ECB violations

63-67-64-01 Wetherole Street, Queens • Block 03095 • Lot 0050

74 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jul 27, 2026 35725454K ACTIVE CLASS - 2 REISSUE #35725440J, DATE OF ISSUE: 09/19/2025. FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. AT THE TIME OF ... $6,250 $0 Aug 14, 2026
Jul 27, 2026 35725457X ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS P... $1,250 $0 Aug 14, 2026
Jul 27, 2026 35725456Y ACTIVE CLASS - 2 REISSUE #35725438K DATE OF ISSUE: 09/19/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITE... $3,125 $0 Aug 14, 2026
Jul 27, 2026 35725455M ACTIVE CLASS - 2 REISSUE #35725439M DATE OF ISSUE: 09/19/2025. EXIT DOOR NOT SELF-CLOSING PROPERLY. AT THE TIME OF INSPECTION OBSERVED... $625 $0 Aug 14, 2026
Sep 19, 2025 35725436R RESOLVE CLASS - 2 RE-ISSUE #35684688P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES A... $1,250 $0 Oct 21, 2025
Sep 19, 2025 35725439M ACTIVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING. NOTED: 1ST FLR-EXTERIOR EXIT DOOR DO NOT CLOSE PROPERLY AT "EXIT 2" AND "EXIT 3". REMEDY:... $625 $0 Oct 21, 2025
Sep 19, 2025 35725438K ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371... $1,250 $0 Oct 21, 2025
Sep 19, 2025 35725440J ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: IN FRONTOF BUILDING THERE IS WATER DAMAGE ON CANOPY ON ... $2,500 $0 Oct 20, 2025
Sep 19, 2025 35725441L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: IN ELECTRIC METE... $1,250 $0 Oct 21, 2025
Sep 19, 2025 35725437Z RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORSMOKE DOOR DOES NOT SELF-CLOSE PROPERLY, 1ST FL... $1,250 $0 Oct 21, 2025
Jul 25, 2024 35684688P RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS P... $625 $0 Oct 8, 2024
Jul 25, 2024 35684689R RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT BULKHEAD STAIR B CRACKS AROUND DOOR, BASEMENT WALL CRACK RE... $625 $0 Oct 8, 2024
Jul 25, 2024 35684687N RESOLVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING. AT 1 FLOOR SMOKEBY ROOM 131, BY EXIT 2, 3 AND EXIT 1, 3 AND 4 ARE NOT CLOSING PROPERLY. R... $625 $0 Oct 8, 2024
Jul 25, 2024 35684686L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT 3 FLOOR DOORS 323, 319, 315, 313, 307, 2FL. GYM ENTRANCE, 2... $625 $0 Oct 8, 2024
Jun 14, 2022 35654865J RESOLVE CLASS - 2 EXIT DDOOR NOT SELF-CLOSING.OBSERVED AT GROUND LEVEL,CAFETERIA EXIT#1 AND GYM,EXIT DOORS DO NOT CLOSE PROPERLY WHEN I... $625 $0 Sep 13, 2022
Jun 16, 2020 35498146L RESOLVE CLASS - 2 REISSUE #34854921P FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES NOTED WATER DAMAGE TO MUSIC ROOM & ELECTRICA... $3,125 $0 Oct 13, 2020
May 19, 2020 39022435J RESOLVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $1,250 $0 May 26, 2020
