Skip to content

ECB violations

37-01-37-11 Junction Boulevard, Queens • Block 01759 • Lot 0001

54 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jul 14, 2025 39153594R RESOLVE CLASS - 2 CLASS 2. THE ELEVATOR IN THE BUILDING IS OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE. R... $312 $0 Dec 2, 2025
Apr 13, 2024 35593444P RESOLVE CLASS - 2 FAILURE TO MAINTAIN EXTERIOR BUILDING WALL OR APPURTENANCES AT EXP #2 VERTICAL CRACK FROM 2ND THRU 3RD FLOORS IN MIDD... $625 $625 Nov 26, 2024
Jan 12, 2023 39077680L RESOLVE CLASS - 1 EMERGENCY ALARM BELL NO BUZZER(CU). EMERGRNCY STOP SWITCH NO BUZZER(CU). IN CAR PHONE NOT WORKING(CU). BRAKE MAINTENA... $1,280 $0 Mar 21, 2023
Jun 1, 2021 38274126K RESOLVE CLASS - 2 7D6,5J10,19H11,35D10,70O2:7/D/6-PROPERLY AFFIX SENSOR TO FRAME. 5/J/10-ADJUST CAR DOOR 19/H/11-REPLACE WORN GIBS/HOIS... $0 $0 Aug 24, 2021
Jul 14, 2020 39025396J RESOLVE CLASS - 1 CLASS 1 DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH/ DISABLED AND RENDERED INOPERATIVE. REPAIR RESTRICTOR. CLASS 2 IT... $1,250 $0 Sep 1, 2020
Jul 14, 2020 39025395H RESOLVE CLASS - 2 RESTORE TO SERVICE SO A FULL INSPECTION CAN BE MADE BY THIS DEPARTMENT $0 $0 Sep 1, 2020
Dec 23, 2019 38272408J RESOLVE CLASS - 1 (C/U 7M7);59BB5,68B7,70O2:7-M-7 ZONE LOCK REMOVED CAUSING A HAZARDOUS CONDITION,ALLOWING CAR DOOR TO BE OPENED AT ALL... $1,250 $0 Mar 10, 2020
Aug 3, 2018 38264675Y RESOLVE CLASS - 1 66-X-10;42-X-10:(66-X-10) REPAIR ROPE GRIPPER.(42-X-10) DOOR MONITORING DOES NOT WORK. $1,250 $0 Sep 18, 2018
Dec 22, 2016 32086488L RESOLVE CLASS - 2 50A,50B,50C,50D. (50A)BOILER ROOM DOORS MISSING. (50B)PROVING SWITCH MISSING ON COMBUSTION AIR FAN. (50C)MISSING GUAR... $250 $0 May 9, 2017
Jun 29, 2015 35140612N RESOLVE CLASS - 1 WORK W/O PERMIT.INSTALLATION OF A LAUNDRY IN CELLAR.INSPECTION TIME 1110 ON 6/29/15,I OBSERVED IN CELLAR WASHING MACH... $0 $0 Nov 10, 2015
Jun 29, 2015 35140614R RESOLVE CLASS - 1 BC903.2.10.6 FAILURE TO PROVIDE SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED (2 OR MORE DRYERS) INSPECTION TIME 1110... $1,600 $0 Nov 10, 2015
Jun 29, 2015 35140613P RESOLVE CLASS - 1 GAS BEING SUPPLIED W/O INSPECTION OR TESTING BY DOB.INSPECTION TIME 1110 ON 6/29/15 I OBSERVED IN CELLAR 3 GAS FIRED ... $1,000 $0 Nov 10, 2015
Sep 9, 2011 38218051Z RESOLVE CLASS - 2 98BB05,99BB05,70O02,34O02,69M07,68B#,77B11. 68B#-MAINTENANCE LOG NOT KEPT UP TO DATE. 77B11-REPLACE TOE GUARD AS PER ... $0 $0 Oct 25, 2011
Jul 26, 2011 32070952J RESOLVE CLASS - 2 16/42/501/50B/50C/50D/50E/50F/ 50A-FRESH AIR FAN RUNS CONTINUOUS(SHOULD ONLY RUN WHEN BURNER OPERATES. 50B-SAIL SWITC... $500 $0 Sep 13, 2011
