ECB violations
86-15-86-29 37 Avenue, Queens • Block 01460 • Lot 0034
31 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 26, 2026 | 35727325N | ACTIVE | CLASS - 2 | REISSUE #35717384Y DATE OF ISSUE: 04/28/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. CRACKS IN MAIN E... | $3,125 | $0 | May 15, 2026 |
| Mar 26, 2026 | 35727349H | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING PROPERLY. AT THE TIME OF INSPECTION, OBSERVED AND NOTED AT 1ST FLOOR EXIT-2 AND EXIT-3 DOO... | $625 | $0 | May 15, 2026 |
| Mar 26, 2026 | 35727326P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS P... | $1,250 | $0 | May 15, 2026 |
| Apr 28, 2025 | 35717384Y | ACTIVE | CLASS - 2 | REISSUE #35678871M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. CRACKS IN MAIN ENTRY DOORWAY. BASE OF DOOR... | $3,125 | $0 | May 27, 2025 |
| May 7, 2024 | 35678871M | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.CRACKS IN MATH DOOR WAY BASE OF DOOR FRAME RUSTING AND BASE OF ... | $625 | $0 | Jul 16, 2024 |
| Apr 26, 2017 | 35253380Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER USE OF PROHIBITED DOOR HARDWARE PER BC 1008-1.8;27-37. ILLEGAL KICK... | $0 | $0 | Sep 5, 2017 |
| Apr 8, 2015 | 35128137L | RESOLVE | CLASS - 2 | REISSUED VIOLATION #35027838L FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: WATER PENETRATION BLDG EN... | $0 | $0 | Jun 16, 2015 |
| Sep 5, 2014 | 35107490J | RESOLVE | CLASS - 2 | REISSUE 35027837J.NO ILLUMINATED EXIT SIGNAGE PROVIDED @ BOILER ROOM.REM:PROVIDE SIGNAGE. | $0 | $0 | Oct 28, 2014 |
| Sep 5, 2014 | 35107489M | RESOLVE | CLASS - 2 | REISSUE 35027838L.WATER PENETRATION THROUGHT ROOF &/OR FACADE HALLWAY CEILING OUTSIDE RM 402 & @ EXIT 2 CORRIDOR 1FL.... | $0 | $0 | Oct 28, 2014 |
| Jul 16, 2013 | 35027839N | RESOLVE | CLASS - 2 | CELLAR -GAS METER ROOM AREAWAY EXTERIOR SIDE OF GAS METER ROOM - STORAGE OF PLANS, 5 GALLON PLASTIC CONTAINERS, MISC ... | $0 | $0 | Sep 17, 2013 |
| Jul 16, 2013 | 35027838L | RESOLVE | CLASS - 2 | REISSUE 34901909L EXTERIOR ROOF AND BRICK FACADE HAS BECOME POROUS & ALLOWS RAIN WATER INTO BUILDING CAUSING INTERIOR... | $0 | $0 | Sep 17, 2013 |
| Jul 16, 2013 | 35027837J | RESOLVE | CLASS - 2 | REISSUE 34949619X MISSING EXIT SIGNS - BOILER ROOM CELLAR MISSING EXIT SIGNS NO ILLUMINATED EXIT SIGNS OR ANY EXIT SI... | $0 | $0 | Sep 17, 2013 |
| Mar 27, 2012 | 34949618Y | RESOLVE | CLASS - 2 | PARTIAL CORRIDOR OBSTRUCTION AT 1ST FLOOR PARTIAL OBSTRUCTION W/ BOOK CASES TABLES BOXES AND ROLLING CARTS REM: REMOV... | $0 | $0 | Jun 5, 2012 |
| Mar 27, 2012 | 34949619X | RESOLVE | CLASS - 2 | MISSING EXIT SIGNS. AT BOILER ROOM NO ILLUMINATED EXIT SIGNS OR ANY EXIT SIGNS. REM:PROVIDE EXIT SIGNS. | $0 | $0 | Jun 19, 2012 |
| Mar 3, 2011 | 34901909L | RESOLVE | CLASS - 2 | REISSUE: 34848012R, 34848011P. EXTERIOR ROOF AND BRICK FACADE HAS BECOME POROUS AND ALLOWING RAIN WATER INTO THE BLDG... | $0 | $0 | May 3, 2011 |
| May 14, 2010 | 34848013Z | RESOLVE | CLASS - 2 | SEC. 28-301.1 FAILURE TO MAINTAIN EGRESS CLEAR & UNOBSTRUCTED OBSERVED: 2ND FL MAIN CORRIDOR PARTIALLY OBSTRUCTED BY ... | $0 | $0 | Sep 14, 2010 |
