... | $2,500 | $0 | Apr 16, 2019 |
| Jan 11, 2019 | 35380890X | RESOLVE | CLASS - 1 | CONSTRUCTION SUPERINTENDENT FAILED TO PERFORM DUTIES AS PER RULE. AT TIME OF INSPECTION I OBSERVED ON CONSTRUCTION SI... | $0 | $0 | Apr 16, 2019 |
| Jan 11, 2019 | 35380888R | RESOLVE | CLASS - 2 | FAILED TO PERFORM PROPER CONCRETE WASHOUT. AT TIME OF INSPECTION, I OBSERVED EXCESSIVE CONCRETE WASHOUT RUN-OFF ON TH... | $0 | $0 | Aug 13, 2019 |
| Sep 5, 2018 | 35353725Z | RESOLVE | CLASS - 1 | FAILURE TO MONITOR ADJOINING STRUCTURES FOR MOVEMENT IN ALL DIRECTIOINS DURING EXCAVATION UNDERPINING ACTIVITY.AT THE... | $2,500 | $0 | Dec 18, 2018 |
| Sep 5, 2018 | 35353726K | RESOLVE | CLASS - 2 | CONSTRUCTION SUPERINTENDENT FAILED TO PERFORM DUTIES AS PER CODE;AT THE TIME OF INSPECTION THE FOLLOWING WAS OBSERVED... | $2,500 | $0 | Dec 18, 2018 |
| Sep 5, 2018 | 35316048H | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE PROTECTION AT SIDE OF EXCAVATION.AT THE TIME OF INSPECTION A 4' TO 8'FT DEEP EXCAVATION WAS OBSERV... | $5,000 | $0 | Dec 18, 2018 |
| Sep 5, 2018 | 35316049J | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONFORM TO THE APPROVED SOE & FO PLAN.THE APPROVED SOE PLAN SHOWS SHORING/PILES WIT... | $625 | $0 | Dec 18, 2018 |
| Sep 30, 2017 | 35289249N | RESOLVE | CLASS - 1 | WORK WITHOUT PREMIT.AT THE TIME OF INSPECTION OBSERVED SITE HAD JOB FENCE UP FENCE WAS BLUE IN COLOR HAD NO VIEWING P... | $4,000 | $0 | Apr 24, 2018 |