ECB violations
21-01-21-33 31 Drive, Queens • Block 00553 • Lot 0001
108 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jan 28, 2015 | 35119216P | RESOLVE | CLASS - 2 | REISSUE #35084626K FAILURE TO MAINTAIN.NOTE:HOLES AROUND PIPE PENETRATION @ CEILING AND WALL NEXT TO PANEL(NEAR FLOOR... | $0 | $0 | Mar 17, 2015 |
| Jan 28, 2015 | 35119215N | RESOLVE | CLASS - 2 | REISSUE #35084628Y FAILURE TO MAINTAIN.WATER PENETRATION @ ELECTRIC METER ROOM + BOILER ROOM.REM:MAINAIN AS PER CODE | $0 | $0 | Mar 17, 2015 |
| Jan 15, 2014 | 35084628Y | RESOLVE | CLASS - 2 | REISSUE 35023849Z. WATER PENETRATION AT CELLAR INTO ELECTRICAL PANEL ROOM,BOILER PIT,CORROSION NOTED AT BASE OF ELECT... | $0 | $0 | May 6, 2014 |
| Jan 15, 2014 | 35084625Z | RESOLVE | CLASS - 2 | 27-371(B) REISSUE 35023852J.PLEXI VISION PANELS NOTED THROUGHOUT STAIRCASE DOORS ON ALL LEVELS.REM: REPLACE WITH FIRE... | $0 | $0 | May 6, 2014 |
| Jan 15, 2014 | 35084627M | RESOLVE | CLASS - 2 | REISSUE 35023850X.DEFECTIVE DOORS NOTED 5FL STAIR F,G 4FL STAIR H,E 1FL CAFETERIA DOORS(WESTSIDE) ALL DOORS NOT CLOSI... | $0 | $0 | May 6, 2014 |
| Jan 15, 2014 | 35084626K | RESOLVE | CLASS - 2 | REISSUE 35023851H. MISSING FIRE STOPPING AT ELECTRICAL METER ROOM CEILING 6"X12"INCH PIPE PENETRATION.REM: SEAL AROUN... | $0 | $0 | May 6, 2014 |
| Jul 18, 2013 | 35023850X | RESOLVE | CLASS - 2 | DOORS NOT CLOSING. AT 4TH FL STWY H,5TH FL STWY F,G,DOOR ARE RACKED TOFRAME & DRAG ON FLOOR REMAINING OPEN. REMEDY: R... | $0 | $0 | Sep 17, 2013 |
| Jul 18, 2013 | 35023849Z | RESOLVE | CLASS - 2 | REISSUE #34941242Z WATER PENETRATION. AT BOILER PIT & ELECTRIC METER ROOM,THE CONCRETE SLAB & FOUNDATION HAVE BECOME ... | $0 | $0 | Sep 17, 2013 |
| Jul 18, 2013 | 35023851H | RESOLVE | CLASS - 2 | SEC. 712.3;27-345 MISSING FIRE STOPPING. AT ELECTRIC METER ROOM,APPROX 6"X12" PENETRATION IN CONCRETE CEILING W/CONDU... | $0 | $0 | Sep 17, 2013 |
| Jul 18, 2013 | 35023853L | RESOLVE | CLASS - 2 | SEC. 1006.1;27-542 DEFECTIVE EMERGENCY LIGHTING. AT 3RD FL GYM,BROKEN,IN OPERATIVE EMERGENCY LIGHTING ABOVE ILLUMINAT... | $0 | $0 | Sep 17, 2013 |
| Jul 18, 2013 | 35023852J | RESOLVE | CLASS - 2 | SEC. 27-371(B) PLEXI VISION PANELS. AT 4TH FL STWY H,5TH FL STWY F,G,H,THERMO PLASTER VISION PANELS INSTALLED IN FIRE... | $0 | $0 | Sep 17, 2013 |
| Mar 7, 2012 | 34941239H | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY. 12 CARS PARKED IN REAR SCHOOLYARD VIA LEGAL CURB CUT FOR TRASH DUMPSTER. NOTED STUDENTS PLAYING I... | $0 | $0 | May 22, 2012 |