Sep 27, 2010 34848692J RESOLVE CLASS - 2 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS FOR ALT II JOB #410231342 OF WHIC... $2,500 $0 Nov 16, 2010
Sep 27, 2010 34848693L RESOLVE CLASS - 2 ALTERED/CHANGED BLDG OCCUPIED W/O A VALID C/O AS PER 28-118.3.1 AND 28-118.3.2 ALT I JOB #402401593 IS COMPLETE. THE ... $2,500 $0 Nov 16, 2010
Jan 19, 2010 38208269M RESOLVE CLASS - 1 52B14,20#11,37T07,72M07,69M07.CEASE USE ITEM.52B14-HOIST ROPE SHORTENING COUNTERWEIGHT SPRING REMOVED.OTHER ITEMS 20I... $5,000 $0 Mar 16, 2010
Jan 19, 2010 38208270J RESOLVE CLASS - 2 52B14,20I11,72M07,69M07,10H11. 52B14-SHORTEN HOIST ROPES. 20I11-6FL VISION GLASS. $500 $0 Oct 11, 2011
Aug 21, 2009 34777622Z RESOLVE CLASS - 3 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLAINT MANNER (INTERIOR). AT TIME OF INSPECTION,A TRANSMISSION OF NOISE & VIB... $0 $0 Oct 20, 2009
Feb 2, 2007 38163870R RESOLVE Non-Hazardous 16D06,56Y02,56Y13,71Q03,38O02,38Q03,05B01,12Q03. 16D06-BSMENT DOOR BACK, 71Q03-MISSING COVERS UNDER THE CAR, 38Q03-EX... $0 $0 Oct 30, 2007
Feb 2, 2007 38163869J RESOLVE Non-Hazardous 83##,51K11,33M07,66O02. 83##- RETURN TO SERVICE, 33M07- COVERS IN THE HOISTWAY. $0 $0 Oct 30, 2007
Dec 12, 2006 38162341R RESOLVE Non-Hazardous 51H11,34Q03,42X10 $0 $0 Oct 30, 2007
Sep 11, 2006 38160650L RESOLVE Non-Hazardous 20M11, 08V01, 85B05, 74B07, 66O02. (20) GLASS. (85) CO. NAME ON TAG. $440 $0 Oct 31, 2006
Sep 11, 2006 38160651N RESOLVE Non-Hazardous 83X10,42X10,85B05,20M11. (83) RESTORE TO SERVICE SO A FULL INSP CAN BEMADE. (85) CO. NAME ON TAG. (20) GLASS. $0 $0 Oct 31, 2006
Jul 10, 2006 38160202H RESOLVE Non-Hazardous 16-D-10,16-A-01,20-R-11,20-Q-03,21-L-10,36-H-10/16-D-10-REPAIR TOP PIVOT ON 5TH FLR HOISTWAY DOOR/16-A-01-HOISTWAY DO... $0 $0 Aug 29, 2006
Jul 10, 2006 38160203J RESOLVE Non-Hazardous 16-D-10,16-A-01,20-R-11,21-M-07,36-O-02,51-H-11/16-D-10-REPAIR TOP ON 3RD, 4TH FLR HOISTWAY DOOR/16-A-01-HOISTWAY DOO... $0 $0 Aug 29, 2006
Mar 14, 2006 38157453P RESOLVE Non-Hazardous 12M07/41M07/08V01/20M07/85BB05 12M COVER LIGHTS 41M #4 AND 5 FUSES MISSING 20M CAR VISION GRILL MISSING. 85BA 5YR TES... $350 $0 Mar 6, 2007
Mar 14, 2006 38157454R RESOLVE Non-Hazardous 51K11/41M07/12D03/85U05 41M FUSES 4 AND 5 MISSING. 12D COVER LIGHTS 85U NO GOV. 5YR TEST TAG. $350 $0 Mar 6, 2007
Feb 17, 2006 38157550R RESOLVE Non-Hazardous 12Q03/16D10/20Q03/20R11/36O02/83V01/85BB05. (12-Q-03)CAB LIGHTING IS UNGUARDED (16-D-10)HOISTWAY DOOR TOP PIVOTS ARE ... $180 $0 Apr 4, 2006
Feb 17, 2006 38157551Z RESOLVE Non-Hazardous 83X10/20R11/36O02/85BB05. (83-X-10)RETURN TO SERVICE SO THAT A COMPLETE INSPECTION CAN BE DONE BY THIS DEPARTMENT. (2... $180 $0 Apr 4, 2006