| May 14, 2010 | 34848012R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN OBSERVED WATER PENETRATION FROM ROOF INTO RMS 406,407,MAIN CORRIDOR 4FL. REMEDY: MAINTAIN BUILDING. | $0 | $0 | Sep 14, 2010 |
| May 14, 2010 | 34848011P | RESOLVE | CLASS - 2 | REISSUE 34761944P FAILURE TO MAINTAIN OBSERVED WATER PENETRATION THROUGH FACADE EXIT 2,FL 1. REMEDY: MAINTAIN BUILDING. | $0 | $0 | Sep 14, 2010 |
| Mar 20, 2009 | 34761943N | RESOLVE | CLASS - 2 | BULKHEAD DOOR LEADING TO ROOF IS DEFECTIVE. DOOR LOCK IS NOT PROPERLY INSTALLED. REMEDY: REPAIR/REPLACE. | $0 | $0 | May 12, 2009 |
| Mar 20, 2009 | 34761944P | RESOLVE | CLASS - 2 | EXTERIOR BRICK FACADE HAS BECOME POROUS AND ALLOWING RAIN INTO THE BLDG BY EXIT 2 (1ST FLR) CAUSING INTERIOR DAMAGES.... | $0 | $0 | May 12, 2009 |
| Mar 20, 2009 | 34761945R | RESOLVE | CLASS - 2 | THE ELECTRICAL ROOM (C03) AT CELLAR LEVEL IS BEING USED AS STORAGE ROOM CONSISTING OF COMPUTERS AND DECK. REMEDY: REM... | $0 | $0 | May 12, 2009 |
| Aug 28, 2007 | 34592905H | RESOLVE | Non-Hazardous | REISSUE #34526990X.CORRIDOR SMOKE STOP DOOR NOT SELF CLOSING.NOTED:CELLAR MANUAL OPERATED 2 DOORS ADJ TO ROOM CJSC HA... | $0 | $0 | Nov 13, 2007 |
| Aug 28, 2007 | 34592906J | RESOLVE | Non-Hazardous | REISSUE #34526991H.1FL CAFETERIA/MULTI PURPOSE RM 2 EXIT DOORS WHEN CLOSED ARE SAGGING & HITTING EACH OTHER.REMEDY:RE... | $0 | $0 | Nov 13, 2007 |
| Aug 28, 2007 | 34592907L | RESOLVE | Non-Hazardous | WATER PENETRATION THROUGH CEILING INTO CORRIDOR IN FRONT OF ROOM 407 &INTO CLASSROOM #406.REMEDY:STOP WATER PENETRATI... | $0 | $0 | Nov 13, 2007 |
| Jun 2, 2006 | 34526991H | RESOLVE | Non-Hazardous | REISSUED ECB# 34474490H. 1ST FL CAFETERIA/MULIT PURPOSE RM 2 EXIT DOORS WHEN CLOSED ARE SAGGING AND HITTING EACH OTHE... | $0 | $0 | Aug 15, 2006 |
| Jun 2, 2006 | 34526990X | RESOLVE | Non-Hazardous | CORRIDOR SMOKE STOP DOORS NOT SELF CLOSING. NOTED:CELLAR MANUAL OPERATED 2 DOORS ADJ TO RM CJSA HAS NO CHECKS. REISSU... | $0 | $0 | Aug 15, 2006 |
| Mar 25, 2005 | 34474488Z | RESOLVE | Non-Hazardous | EXIT PASSAGEWAY OR CORRIDOR REQUIRED WIDTH DECRESED BY OBSTRUCTION NOTED FOURTH FLOOR CORRIDOR BLOCKED AT 12 ELECTRIC... | $0 | $0 | Aug 2, 2005 |
| Mar 25, 2005 | 34474490H | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING DEFECT NOTED FIRST FLOOR CAFETERIA MULTI PURPOSE ROOM 2 EXIT DOORS WHEN CLOSED SAGGING A... | $0 | $0 | Aug 2, 2005 |
| Mar 25, 2005 | 34474489K | RESOLVE | Non-Hazardous | CORRIDOR SMOKE STOP DOORS NOT SELF-CLOSING NOTED CELLAR MANUAL OPERATED 2 DOORS NEAR ROOM C-JSC HAVE NO CHECKS REMEDY... | $0 | $0 | Aug 2, 2005 |
| Jan 6, 2003 | 34376175Z | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING. DEFECT: MISSING FIREPROOFING MATERIAL ONCEILING (METAL DECKING) BETWEEN CELLAR & FIRST ... | $0 | $0 | Mar 18, 2003 |
| Jan 6, 2003 | 34376174R | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING. DEFECT: MISSING FIREPROOFING MATERIAL UNDER METAL DECKING (ROOF SLAB) IN PENTHOUSE -MAC... | $0 | $0 | Mar 18, 2003 |