| Mar 7, 2012 | 34941244M | RESOLVE | CLASS - 2 | PROHIBITED HARDWARE. AT MAIN ENTRY LOCKABLE DEAD BOLT INSTALLED ON VESTIBULE DOOR. AT AUDITORIUM LOBBY DOOR KICK STOP... | $0 | $0 | May 22, 2012 |
| Mar 7, 2012 | 34941242Z | RESOLVE | CLASS - 2 | WATER PENETRATION. AT CELLAR BOILER PIT & FURNITURE STORAGE ROOM ADJACENT TO ELECTRIC SERVICE,THE FOUNDATION SLAB HAS... | $0 | $0 | May 22, 2012 |
| Mar 7, 2012 | 34941245Y | RESOLVE | CLASS - 2 | SPALLING PLASTER SURFACE. AT AUDITORIUM STAGE CEILING SPALLING & CRUMBLING PLASTER SURFACE. REM:REPAIR PLASTER SURFACE. | $0 | $0 | May 22, 2012 |
| Mar 7, 2012 | 34941240P | RESOLVE | CLASS - 3 | REISSUE #34907940R DEFECTIVE METAL MESH CAGE. AT 3RD FLR GYM,THE METALMESH CAGE MOUNTS HAVE BECOME LOOSE FLR & CEILIN... | $0 | $0 | May 22, 2012 |
| Mar 7, 2012 | 34941241R | RESOLVE | CLASS - 2 | DEFECTIVE DOOR. AT 2ND FLR STAIRWAY E,THE FIREPROOF DOOR IS RACKED TO FRAME & JAMS SHUT REQUIRING EXTREME FORCE TO OP... | $0 | $0 | May 22, 2012 |
| Mar 7, 2012 | 34941243K | RESOLVE | CLASS - 2 | CRACKED GLAZED BRICK. AT 3RD FLR GYM WEST WALL CRACKED GLAZED BRICK COLUMN FLR TO CEILING UNDER GIRDER. REM:REPAIR GL... | $0 | $0 | May 22, 2012 |
| Dec 15, 2011 | 34944705J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION I OBSERVED 5 COOKING EQUIPMENTS IN U... | $0 | $0 | Mar 6, 2012 |
| Apr 14, 2011 | 34907939J | RESOLVE | CLASS - 2 | DEFECTIVE WALL MOUNTS FOR EXIT LIGHTS. AT 4TH FLOOR OVER STAIRWAY DOORS D,F,& G,THE LIGHTED EXIT SIGNS HAVE WITH STRI... | $0 | $0 | Jun 14, 2011 |
| Apr 14, 2011 | 34907937X | RESOLVE | CLASS - 2 | ROOF DEFECTIVE. AT 2ND ROOM 200 & ADJACENT SECTION TO AUDITORIUM,THE ROOF ABOVE HAS BECOME POROUS ALLOWING PENETRATIO... | $0 | $0 | Jun 14, 2011 |
| Apr 14, 2011 | 34907933Z | RESOLVE | CLASS - 2 | REISSUE #34846309Z DEFECTIVE PLASTER SURFACE. THE PLASTER SURFACE IS CRACKED & SPALLING AT VARIOUS ROOMS ON 5TH FL,& ... | $0 | $0 | Jun 14, 2011 |
| Apr 14, 2011 | 34907934K | RESOLVE | CLASS - 2 | REISSUE #34846309Z DEFECTIVE DOORS. THE FIRE PROOF SELF CLOSING DOORS ARE RACKED & NOT SELF CLOSING PROPERLY AT. ALL ... | $0 | $0 | Jun 14, 2011 |
| Apr 14, 2011 | 34907940R | RESOLVE | CLASS - 3 | DEFECTIVE MESH CAGE (MOUNTS) AT GYM 3,THE MESH CAGE SECTIONS HAVE BECOME LOOSE IN FLOOR & CEILING MOUNTS AT ALL 12 CA... | $0 | $0 | Jun 14, 2011 |
| Apr 14, 2011 | 34907935M | RESOLVE | CLASS - 2 | REISSUE #34692959L DEFECTIVE ROOF & EXTERIOR WALLS. AT 5TH FL,MULTIPLE ROOMS HAVE MOISTURE PENETRATION FROM POROUS RO... | $0 | $0 | Jun 14, 2011 |
