Skip to content

ECB violations

1614-1618 Summerfield Street, Queens • Block 03555 • Lot 0012

47 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Feb 28, 2025 39139989K RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $2,500 $0 Oct 21, 2025
Feb 24, 2025 39139404X RESOLVE CLASS - 2 CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. IN-CAR EMERGENCY LIGHTING INOPERATIVE. CATEGORY 5 TEST TAG MISSING. ... $625 $625 Jun 10, 2025
Feb 24, 2025 39139405H RESOLVE CLASS - 2 CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. CATEGORY 5 TEST TAG MISSING. PROVIDE BRAILE FLOOR SIGNS AS NEEDED. $625 $625 Jun 10, 2025
Mar 7, 2024 39108104M RESOLVE CLASS - 2 OBSERVED TEMPORARY PLASTIC CAPS ON STAND PIPE VALVES THROUGHOUT BUILDING. THIS IS A HAZARDOUS CONDITION BECAUSE IN A ... $0 $0 May 14, 2024
Nov 14, 2022 39073835Z RESOLVE CLASS - 2 OBSERVED ON THE 3RD AND 2ND FLOOR LAUNDRY ROOM RESIDENTIAL GAS FLEX INSTALLED ON COMMERCIAL LAUNDRY EQUIPMENT. AS PER... $0 $0 Feb 7, 2023
Nov 14, 2022 39073818R RESOLVE CLASS - 2 I OBSERVED ON THE C LEVEL IN THE FUEL TANK ROOM THE INSTALLATION OF AN EXTENSION CORD SECURED TO METAL CONDUITS AND C... $0 $0 Feb 7, 2023
Nov 14, 2022 39073804X RESOLVE CLASS - 2 OBSERVED - AT ROOF LEVEL, MECHANICAL/ELECTRICAL PANELS RM, AT 4TH, 2ND, AND FIRST FLOOR MECHANICAL RMS, REFUSE RMS, O... $0 $0 Jan 3, 2023
Nov 14, 2022 39073833P RESOLVE CLASS - 1 GAS LEAK FOUND ON THE BULL ON THE TEE SUPPLING THE GAS TO THE WATER HEATER. NATIONAL GRID CALLED FOUND THE LEAK AND S... $1,250 $0 Jan 3, 2023
Nov 14, 2022 39073816N RESOLVE CLASS - 1 I OBSERVED ON THE C LEVEL THE ROOM LABELED HWH WITH NO REMOTE SHUT-OFF AS REQUIRED IN MC 1006.8.1 FOR FUEL BURNING SY... $2,500 $0 Jan 3, 2023
Nov 14, 2022 39073817P RESOLVE CLASS - 1 I OBSERVED ON THE FLOORS IN THE COMMON HALL THE OUTLETS NOT OF THE TAMPER-RESISTANT TYPE AS REQUIRED BY LL-39, COMPLY... $1,600 $0 Jan 3, 2023
Nov 14, 2022 39073805H RESOLVE CLASS - 2 OBSERVED: AT ROOF LEVEL, MECHANICAL/ELECTRICAL PANELS RM, AT 4TH MECHANICAL RMS, AT FIRST FLOOR MECHANICAL RM NEAR LO... $0 $0 Jan 3, 2023
Nov 14, 2022 39073834R RESOLVE CLASS - 2 OBSERVED IN CELLAR ACTIVE WATER LEAK ON FITTING( ELBOW) FOR DOMESTIC WATER. AS PER PC 102.3 OF 2014 INSTALLATIONS, BO... $0 $0 Jan 3, 2023
Nov 14, 2022 39073819Z RESOLVE CLASS - 2 I OBSERVED THE VIOLATING CONDITIONS STATED IN ECBS 39065110L & 39065109Y UNCORRECTED ON FLOORS C THRU 4, A CERTIFICAT... $0 $0 Jan 3, 2023
Jul 1, 2022 39065109Y RESOLVE CLASS - 2 I OBSERVED IN THE 3RD FLOOR ELECTRICAL CLOSET, IMPROPERLY LABELED MECH ROOM AND THE CELLAR ATS ROOM THE INSTALLATION ... $300 $300 Sep 13, 2022
Jul 1, 2022 39065110L RESOLVE CLASS - 1 I OBSERVED ON ALL FLOORS THE INSTALLATION OF GFCI OUTLETS IN THE CORRIDORS, NONE OF THE RECEPTACLES ARE TAMPER-RESIST... $1,600 $0 Jan 24, 2023
