| Apr 13, 2007 | 32053629P | RESOLVE | Hazardous | 50A,38.50A-INSTALL SLOW OPENING VALVE ON BLOW DOWN LINE TO TERMINATE LAST. | $0 | $0 | Jun 5, 2007 |
| May 27, 2005 | 32047869N | RESOLVE | Non-Hazardous | 50A/50B/50C/48(A)(B).FULTON V.T.BOILER,10 HO,NB 36445,OIL,1979.50A) IMPROPER ARRANGEMENT OF THE BLOWDOWN VALVES.INSTA... | $350 | $0 | Jul 12, 2005 |
| Feb 26, 2003 | 32041288H | RESOLVE | Non-Hazardous | B4A/ 50(A)/ 50(B)/ 50(A) FUEL PIL PIPING SYSTEMS ARE RUN BELOW BOIELR BASE RE - ROUTE OIL LINES AWAY FROM BOILER BASE... | $0 | $0 | Apr 15, 2003 |
| Sep 5, 2000 | 32019212K | RESOLVE | Non-Hazardous | WATER COLUMN DRAIN REDUCED ALSO NEEDS SEOND VALVE. L.W.C MANUAL RESET SWITCH IN PANNEL BOX REMOVED TO RESTORE. | $0 | $0 | Oct 24, 2000 |
| Dec 13, 1995 | 32013212N | ACTIVE | Non-Hazardous | 8C,9A,9B,49. FLUE PIPE TO BE PROPERLY FITTED IN THE BOILER HOUSING ANDSECURED. | $175 | $0 | Jan 30, 1996 |
| Aug 22, 1994 | 32012917Z | RESOLVE | Non-Hazardous | 49 HAND HOLE SLEEVE CORRODED GASES ESCAPING: WATER FEEDLINE MIPPLE WELLDED REPAIR UNSATISFACTORY & UN LICENSED REPALC... | $0 | $0 | Nov 1, 1994 |
| Oct 11, 1990 | 32006861H | RESOLVE | Non-Hazardous | THE PIPE SECTION NOT PROPERLY SEALED AT JOINT B GAGE GLASS TO BE FITTED WITH STOP VALVE & DRAIN PIPE UNDERNEATHE | $0 | $0 | Nov 27, 1990 |