| Apr 14, 2011 | 34907936Y | RESOLVE | CLASS - 2 | DEFECTIVE DOOR. AT 3RD FL BETWEEN ROOMS 313 & 314,THE SMOKE DOOR IS RACKED,BENT WITH BENT & DISLODGED FRAME,CONDITION... | $0 | $0 | Jun 14, 2011 |
| Apr 14, 2011 | 34907938H | RESOLVE | CLASS - 2 | DEFECTIVE INTERIOR WALLS. AT STAIRWAY H BULKHEAD FAN ROOM,& VARIOUS CLASSROOMS 1E,514,INTERIOR WALLS HAVE CRACKED,LOO... | $0 | $0 | Jun 14, 2011 |
| May 12, 2010 | 34846309Z | RESOLVE | CLASS - 2 | REISSUE: 34692958J THE INTERIOR PLASTER ON THE WALLS & CEILING IS SPALLING & CRACKED LOCATED IN MULTIPLE ROOMS ON THE... | $0 | $0 | Sep 14, 2010 |
| May 12, 2010 | 34846308R | RESOLVE | CLASS - 2 | REISSUE: 34760736X THE CORRIDOR SMOKE DOORS & EXIT DOORS ARE DEFECTIVELOCATED ON THE 2ND,3RD & 4TH FL LEVEL. NOTED: D... | $0 | $0 | Sep 14, 2010 |
| Feb 9, 2009 | 34760738J | RESOLVE | CLASS - 2 | SEVERE DAMAGE TO FLOOR IN ROOM 301. APPROX 6X4 SECTION AFFECTED. 9X9 TILES MISSING & SUB FLOORING EXPOSED. REMEDY: MA... | $0 | $0 | May 12, 2009 |
| Feb 9, 2009 | 34760737H | RESOLVE | CLASS - 1 | HAZ. CEILING IN DANGER OF FALLING;ROOM 220, LOOSE & MISSING PLASTER, 2AREAS AFFECTED BOTH END CORNERS, ROOM OCCUPIED.... | $0 | $0 | May 12, 2009 |
| Feb 9, 2009 | 34760736X | RESOLVE | CLASS - 2 | REISSUE: 34692957H. DEFECTIVE DOORS. NOTED: 2 STAIRWAY DOOR ON 5TH FL DEFECTIVE & 4TH FL ALL STAIRWAY & 3,2 FLOORS AL... | $0 | $0 | May 12, 2009 |
| Jul 17, 2008 | 34692958J | RESOLVE | CLASS - 2 | REISSUE: 34592180J FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: PLASTER IS SPALLING AWAY FROM THE CE... | $0 | $0 | Sep 9, 2008 |
| Jul 17, 2008 | 34692959L | RESOLVE | CLASS - 2 | REISSUE: 34692957H FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCESNOTED: ROOF HAS BECOME POROUS AND ALLOW RAIN WA... | $0 | $0 | Sep 9, 2008 |
| Jul 17, 2008 | 34692957H | RESOLVE | CLASS - 2 | REISSUE: 34592181L FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED: CORRIDOR SMOKE DOORS ARE NOT SELF CLO... | $0 | $0 | Sep 9, 2008 |
| Aug 15, 2007 | 34592181L | RESOLVE | Hazardous | EXIT DOOR NOT SELF-CLOSING. 2ND FLOOR - END OF CORRIDOR DOOR BY ROOM 313 - FIRE/CORRIDOR DOOR BY ROOM 354. REMEDY: RE... | $0 | $0 | Nov 13, 2007 |
| Aug 15, 2007 | 34592179M | RESOLVE | Hazardous | REISSUE: 34467250N. FAILURE TO MAINTAIN - EXTERIOR. ROOF LEAKS WATER -CLASSROOM 501, 502, 506, 509, 511, 5TH FL GYM A... | $0 | $0 | Nov 13, 2007 |