May 30, 2021 35454507N RESOLVE CLASS - 1 DUTIES OF PERMIT HOLDER ATO MY INSP,I OBSERVED ACTIVE JOBSITE W/15 WORKERS FROM VARIOUS SUBCONTRACTORS ON VARIOUS FLS... $5,000 $0 Nov 9, 2021
Mar 25, 2021 35552408R RESOLVE CLASS - 1 PERMIT HOLDER FAILED TO ENSURE WORKERS ATTEND PRESHIFT SAFETY MEETING PRIOR TO COMMENCEMENT OF WORK.NOTE:@TIME OF MY ... $0 $0 Jul 26, 2022
Mar 25, 2021 35552407P RESOLVE CLASS - 1 UNQUALIFIED SUPER OR WORKER PERFORMING WORK ON SCF.NOTE:@TIME OF MY INSP OF 4STYNB CONST WORK IN PROGRESS I OBSERVED ... $0 $0 Jul 26, 2022
Mar 17, 2021 35551405R RESOLVE CLASS - 2 FAILURE TO MAINTAIN ADEQUTE HOUSEKEEPING PER SECTION REQUIREMENTS.NOTE:AT THE TIME OF INSPECTION OF A 4 STORY NB JOBS... $0 $0 Jun 8, 2021
Mar 17, 2021 35551406Z RESOLVE CLASS - 2 FAILURE TO SAFEGUARD ALL PERSONS AND PROPERTY AFFECTED BY CONSTRUCTIONOPERATIONS.NOTE AT THE TIME OF MY INSPECTION OF... $0 $0 Jun 8, 2021
Mar 17, 2021 35551407K RESOLVE CLASS - 2 FAILURE TO MAINTAIN/DISPLAY ONSITE DOCUMENTS REQUIRED BY CHAPTER 33.ATTHE TIME OF MY INSPECTION OF A 4 STORY NB JOBSI... $0 $0 Jun 8, 2021
Nov 24, 2020 35509425P RESOLVE CLASS - 1 FAILURE TO INSTITUTE AND MAINTAIN SAFETY EQUIPMENT MEASURES. NOTE:AT THE TIME OF MY INSPECTION RESPONDING TO A COMPLA... $10,000 $0 Jun 8, 2021
Jul 10, 2020 35497425J RESOLVE CLASS - 1 CONSTRUCTION SUPERINTENDENT FAILED TO PERFORM DUTIES PER CODE.AT TIME OF INSPECTION ON AN ACTIE NEW BUILDING CONSTRUC... $10,000 $10,000 Dec 21, 2021
Jul 10, 2020 35497426L RESOLVE CLASS - 1 FAILURE TO DESIGNATE AND/OR HAVE A CONSTRUCTION SUPERINTENTDENT PRESENT AT SITE AS REQUIRED.AT TIME OF INSPECTION ON ... $0 $0 Aug 17, 2021
Jun 4, 2020 35492556R RESOLVE CLASS - 1 BC3309.1-FAILURE TO PROTECT ADJONINNG STRUCTURES(GOVERNOR)NOTED:AT TIME OF MY INSPECITON OF A NEW 4 STORY BUILDING,CO... $0 $0 Oct 19, 2021
Jun 4, 2020 35492557Z RESOLVE CLASS - 1 UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT.NOTED:AT TIME OF MY INSPECTION OF A NEW 4 STORIE BUILDING CONSTR... $2,500 $0 Oct 19, 2021
May 1, 2020 35489773X RESOLVE CLASS - 1 FAILURE O MAINTAIN/DISPLAY ON SITE DOCUMENT REQUIRED BY CHAPTER 33 AT TIME OF INSPECTION OF A 4 STORY NEW BUIDLING UN... $2,500 $0 Dec 15, 2020
Feb 27, 2020 35470890P RESOLVE CLASS - 2 BC33012-FAILURE TO COMPLY WITH ALL SAFETY MEASURES STANDARDS.AT TIME OF INSPECTION OF AN ACTIVE JOBSITE I OBSERVED 2 ... $625 $0 Jan 26, 2021
Jan 23, 2020 35457474J RESOLVE CLASS - 2 BC330762-PEDESTRIAN WALKWAY.AT TIME OF MY SWO RE-INSPECTION.PROPOSED 4STY NB,CURRENTLY AT EXCAVATION LEVEL.OBSERVED,F... $0 $0 Jul 27, 2021
Jan 16, 2020 35467431Z RESOLVE CLASS - 1 3301.1.2=FAILURE TO COMPLY WITH NYC FIRE CODE CURING WELL DING. NO WATCH PERSOSN AND NO FIRE EXTINGUIHSER NOTE:"AT TI... $0 $0 Feb 1, 2022
Jan 16, 2020 35467430R RESOLVE CLASS - 1 FAILURE TO INSTISTUTE AND MAINTAIN SAFETY EQUIPMENT MEASURES AND TEMPORARY CONSTRUCTION NOTE:AT TIME OF MY INSPECTION... $0 $0 Feb 1, 2022
