ECB violations

78-00-78-20 88 Street, Queens • Block 03846 • Lot 0040

56 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Mar 10, 2026 35722520X ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8;27-371(J... $1,250 $0 Mar 23, 2026
Mar 10, 2026 35722519Z ACTIVE CLASS - 2 EXIT DOOR NOT SELF CLOSING.NOTED:EMERGENCY EXTERIOR DOORS NOT SELF CLOSING DUE TO FAULTY HARDWARE OR BINDING ON EXIT ... $625 $0 Mar 23, 2026
Mar 10, 2026 35722518R ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:FIRE RATEDCLASSROOMS & SMOKE DOORS NOT SELF CLOSING DUE T... $1,250 $0 Mar 23, 2026
Mar 7, 2025 35691605X RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.STAIRS COMING FROM 2ND FLOOR AT EXP 1 STEEL STAIRS RUSTED AND H... $1,250 $0 Jun 17, 2025
Mar 14, 2024 35678981N RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED EMERGENCY LIGHTS NOT OPERABLE THROUGHOUT ENTIRE BUILDING ... $625 $0 May 6, 2024
Mar 7, 2022 35635837Z RESOLVE CLASS - 2 REISSUED #35582329J FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:NOTED:OBSERVED SPALLING CONCRETE AT ELECTRI... $1,562 $0 Jun 14, 2022
Mar 7, 2022 35635838K RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES.NOTED:OBSERVED VERTICAL CRACK APROX 12 FT IN LENGTH AT WEST ELE... $1,250 $0 Jun 14, 2022
Jun 16, 2021 35582321L RESOLVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING PROPERLY AT BASEMENT LEVEL GYM ROOM NO-C07 3 EXIT DOOR NOT SELF CLOSING PROPERLY AT 2ND FL... $625 $0 Sep 28, 2021
Jun 16, 2021 35582319M RESOLVE CLASS - 2 REISSUE#35498189L DATE OF ISSUE:06.04.2020 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED OBSERVED STORA... $1,562 $0 Sep 28, 2021
Jun 16, 2021 35582320J RESOLVE CLASS - 2 REISSUE#35498188J DATE OF ISSUE#06.04.2020 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED OBSERVED WITHI... $1,562 $0 Sep 28, 2021
Mar 11, 2021 39037500Z RESOLVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $1,250 $0 Apr 16, 2021
Mar 11, 2021 39037499K RESOLVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $1,250 $0 Apr 16, 2021
Mar 11, 2021 39037498Z RESOLVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $1,250 $0 Apr 16, 2021
Jun 4, 2020 35498186X RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER USE OF PROHIBITED DOOR &/OR HARDWARE PER BC 1008.1.8;27-371(J). NOT... $625 $0 Sep 15, 2020
Jun 4, 2020 35498187H RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: OBSERVED ILLEGAL STORAGE OF COMBUSTIBLE MATERIAL EG. PLASTI... $625 $0 Sep 15, 2020
Jun 4, 2020 35498188J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: OBSERVED WITHIN BASEMENTS ELECTRICAL ROOM WATER PENTRATING ... $625 $0 Sep 15, 2020
Jun 4, 2020 35498189L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: OBSERVED STORAGE ROOM THAT LEADS OUT INTO PLAYGROUND(ADJACE... $625 $0 Sep 15, 2020
Jul 9, 2018 35346061J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT NW SIDE (79 AVE), PARAPET W/SPAULDING AND MISSING MA... $0 $0 Oct 23, 2018