| Aug 15, 2007 | 34592180J | RESOLVE | Hazardous | REISSUE #34393589N. FAILURE TO MAINTAIN - INTERIOR. WATER PENETRATING AT WALLS IN CLASSROOM 502, 503, 505, 507, 511, ... | $0 | $0 | Nov 13, 2007 |
| May 23, 2006 | 34393589N | RESOLVE | Non-Hazardous | REISSUE: 34266656M, 34467201R SPALLING PLASTER IN RM 265,502,503,503, 507,511,513,552,509, STAIR D. 5TH FL BEHIND RAD... | $0 | $0 | Aug 15, 2006 |
| May 23, 2006 | 34393590K | RESOLVE | Non-Hazardous | REISSUE: 34467202Z: 1ST FL CORRIDOR SMOKE DOORS(2) ARE MISSING @ EXIT 9. REMEDY: INSTALL DOORS. | $0 | $0 | Aug 15, 2006 |
| May 23, 2006 | 34393591M | RESOLVE | Non-Hazardous | REISSUE: 34467250N. ROOF LEAKS AT CLASS RMS 501, 502, 506, 511, 509, 5TH FL GYM AT DRAIN PIPE & OFFICE #560. REMEDY: ... | $0 | $0 | Aug 15, 2006 |
| May 23, 2006 | 34393592Y | RESOLVE | Non-Hazardous | WATER PENETRATION THROUGH EXTERIOR MASONRY WALLS AT VARIOUS LOCATIONS THROUGHOUT 5TH & 4TH FLOORS. REMEDY: STAL/REPOI... | $0 | $0 | Aug 15, 2006 |
| May 23, 2006 | 34393593X | RESOLVE | Non-Hazardous | DEFECTIVE MOTORIZED FRESH AIR INTAKE DAMPERS AT CELLAR BOILER ROOM. REMEDY: REPAIR/REPLACE ACTIVATORS. | $0 | $0 | Aug 15, 2006 |
| Mar 11, 2005 | 34467201R | RESOLVE | Hazardous | FAILURE TO MAINTAIN BLDG. DEFECTS NOTED: WATER PENETRATION AT WALLS IN CLASSROOMS: 502,503,505,507,511,513, & OFFICE ... | $0 | $0 | Aug 2, 2005 |
| Mar 11, 2005 | 34467250N | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING DEFECTS NOTED ROOD LEAKS AT CLASSROOMS 501,502,506,511,509,5 FLOOR GYM AT DRAIN PIPE & O... | $0 | $0 | Aug 2, 2005 |
| Mar 11, 2005 | 34467203K | RESOLVE | Non-Hazardous | EXIT PASSAGEWAY OR CORRIDOR REQUIRED WIDTH DECREASED BY OBSTRUCTION. NOTED: FIRST FLOOR AUDITORIUM, STAGE REAR CORRID... | $0 | $0 | Aug 2, 2005 |
| Mar 11, 2005 | 34467202Z | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BLDG. DEFECTS NOTED: FIRST FLOOR CORRIDOR SMOKE DOORS 2 ARE MISSING AT EXIT 9. REMEDY:MAINTAIN BL... | $0 | $0 | Aug 2, 2005 |
| Apr 9, 2002 | 34318927R | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING HAZARDOUS DEFECT IS LEAKY ROOF AT EXIT 8 BETWEEN 2 AND 3 RD FLOORS REMEDY MAINTAIN BUILDING | $0 | $0 | Jun 4, 2002 |
| Apr 9, 2002 | 34318926P | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING HAZARDOUS DEFECT IS LEAKY ROOF OVER ROOM 511 AND GYM REMEDY MAINTAIN BUILDING | $0 | $0 | Jun 4, 2002 |
| Jan 3, 2001 | 34266781L | RESOLVE | Non-Hazardous | FAILURE TO PRIVIDE PANIC HARDWARE IN PLACE OF ASSEMBLE UPON INSPECTION OF THE CAFETERIA/LIBRARY NO PANIC HARDWARE WAS... | $0 | $0 | Apr 10, 2001 |