112-40 37 Avenue, Queens • Block 01782 • Lot 0019

35 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jul 6, 2026 39194846P ACTIVE CLASS - 2 CLASS 2: **EMERGENCY PHONE UNRESPONSIVE - RENDERED INOPERATIVE** - AS PER ASME A17.1/CSA B44 2.27.1; REMEDY: RESTORE ... $625 $625 Sep 15, 2026
Jul 6, 2026 39194883Y ACTIVE CLASS - 1 ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE KITCHEN INSTALLATION OF 35 AMP ELECTRIC OVEN, IN STAIRWAY A AND B N... $2,500 $2,500 Sep 15, 2026
Jul 6, 2026 39194884X ACTIVE CLASS - 3 FAILURE TO CLOSE UNUSED OPENINGS (KNOCKOUTS) IN OUTLET/PANEL BOX. OBSERVED THRU OUT BUILDING ELECTRICAL PANELS IN BAS... $300 $300 Sep 15, 2026
Jul 6, 2026 39194885H ACTIVE CLASS - 1 ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN ELECTRICAL CLOSET THRU OUT FLO... $1,200 $1,200 Sep 15, 2026
Jul 6, 2026 39194886J ACTIVE CLASS - 2 MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED IN THE MAIN ELECTRICAL RM THAT THE TEMPO... $800 $800 Sep 15, 2026
Jul 6, 2026 39194892X ACTIVE CLASS - 1 ATOI OBSERVED THROUGHOUT BUILDING NO OPEN ENDED TOILET SEATS OR TRAP WRAPS IN RESTROOMS PER PC 420.3 WATER CLOSETS SH... $2,500 $2,500 Sep 15, 2026
Jul 6, 2026 39194893H ACTIVE CLASS - 1 OBSERVED IN BASMENT LAUNDRY LACK OF SPRINKLER COVERAGE AND OPEN ENDED GAS LINE. PER FGC 903.3.3 OBSTRUCTED LOCATIONS ... $2,500 $2,500 Sep 15, 2026
Jul 6, 2026 39194793K ACTIVE CLASS - 2 OBSERVED AN INOPERATIVE LAARS BOILER MODEL VW 2450 IN 18 CCACCV SERIAL # C00L13459 CORRECT VIOLATING CONDITIONS AND S... $1,250 $1,250 Sep 15, 2026
Jul 6, 2026 39194847R ACTIVE CLASS - 2 CLASS 2: CAR STATION PANEL - KEY SWITCHES NOT LABELED - AS PER ASME A17.1/CSA B44 2.26.4; REMEDY: PROVIDE PROPER LABE... $625 $625 Sep 15, 2026
Jul 6, 2026 39194848Z ACTIVE CLASS - 1 CLASS 1 C/U: NORMAL TERMINAL SWITCH DAMAGED AS PER ASME A17.1/CSA B44. THIS CONDITION COMPROMISES SAFE TERMINAL OPERA... $1,250 $1,250 Sep 15, 2026
Jul 6, 2026 39194877H ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. HOLE PENETRATIONS CEILING REMOVED IN GAS METER ROOM. WIRE MESH... $2,500 $2,500 Sep 15, 2026
Jul 6, 2026 39194881K ACTIVE CLASS - 1 FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR. OBSERVED IN THE MAIN ELECTRICAL RM NO INSTALLATION OF ELECTRODE GRO... $4,800 $4,800 Sep 15, 2026
Jul 6, 2026 39194882M ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED IN THE GAS METER RM FAINT ODOR OF GAS NATIONAL GRID W... $2,500 $2,500 Sep 15, 2026
Jan 3, 2024 39102610H ACTIVE CLASS - 2 REPAIR AND RESTORE TO SERVICE. $625 $625 Mar 12, 2024
Nov 22, 2022 35664382Y RESOLVE CLASS - 3 FAILURE TO POST BUILDING EXTERIOR WALL CONDITION CERTIFICATE AS REQUIRED UNDER 1RCNY 103-04 NOTED AT TIME OF INSPECTI... $0 $0 Feb 28, 2023
Jun 7, 2022 35651414R RESOLVE CLASS - 1 FAILURE TO TAKE REQUIRED MEASURES TO SECURE PUBLIC SAFETY-UNSAFE FACADE.AS PREV V35651279N ISSUED4/22/22&AS TODAY6/7/... $25,000 $25,000 May 16, 2023
Jun 7, 2022 35651412N RESOLVE CLASS - 1 WORK W/O PERMIT ATOI OBSERVED FACADE WORK IN PROGRESS W/O WORK PERMIT.OBTAIN PERMIT $2,500 $0 Dec 20, 2022