Aug 13, 2019 35447675R RESOLVE CLASS - 2 RE-ISSUE #35342166H.FAILURE TO MAINTAIN BLDG WALL(S)OR APPURTENANCES. NOTE:@CELLAR ELECTRICAL ROOM(BACK LEFT),MUSIC R... $0 $0 Nov 12, 2019
Aug 13, 2019 35442824Z RESOLVE CLASS - 2 RE-ISSUE 35342169N.EXIT DOOR NOT SELF CLOSING.NOTE:AT PARKING LOT ENTRANCES DOOR IS STILL NOT SELF CLOSING DUE TO WAT... $0 $0 Nov 12, 2019
Jul 3, 2018 35342169N RESOLVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING. NOTED: WATER PENETRATION THROUGH EXTERIOR DOOR, MAKES THE DOOR NOT SELF-CLOSING AT ENTRAN... $0 $0 Sep 4, 2018
Jul 3, 2018 35342168L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBL... $0 $0 Sep 4, 2018
Jul 3, 2018 35342167J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC712.3; 27-345. NOTED: MISSING FIRE STOP... $0 $0 Sep 4, 2018
Jul 3, 2018 35342166H RESOLVE CLASS - 2 RE-ISSUE VIOL #35099926Y. FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: WATER PENETRATION AT ELECTRIC... $0 $0 Sep 4, 2018
Aug 19, 2015 35147193J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.RE-ISSUE #35099929J ISSUE ON 6/14/14 DEFECTIVE EMERGENCY LIGHTING @... $0 $0 Oct 27, 2015
Aug 19, 2015 35147194L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.RE-ISSUE #35099925M ISSUED ON 6/16/14 PLASTER DAMAGE EXIT 3 VESTIBU... $0 $0 Oct 27, 2015
Jun 16, 2014 35099928H RESOLVE CLASS - 2 DEFECTIVE DOORS AT 3RD FLOOR CORRIDOR DOORS DRAGGING & 2ND FLOOR STAIR F DOORS NOT CLOSING PROPERLY. REMEDY: REPAIR/R... $0 $0 Aug 26, 2014
Jun 16, 2014 35099925M RESOLVE CLASS - 2 RE-ISSUE # 34981822L. PLASTER DAMAGE EXIT 3 VESTIBULE (SKYLIGHT) & 1ST FLOOR MUSIC ROOM OFFICE AUDITORIUM. REMEDY: RE... $0 $0 Aug 26, 2014
Jun 16, 2014 35099674R RESOLVE CLASS - 2 RE-ISSUE # 35023339Z. SCHOOL YARD FENCE ATOP OF RETAINING WALL AT CHILDREN PLAY YARD EQUIPMENT ADJACENT TO LOWER YARD... $0 $0 Aug 26, 2014
Jun 16, 2014 35099927X RESOLVE CLASS - 2 MISSING VENT COVERS AT EXTERIOR WALL, SCHOOL YARD & FRONT OF BUILDING. REMEDY: PROVIDE COVERS. $0 $0 Aug 26, 2014
Jun 16, 2014 35099926Y RESOLVE CLASS - 2 RE-ISSUE # 34909826M. WATER PENETRATION INTO ELECTRICAL PANEL ROOM WATER PONDING IN ROOM AT TIME OF INSPECTION, ALSO ... $0 $0 Aug 26, 2014
Jun 16, 2014 35099929J RESOLVE CLASS - 2 DEFECTIVE EMERGENCY LIGHTING AT GYM 2NF FLOOR, CAFE, AUDITORIUM BATTERY PACK UNITS. REMEDY: REPLACE BATTERY PACK UNITS. $0 $0 Aug 26, 2014
Jun 13, 2014 35099673P RESOLVE CLASS - 1 SEVERE CORROSION OF METAL GRATING SUPPORTS AT INNER COURT YARD ADJACENT TO EXIT 3. EVIDENT DEFLECTION NOTED WITH DETA... $0 $0 Aug 26, 2014
Jun 28, 2013 35023339Z RESOLVE CLASS - 2 FALL HAZARD AT NW CORNER SCHOOL YARD FENCE NOT SECURED TO POST/ADJACENT TO COURTYARD ENTRANCE (BOOTH ST) SIDE. 5' FAL... $0 $0 Aug 20, 2013
May 30, 2012 34981822L RESOLVE CLASS - 2 SPALLING PLASTER AT EXIT 3 VESTIBULE SKYLIGHT SPALLING AND CRUMBLING PLASTER IN OVER HEAD SKYLIGHT POCKET REM; REPAIR... $0 $0 Aug 14, 2012
