ECB violations
1824 Harman Street, Queens • Block 03431 • Lot 0030
4 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 17, 2010 | 32068785Z | RESOLVE | CLASS - 3 | 5A, 50: 50 SAFTEY RELIEF VALVE MUST BE EXTENDED DOWN AND THREADS ON END REMOVED. | $0 | $0 | Jul 6, 2010 |
| Nov 14, 2008 | 32061090K | ACTIVE | CLASS - 2 | 18B,48B,50A,B. 50A-INSTALL DRAIN LINE ON GAUGE GLASS TO SAFE LOCATION.50B-ENCLOSE BOILER ROOM & ADD SECOND ENTRY DOOR... | $250 | $0 | Jan 6, 2009 |
| Aug 1, 2005 | 32048400K | RESOLVE | Non-Hazardous | 50A/50B/50C. FULTON V.T. BLR 15 HP, NB 57083, GAS 1983. 50A-SECONDARY LOW WATER CUT OFF MANUAL RESET SWITCH DISCONNEC... | $250 | $0 | Sep 20, 2005 |
| Sep 15, 2000 | 32019225J | ACTIVE | Non-Hazardous | 16/49 WATERCOLUMN DRAIN REDUCED RECEIPT FROM A CERTIFIED WELDER HOLDING R STAMP TO SUBMIT FOR WELDED HAND HOLES SUBMI... | $180 | $0 | Apr 24, 2001 |