Jun 7, 2022 35651413P RESOLVE CLASS - 1 FAILURE TO MAINTAIN EXTERIOR BLDG FACADE&APPURTENANCES.@ALL EXP1,2,3,4(E,S,W,N ELEVATIONS) OBSERVED:CRACKED MASONRY S... $2,500 $2,500 May 16, 2023
Jun 7, 2022 35651415Z RESOLVE CLASS - 1 FAILURE TO COMPLY W/COMMISSIONER'S ORDER AS PREV V35651279N ISSUED4/22/22&AS TODAY6/7/22,OWNER DOESNT PROVIDE ANY SAF... $2,500 $2,500 May 16, 2023
Apr 22, 2022 35651279N RESOLVE CLASS - 1 FAILURE TO TAKE REQUIRED MEASURES TO SECURE PUBLIC SAFETY-UNSAFE FACADE.OBSERVED THAT THERE WERE NO SAFETY MEASURE IN... $10,000 $0 Oct 18, 2022
Feb 13, 2020 37018547J RESOLVE CLASS - 2 FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8C REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... $1,250 $0 Feb 9, 2021
Aug 1, 2017 38256725N RESOLVE CLASS - 2 41B7,57BB7,68M7,12B7,12Q3,67X10,70O2,25M7. 41B7-PROVIDE SPRING TYPE LOCK ON M/R DOOR; 57BB7-FIRE EXTINGUISHER TAG EXP... $0 $0 Sep 19, 2017
Oct 1, 2010 38213254X RESOLVE CLASS - 2 98M07,99M07,40Q03,69M07,100M07,40R09,16J01,100M07.(40Q03)PROVIDE COVER FOR MOTOR ROOM LIGHT SWITCH.(100M07)PROVIDE FI... $250 $0 Nov 23, 2010
Dec 19, 2005 38164088L RESOLVE Non-Hazardous 17-M-11/66-Z-09. (17-M-11) REPLACE MISSING HOISTWAY DOOR GIBON 8TH FLOOR. (66-Z-09) REMOVE WATER FROM PIT. $350 $0 Feb 7, 2006
Dec 15, 2005 38164084Y RESOLVE Non-Hazardous 66Z09 (66-Z-09) THERE IS A WATER LEAK IN PIT, REMOVE WATER FROM PIT. $0 -$180 Jan 31, 2006
Dec 15, 2005 38164085X RESOLVE Non-Hazardous 66Z09 (66-Z-09) THERE IS A WATER LEAK IN PIT, REMOVE WATER FROM PIT. $0 -$180 Jan 31, 2006
Mar 28, 2005 38156797Y RESOLVE Non-Hazardous 86M07/47Y10/02L10 86-PROVIDE AFTER TESTING HYDRAULIC TESTS OF PRESSURERELIEF VALVE & ALL OTHER COMPONETS MOTIFY DEPT ... $180 $0 May 17, 2005
Apr 17, 2003 34398634X RESOLVE Non-Hazardous HAVING A SIGN EXTENDING ABOVE THE GOUND FLOOR CEILING. LOCATION: ROOF LEVEL. WORDING: RAMADA PLAZA HOTEL. REMEDY: REM... $0 $0 Jan 29, 2004
Apr 17, 2003 34398630Z RESOLVE Non-Hazardous (1)HAVING INSTALLED A GROUND SIGN WITHOUT A PERMIT (2)HAVING AN ILLUMINATED SIGN WITHOUT A CURRENT PERMIT. (2)HAVING ... $800 $0 Jan 29, 2004
Apr 17, 2003 34398631K RESOLVE Non-Hazardous HAVING INSTALLED A WALL SIGN WITHOUT A PERMIT. LOCATION: ROOF LEVEL. WORDING: RAMADA PLAZA HOTEL. REMEDY: REMOVE ILLE... $800 $0 Jan 29, 2004
Apr 17, 2003 34398632M RESOLVE Non-Hazardous (1)HAVING PROHIBITED ILLUMINATED SIGN IN AN "R" DISTRICT (2)HAVING PROHIBTED ILLUMINATED SIGNAGE IN A WINDOW IN AN "R... $0 $0 Jan 29, 2004
Apr 17, 2003 34398633Y RESOLVE Non-Hazardous (1)HAVING MORE THAN ONE IDENTIFICATION SIGN (2)HAVING AN IDENTIFCATION SIGN WITH AN AREA MORE THAN 12 SQ FT. LOCATION... $0 $0 Jan 29, 2004
Jan 26, 2002 34308576P RESOLVE Non-Hazardous ALTERED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY ALTERATION #401076465 EXPURED JAN 10 2002. REMEDY:... $0 $0 Mar 4, 2002
Oct 11, 2000 34263406X RESOLVE Non-Hazardous FAILURE TO PROVIDE APPROVED PLANS AT PREMISES AT TIME OF INSPECTION NOTED:NO APPROVED PLANS ON SITE.REM:PROVIDE APPRO... $2,500 $0 Nov 28, 2000
Oct 11, 2000 34263407H RESOLVE Hazardous FAILURE TO PROVIDE 8'HIGH FENCE WHERE REQUIRED DURING EXCATION OPERATION.NOTED:NO 8'HIGH FENCE AT CONSTRUCTED SITE DU... $2,500 $0 Nov 28, 2000