May 30, 2012 34981823N RESOLVE CLASS - 2 PARTIAL OBSTRUCTION AT AUDITORIUM STAGE RIGHT EXIT PASSAGEWAY PARTIALLY OBSTRUCTED W/ STANDING FAN PODIUM TABLES AND ... $0 $0 Aug 14, 2012
May 30, 2012 34981824P RESOLVE CLASS - 2 OCCUPANCY CONTRARY 22 CARS PARKED IN CENTER SCHOOLYARD CERT OF OCCUPANCY DOES NOT INDICATE OFF STREET PARKING REM; DI... $0 $0 Aug 14, 2012
May 30, 2012 34981821J RESOLVE CLASS - 2 REISSUE #34909825K MISSING FIRE STOPPING AT ELECTRIC ROOM W/ CEILING CONDUIT PENTERATIONS AT BOILER ROOM W/ PIPE PENE... $0 $0 Aug 14, 2012
Jun 2, 2011 34909827Y RESOLVE CLASS - 3 REISSUE#34854922R.PLASTIC DAMAGE IN MUSIC ROOM IN AUDITORIUM.REM:REPAIR CEILING $0 $0 Aug 2, 2011
Jun 2, 2011 34909826M RESOLVE CLASS - 2 REISSUE#34854921P.WATER PENETRATION INTO MUSIC ROOM BY AUDITORIUM ALSOIN ELECTRICAL PANEL ROOM.REM:SEAL PENETRATION. $0 $0 Aug 2, 2011
Jun 2, 2011 34909828X RESOLVE CLASS - 2 EXTERIOR WALL @ EASTSIDE CHIMNEY MORTAR JOINTS MISSING/WASHING OUT ALSO EASTSIDE,AUDITORIUM MISSING MORTAR.ALSO SPALL... $0 $0 Aug 2, 2011
Jun 2, 2011 34909825K RESOLVE CLASS - 2 REISSUE:34854950Y,34761954Z,34645897N,34586929L,34519253K.MISSING FIRESTOPPING @ CELLAR ELECTRICAL PANEL ROOM AROUND ... $0 $0 Aug 2, 2011
May 27, 2010 34854923Z RESOLVE CLASS - 2 USE OF PROHIBITED DOOR HARDWARE.OBSERVED:BULKHEAD DOOR STAIR B HAS DEAD BOLT LOCK, LOCK DIFFICULT TO OPERATE.REMEDY:U... $0 $0 Sep 14, 2010
May 27, 2010 34854950Y RESOLVE CLASS - 2 REISSUE 34761954Z.FAILURE TO MAINTAIN ADEQUATE FIRESTOPPING OBSERVED: MISSING CONCRETE BOCK ABOVE BOILER ROOM ENTRANC... $0 $0 Sep 14, 2010
May 27, 2010 34854921P RESOLVE CLASS - 2 FAILURE TO MAINTAIN.OBSERVED:WATER PENETRATION THROUGH FOUNDATION @ ELECTRIC METER ROOM(BACK LEFT CORNER) AND MUSIC R... $0 $0 Sep 14, 2010
May 27, 2010 34854924K RESOLVE CLASS - 3 FAILURE TO MAINTAIN.OBSERVED:RACKED,WARPED STAIRWELL DOORS 3 FL E,D, 2 FL C.DOORS WON'T PROPERLY CLOSE. REMEDY:MAINTA... $0 $0 Sep 14, 2010
May 27, 2010 34854922R RESOLVE CLASS - 3 FAILURE TO MAINTAIN.OBSERVED:SPALLING PLASTER ON CEILING OF MUSIC ROOMADJACENT AUDITORIUM STAGE.REMEDY:MAINTAIN BUILD... $0 $0 Sep 14, 2010
Mar 5, 2009 34761954Z RESOLVE CLASS - 2 RE 34645897N. MISSING FIRE STOPPING AT ELECTRICAL METER ROOM AT REAR WALL PIPES THAT GO INTO CEILING. ALSO ABOVE DOOR... $0 $0 May 12, 2009
May 27, 2008 34645899R RESOLVE Hazardous 27-127 REISSUE 34586926X MORTAR MISSING B/T BRICKS & DOOR LINTEL IS ROTTEN & RUSTED LOCATED @ 2 EXITS FROM CAFETERIA ... $0 $0 Jul 22, 2008
May 27, 2008 34645897N RESOLVE Hazardous 27-345 REISSUE 34586929L ELECTICAL METER RM IS MISSING FIRE STOPPING AROUND PIPE PENETRATION THROUGH THE WALL ON & DO... $0 $0 Jul 22, 2008
May 27, 2008 34645898P RESOLVE Hazardous 27-127 REISSUE 34586928J DEFECTIVE DOORS NOTED MAIN ENTRY DOOR (MIDDLEDOOR WETHEROLE SIDE) HITTING FRAME 3 FL STAIR B... $0 $0 Jul 22, 2008