Jan 16, 2020 35467429J RESOLVE CLASS - 1 CONSTRUCTION SUPERINTENDENT FAILED TOIMMEDIATELY NOTIFY THE DEPARTMENT OF CONDOITIOSN AS REQUIRED NOTE:AT TIME OF INS... $2,500 $2,500 Apr 20, 2021
Jan 16, 2020 35467428H RESOLVE CLASS - 1 FAILURE TO PROMPTLY NOTIFY THE DEPARTMENT OF AN ACCIDENT OR DAMAGE PROPERTY NOET:AT TIME OF MY INSPECTION RESPODNING ... $0 $0 Feb 1, 2022
Dec 6, 2019 35462683M RESOLVE CLASS - 1 FAILURE TO MAINTAIN/DISPLAY ON SITE DOCUMENTS REQUIRED BY CHAPTER 33 @THE TIME OF INSPECTION @A 4 STY NB I OBSERVED E... $0 $0 Jun 24, 2021
Nov 27, 2019 39013605Z RESOLVE CLASS - 1 FAILURE TO PROVIDE PROTECTION AT SIDES OF EXCAVATION. AT TIME OF INSPECTION OBSERVED AT SUMMERFIELD EXPOSURE ADJACENT... $5,000 $0 Oct 12, 2021
Nov 2, 2019 35456936K RESOLVE CLASS - 2 BC 3301.1.3 FALILURE TO COMPLY WITH MANUFACTURER SPECIFICATIONS.AT TIME OF MY INSPECTION I OBSERVED THE YODOCK SYSTEM... $0 $0 Jan 14, 2020
Nov 2, 2019 35456935Z RESOLVE CLASS - 2 FAILURE TO SAFEGUARD.AT TIME OF INSPECTION I OBSERVED AT EXP #1 THE PEDESTRIAN PROTECTION WAS INADEQUATELY PROVIDED,M... $5,000 $0 Mar 10, 2020
Sep 24, 2019 35452868J RESOLVE CLASS - 2 FENCE NOT MAINTAINED AT TIME OF INSPECTION OF AN ACTIVE NB PERMIT I OBSERVED THAT THE JOBSITE PERIMETER FENCE WAS NOT... $0 $0 Dec 10, 2019
Mar 11, 2019 35363960H RESOLVE CLASS - 2 FAILURE TO SAFEGUARD PUBLIC AND PROPERTY AT TIME OF INSPECTION OF A NEW BUILDING I OBSERVED A UTILITY CABLE FROM THE ... $2,400 $0 May 21, 2019
Mar 6, 2019 35356489J RESOLVE CLASS - 2 PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS. AT THE TIME OF MY INSPECTION IT HAS OBSERVED THAT AT EXP#1 O... $2,400 $0 Sep 10, 2019
Oct 22, 2018 35367665N RESOLVE CLASS - 2 FENCE.AT THE TIME OF MY INSPECTION OF A 2 STORY BUILDING DEMOLITION INPROGRESS.I OBSERVED MISSING CONSTRUCTION FENCE ... $0 $0 Dec 18, 2018
Oct 19, 2018 35322965X RESOLVE CLASS - 1 FAILURE TO SAFEGUARD ALL PERSON+PROPERTY AFFECTED BY CONSTRUCTION OPERATION.AT THE TIME OF MY INSPECTION @ THE ABOVE ... $0 $0 Feb 5, 2019
Jul 30, 2018 35324537Z RESOLVE CLASS - 2 PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATION. NOTE: OBSERVED SIDEWALK SHED LIGHT FIXTURES ARE NOT INSTALLED... $2,400 $0 Nov 1, 2018
Dec 2, 2008 32065227K RESOLVE CLASS - 3 48B.50A.50B 50A REVERSE BLOW DOWN VALV ALLOWING THE SLOW OPENING VALVE TO TERMINATE LAST 50B FIRE RATED SHORTROCK MIS... $0 $0 Jan 27, 2009
Dec 2, 2008 32065228M RESOLVE CLASS - 3 50A 50A REPLACE STEAM GAUGE W/ A 300 PSI APPROVED TYPE $0 $0 Jan 27, 2009
Apr 4, 2007 32045930Y RESOLVE Non-Hazardous 50A,50B,50C,50D.FUCTON VT BOILER 15HP NB 361182 GAS 1990.50A-DEFECTIVE PRIMARY BLOWDOWN VALVE.REPLACE.50B-SECONDARY B... $180 $0 May 29, 2007
Apr 4, 2007 32045929R RESOLVE Non-Hazardous 50A,B.FUCTON VT BOILER 15HP NB 50440 GAS 1986.50A-POOR HOUSEKEEPING IN BOILER ROOM.REMOVE EXISTING DEBRIS & OCEAN ENC... $180 $0 Aug 20, 2007