May 8, 2012 34954331N RESOLVE CLASS - 2 FAILURE TO POST-PROVIDE CERTIFICATE OF OCCUPANCY POSTED TCO EXPIRED FOR NEW & OLD BLDG #400821893T032 EXPIRED 9/18/20... $0 $0 Jul 17, 2012
May 8, 2012 34954332P RESOLVE CLASS - 2 MISSING FIRE STOPPING. @ ROOMS 238B & 338B,MOP SINK, APPROX 1 1/2' * 2' HOLE IN WALL, ABOVE MESH DOOR HEAD, TO CONCEA... $0 $0 Jul 17, 2012
Apr 15, 2011 34906570Y RESOLVE CLASS - 2 THE FOUNDATION WALL HAS BECOME POROUS AND ALLOWING RAIN WATER TO ENTERTHE BLDG CAUSING INTERIOR DAMAGES IN THE ELECTR... $0 $0 Jun 14, 2011
Apr 15, 2011 34906569R RESOLVE CLASS - 2 THE PLASTER ON THE WALL & CEILING IS SPAWING LOCATED IN ROOM 235 ON THE 2ND FLOOR LVL REM: REPAIR &/OR REPLACE PLASTER $0 $0 Jun 14, 2011
Jun 9, 2010 34861604R RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG WALLS & APPURTENANCES NOTED: CORNICE @ 2ND FL WINDOWS DEFECTIVE MISSING SECTION LOCATION EXI... $0 $0 Sep 14, 2010
Jun 9, 2010 34861603P RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER NOTED: CORRIDOR DOORS ADJACENT TO ROOMS 248 & 249 ARE MISSING FRA... $0 $0 Sep 14, 2010
May 15, 2009 34743380J RESOLVE CLASS - 3 FAILURE TO MAINTAIN BLDG. DEFECT NOTED: 2ND FLR, STAIR 'A' NEAR RM. 254 DOOR DOES NOT CLOSE. REMEDY: REPLACE DOOR. $0 $0 Jul 7, 2009
May 15, 2009 34743378K RESOLVE CLASS - 3 REISSUE: 34646520H. BASEMENT CAFETERIA GLAZED BRICK WALL NEAR EXIT 5 HAS 2 VERTICAL CRACKS FROM FLR UP APPROX 8'. REM... $0 $0 Jul 7, 2009
May 15, 2009 34743379M RESOLVE CLASS - 3 FAILURE TO MAINTAIN BLDG. DEFECT NOTED: 2ND FLR CLASSROOM 208 WALL - FRONT AT ROOF DRAIN HAS SPALLING PLASTER FROM PR... $0 $0 Jul 7, 2009
May 15, 2009 34743381L RESOLVE CLASS - 2 SEC. 1017.1;27-369. FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:PROVIDE REQUIRED CORRIDOR WIDTH PER BC 1016.2;2... $0 $0 Jul 7, 2009
Aug 25, 2008 34685042Y RESOLVE CLASS - 2 SIDEWALK SHED DOES NOT MEET BLDG CODE SPECIFICATIONS. NOTED: SIDEWALK SHED #402344138-01-EQ-SH. LIGHTS NOT ILLUMINATE... $0 $0 Dec 16, 2008
Apr 24, 2008 34646520H RESOLVE Non-Hazardous RE ISSUE #34586221X. BSMT CAFETERIA GLAZED BRICK WALLS 4 CORNERS HAVE VERTICAL CRACK FROM FLOOR UP TO CEILING. REMEDY... $0 $0 Jun 10, 2008
Apr 24, 2008 34646519K RESOLVE Non-Hazardous RE-ISSUE 34586222H. WATER PENETRATION THROUGH ROOF INTO CLASSROOM 208.REMEDY: STOP WATER PENETRATION. $0 $0 Jun 10, 2008
Jul 26, 2007 34586219R RESOLVE Non-Hazardous REISSUE #34523248H.BASEMENT:ELECTRICAL EQUIPMENT ROOM OPEN WIRE LATH ABOVE ENTRY DOORS & WALL FIRE STOPPING MISSING.A... $0 $0 Sep 11, 2007
Jul 26, 2007 34586220Y RESOLVE Non-Hazardous REISSUE #34523247X.BASEMENT ELECTRICAL EQUIPMENT ROOM CONCRETE CEILINGBEAM HORIZONTIAL CRACK LOCATED BEHIND ELECTRICA... $0 $0 Sep 11, 2007
Jul 26, 2007 34586221X RESOLVE Non-Hazardous REISSUE #34523246Y.BASEMENT CAFETERIA GLAZED BRICK WALL NEAR EXIT 5 HAS A VERTICAL CRACK FROM FLOOR UP APPROX 8'.REME... $0 $0 Sep 11, 2007