Jan 20, 2006 38164106X RESOLVE Non-Hazardous 51H11/42X10/85BB05. $350 $0 Jun 13, 2006
Jan 20, 2006 38164105Y RESOLVE Non-Hazardous 85BB05/08V01/21F01. (21) ADJUST CAM ROLLER $350 $0 Jun 13, 2006
Apr 20, 2005 38151697Y RESOLVE Non-Hazardous 20050809Y $0 $0 Oct 30, 2007
Jan 5, 2005 38156812N RESOLVE Non-Hazardous 11X16/23X16 (11)6 FLOOR (23)6 FLOOR $0 $0 Nov 13, 2007
Jan 5, 2005 38156813P RESOLVE Non-Hazardous 51H11/85M05 $0 $0 Oct 30, 2007
Sep 14, 2004 38149505H RESOLVE Non-Hazardous 83X10 83X REPAIR AND RESTORE TO SERVICE. $0 $0 Oct 26, 2004
Apr 22, 2003 34399667R RESOLVE Non-Hazardous HAVING INSTALLED AN AWNING WITHOUT A PERMIT.REMOVE ILLEGAL WORK/AWNING $0 $0 Jun 12, 2003
Apr 22, 2003 34399669K RESOLVE Non-Hazardous HAVING AN ILLUMINATED SIGN ALRGER THAN 8 SQ FEET. IN A WINDOW IN C DISTRICT.REMEDY;REMOVE ILLEGAL WORK/SIGNAGE $0 $0 Jun 12, 2003
Apr 22, 2003 34399666P RESOLVE Non-Hazardous HAVING AN ILLUMINATED AWNING SIGN.HAVING AWNING SIGNAGE NOT LIMITED TO THE NAME & ADDRESS OF THHE ESTABLISHMENT.HAVIN... $0 $0 Jun 12, 2003
Apr 22, 2003 34399668Z RESOLVE Non-Hazardous HAVING AWNING SIGNAGE NOT LIMITED TO THE NAME & ADDRESS OF TH ESTABLISHMENT.HAVING AWNING SIGNAGE WITHOUT LETTERS HIG... $0 $0 Jun 12, 2003
Apr 22, 2003 34399665N RESOLVE Non-Hazardous HAVING INSTALLED AN AWNING WITHOUT A PERMIT.REMEDY;REMOVE ILLEGAL WORK/AWNING $0 $0 Jun 12, 2003
Sep 25, 2002 34340700N RESOLVE Non-Hazardous HAVING AN ILLUMINATED AWNING SIGN HAVING AWNING SIGNAGE WITH A SURFACE ARE EXCEEDING 12 SW FT. HAVING AWNING SIGNAGE ... $0 $0 Nov 14, 2002
Sep 25, 2002 34340699P RESOLVE Non-Hazardous HAVING INSTALLED SIGNAGE WITHOUT A PERMIT. REMEDY: REMOVE ILLEGAL WORK. $0 $0 Nov 14, 2002
Sep 25, 2002 34340709J RESOLVE Non-Hazardous HAVING AN ILLUMINATED SIGN LARGER THAN 8 SQ FT. IN A WINDOW. REMEDY: REMOVE ILLEGAL SIGNAGE. $0 $0 Nov 14, 2002
Sep 25, 2002 34340701P RESOLVE Non-Hazardous HAVING SIGNAGE WITH A SURFACE AREA GREATER THAN 3 TIMES THE STREET FRON TAGE OF THE ZONING LOT (OR MORE THAN 150 SQ, ... $0 $0 Nov 14, 2002
Nov 20, 1998 38080865Z RESOLVE Non-Hazardous 2L11,38L11,50O2,57O2. $0 $0 Feb 9, 1999
Oct 23, 1995 38052451K RESOLVE Non-Hazardous 08V,28H,74M,57O. 28 ELIMINATE EXCESSIVE SIDE MOVMT IN CAR. 74 PROVIDE DEVICE TAGS ON MACHINE ROOM EQUIPMENT. $0 $0 Dec 12, 1995
May 5, 1993 38033704X RESOLVE Non-Hazardous 35P UNABLE TO GAIN ACCESS TO MACHINE ROOM TO COMPLETE INSPECTION. $0 $0 Jul 6, 1993
May 5, 1993 38033703Y RESOLVE Non-Hazardous 36P. UNABLE TO GAIN ACCESS TO MACHINE ROOM TO COMPLETE INSPECTION. $0 $0 Jul 6, 1993
Dec 9, 1991 38020358J RESOLVE Non-Hazardous 3O,8V,33O,47H,57O,3 CLEAN TOP OF CAR. $185 $0 Feb 11, 1992