ECB violations
30-05 30 Avenue, Queens • Block 00595 • Lot 0008
12 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 4, 2012 | 32071881X | RESOLVE | CLASS - 2 | 50A- FLUE PIPES ON ALL 4 BOILER SHOWS EARLY INDICATION OF CORROSION DUE TO CONDENSATE CONDITIONS. REMEDY: REPLACE ALL... | $500 | $0 | Oct 23, 2012 |
| Jul 23, 2012 | 32072026J | RESOLVE | CLASS - 1 | HIGH PRESSURE FULTON BOILER #PV45655 INSTALLED WITHOU PERMIT | $800 | $0 | Sep 14, 2012 |
| Aug 19, 2008 | 32060490P | RESOLVE | CLASS - 2 | 18A,18B,50A.50A-COMBUSTION SPILLAGE DUE TO DEFECTED FLUE PIPE INSTALLATION,RELOCATE FLUE PIPE TO NEW CHIMNEY TO ROOF ... | $500 | $0 | Sep 7, 2010 |
| Jan 17, 2007 | 32050635H | RESOLVE | Non-Hazardous | 18A,18B,48B,40,50A. 50A-MOVE HOT WATER HEATER TO GIVE CLEARANCE TO MAINTAIN & INSPECT CHIMNEY BASE. | $0 | $0 | Mar 13, 2007 |
| Jul 30, 2003 | 32042162R | RESOLVE | Non-Hazardous | 44A, 50A, 50B FUCTION VERT TBCP BCR NB44552 10HP OIL FIRED 1984 50A REARRANGE BLOW DOWN VALVERS ON BOILER PRIMARY VAL... | $180 | $0 | Sep 16, 2003 |
| Feb 2, 2001 | 32020531X | RESOLVE | Non-Hazardous | 8C 9B | $0 | $0 | Mar 20, 2001 |
| Jul 21, 2000 | 32019142Y | RESOLVE | Non-Hazardous | HAND HOLE SLEEVE CORRODED FLAME EXITING THE SLEEVE TP BE RENEWED AND SEALED GAS TIGHT. | $0 | $0 | Sep 5, 2000 |
| May 15, 1999 | 32017964Y | RESOLVE | Hazardous | 4A,19B. 4A-LOW WATER CUTOFF MISSING. 19B-MANUAL RESET MISSING. WEILMCLAIN-FHW-GAS-3L. | $400 | $0 | Jul 6, 1999 |
| May 15, 1999 | 32017961Z | RESOLVE | Hazardous | 4A,19B. 4A-LOW WATER CUTOFF MISSING. 19B-MANUAL RESET AQUASTAT MISSING. WEIL MCLAIN-GAS-FHW-2R. | $400 | $0 | Jul 6, 1999 |
| May 15, 1999 | 32017962K | RESOLVE | Hazardous | 4A,19B. 4A-LOW WATER CUTOFF MISSING. 19B-MANUAL RESET AQUASTAT MISSING. WEIL MCLAIN-GAS-FHW-2L. | $400 | $0 | Jul 6, 1999 |
| May 15, 1999 | 32017963M | RESOLVE | Hazardous | 4A,19B. 4A-LOW WATER CUTOFF MISSING. 19B-MANUAL RESET AQUASTAT MISSING. WEIL MCLAIN-FHW-GAS-3R. | $400 | $0 | Jul 6, 1999 |
| Aug 16, 1988 | 32000606N | RESOLVE | Hazardous | — | $150 | $0 | Oct 4, 1988 |