Jul 26, 2007 34586222H RESOLVE Non-Hazardous REISSUE #34523245M.WATER PENETRATION THROUGH ROOF INTO VESTIBULE AT EXIT 6 ALSO NOTED:ROOF LEAK INTO CLASSROOM 208 & ... $0 $0 Sep 11, 2007
May 12, 2006 34519441H RESOLVE Non-Hazardous ALTERED BUILDING OCCUPIED W/OUT A VALID C OF O. NOTED:JOB#400821893,ALTERATION 1, FOR MODULOR ADDITION OF BASEMENT & ... $0 $0 Aug 15, 2006
May 12, 2006 34523246Y RESOLVE Hazardous BASEMENT CAFETERIA GLAZED BRICK WALL NEAR EXIT 5 HAS A VERTICAL CRACK FROM FLOOR UP APPROX. 8 FEET. REMEDY:REPAIR/PAT... $0 $0 Aug 15, 2006
May 12, 2006 34523248H RESOLVE Hazardous BASEMENT:ELECTRICAL EQUIPMENT ROOM OPEN WIRE LATH ABOVE ENTRY DOORS & WALL FIRESTOPPING MISSING. ALSO NOTED:PAINT ROO... $0 $0 Aug 15, 2006
May 12, 2006 34523245M RESOLVE Hazardous REISSUE:#34482207N WATER PENETRATION THROUGH ROOF INTO VESTIBULE AT EXIT 6.ALSO NOTED:ROOF LEAK INTO CLASSROOM 208 & ... $0 $0 Aug 15, 2006
May 12, 2006 34523247X RESOLVE Hazardous BASEMENT ELECTRICAL EQUIPMENT ROOM CONCRETE CEILING BEAM HORIZONTAL CRACK LOCATED BEHIND ELECTRICAL PANELS. REMEDY:RE... $0 $0 Aug 15, 2006
May 25, 2005 34482207N RESOLVE Hazardous WATER PENETRATION THROUGH ROOF INTO VESTIBLUE @ EXIT 6.REMMEDY:STOP WATER PENETRATION MAKE ALL NECESSARY REPAIRS $0 $0 Aug 2, 2005
Feb 10, 2003 34375137N RESOLVE Non-Hazardous FAILURE TO MAINTAIN BUILDING DEFECT : SPALLING MISSING BRICKS OVER EIXT 3 ( INSIDE OF AUDITORIUM ) REMEDY : MAKE ALL ... $0 $0 Apr 22, 2003
Feb 10, 2003 34375138P RESOLVE Non-Hazardous FAILURE TO MAINTAIN BUILDING DEFECT : LEAKY ROOF OVER ROOMS : 208, 209AND BOY'S BATHROOM REMEDY : MAKE ALL REPAIRS $0 $0 Apr 22, 2003
Jan 22, 2002 34308445P RESOLVE Non-Hazardous *REISSUE* FAILURE TO MAINTAIN. DEFECT IS CRACKED AND SPALLING CONCRETE AT RETAINING WALL SUPPORTING PERIMETER FENCE. ... $0 $0 Apr 9, 2002
Sep 20, 2001 34280287R RESOLVE Non-Hazardous FAILURE TO PROVIDE EMERGENCY POWER EXIT LIGHTS ON THE 1ST,2ND FLOOR AND STAIRS.FAILURE TO PROVIDE EMERGENCY POWER TO ... $0 $0 Nov 27, 2001
Jul 17, 2001 34297411X RESOLVE Non-Hazardous FAILURE TO MAINTAIN DEFECT IS AS FOLLOWS RETAINING WALLS SUPPORTING PERIMETER FENCE HAS STRESS CRACKS & BROKEN CONCRE... $0 $0 Sep 25, 2001
Jul 17, 2001 34297412H RESOLVE Non-Hazardous FAILURE TO MAINTAIN DEFECTS ARE AS FOLLOWS PLAY AREA IN BACK OF SCHOOL HAS UNEVEN SURFACES AND IS SEVERELY CRACKED CA... $0 $0 Sep 25, 2001
Jan 23, 2001 34257103H RESOLVE Non-Hazardous ALTERED BUILDING OCCUPIED W/O A VALID CERTIFICATE OF OCCUPANCY.NOTE NEW WING WAS ADDED TO SCHOOL REMEDY:OBTAIN A VALI... $0 $0 Apr 3, 2001
Jan 23, 2001 34266698K RESOLVE Non-Hazardous FAILURE TO MAINTAIN DEFECTS ARE: CONCRETE RETAINING WALL SUPPORTING PERIMETER FENCE OF EASTSIDE OF PLAY YARD IS CRACK... $0 $0 Apr 3, 2001
Jan 23, 2001 34266700K RESOLVE Non-Hazardous FAILURE TO MAINTAIN BUILDING CRACK WALL IN RM151 CRACK CEILING IN RM102, 201, 103. CRACK CEILING BEAM IN HALLWAY A EX... $0 $0 Apr 3, 2001