ECB violations
18-55-18-65 211 Street, Queens • Block 05872 • Lot 0002
37 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jan 14, 2026 | 39173893P | ACTIVE | CLASS - 1 | THE ONLY ELEVATOR IN BUILDING (OR SECTION OF BUILDING) OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT... | $1,250 | $1,250 | Aug 4, 2026 |
| Feb 21, 2023 | 39080005P | RESOLVE | CLASS - 2 | IN CAR PHONE NOT WORKING NEEDS TO BE REPAIRED. | $0 | $0 | Oct 22, 2024 |
| Oct 7, 2010 | 38213261Y | RESOLVE | CLASS - 2 | 16M07,99BB05,70O02.(16M07)PROVIDE HOISTWAY DOOR SIDE GUARDS WHERE EVER DISTANCE BETWEEN HOISTWAY DOOR & CAR DOOR IS G... | $0 | $0 | Nov 30, 2010 |
| Oct 7, 2010 | 38213260M | RESOLVE | CLASS - 2 | 16M07,99BB05,71X10.(16M07)PROVIDE HOISTWAY DOOR SIDE GUARDS WHERE EVER DISTANCE BETWEEN HOISTWAY DOOR & CAR DOOR IS G... | $0 | $0 | Nov 30, 2010 |
| Sep 20, 2010 | 38212988K | RESOLVE | CLASS - 2 | 06Q03 PROVIDE HALL DOOR SIDE GUARDS WHEREVER DISTANCE BETWEEN CAR DOOR AND HALL DOOR IS GREATER THAN 5 1/2 WAR | $0 | $0 | Nov 9, 2010 |
| Sep 20, 2010 | 38212989M | RESOLVE | CLASS - 2 | 06Q03 INSTALL HALL DOOR SIDE GUARDS WHEREVER DISTANCE BTWN CAR AND HALL DOOR IS GREATER THAN 5 1/2 INCH | $0 | $0 | Nov 9, 2010 |
| Sep 20, 2010 | 38212990J | RESOLVE | CLASS - 2 | 06Q03 06M07 6Q-INSTALL HALL DOOR SIDE GUARDS WHEREVER DISTANCE BTWN CAR AND HALL DOOR IS GREATER THAN 5 1/2 INCH 6M-I... | $0 | $0 | Nov 9, 2010 |
| Jul 28, 2010 | 38210593R | RESOLVE | CLASS - 2 | 14M07,40P07 | $250 | $0 | Sep 21, 2010 |
| Jun 2, 2008 | 38185184Y | RESOLVE | Non-Hazardous | 14M07.85V15.86V15.59Q03. | $350 | $0 | Jul 22, 2008 |
| Oct 22, 2002 | 38123417M | RESOLVE | Non-Hazardous | 75U05. PERFORM 5 YERAR TEST 5 TAG. | $350 | $0 | Dec 10, 2002 |
| Mar 23, 1999 | 38085345H | RESOLVE | Non-Hazardous | 57##. -57 REMOVE WATER FROM PIT | $0 | $0 | May 11, 1999 |
| Oct 30, 1998 | 34188573X | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT. PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED... | $1,000 | $0 | Dec 23, 1998 |
| Oct 30, 1998 | 34188592L | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED... | $1,000 | $0 | Dec 23, 1998 |
| Oct 30, 1998 | 34188594P | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT. PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED... | $1,000 | $0 | Dec 23, 1998 |
| Oct 30, 1998 | 34188593N | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED... | $1,000 | $0 | Dec 23, 1998 |
| Aug 28, 1998 | 34176722M | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A FOURTH ROUND REPORT: PERIODIC INSPECTION OF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED BY LOCAL... | $1,000 | $0 | Dec 29, 1998 |
| Aug 28, 1998 | 34176721K | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTION OF EXTERIOR WALLS AND APPURTENANCES AS REQUIRE... | $1,000 | $0 | Dec 29, 1998 |
| Aug 27, 1998 | 34176720Z | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTION OF EXTERIOR WALLS AND APPURTENANCES AS REQUIRE... | $1,000 | $0 | Dec 29, 1998 |
| Jul 6, 1998 | 34174120X | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. DEFECT IS: CRACKED PARAPETWALLS THROUGHOUT ENTIRE BUILDING EXTERIOR,BUILD... | $2,500 | $0 | Dec 15, 1998 |
| Jul 1, 1998 | 34176777J | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED... | $400 | -$400 | Oct 13, 1998 |
| Jul 1, 1998 | 34176776H | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED... | $400 | -$400 | Oct 13, 1998 |
| Jun 2, 1998 | 34176492X | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENNANCES AS REQUIRE... | $400 | $0 | Dec 29, 1998 |
| Jun 2, 1998 | 34176493H | RESOLVE | Hazardous | FAILURE TO SUBMIT A FORTH ROUND TECHNICAL REPORT: PERIODIC INSPECTION OF EXTERIOR WALLS AND APPURTENANES AS REQUIRED ... | $400 | $0 | Dec 29, 1998 |
| Jun 2, 1998 | 34176494J | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCESAS REQUIRED ... | $400 | $0 | Dec 29, 1998 |
| Oct 31, 1997 | 34156110N | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED... | $400 | $0 | Feb 17, 1998 |
| Oct 31, 1997 | 34156111P | RESOLVE | Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL REPORT: PERIODIC INSPECTIONOF EXTERIOR WALLS AND APPURTENACES AS REQUIRED ... | $400 | $0 | Feb 17, 1998 |
| Aug 29, 1997 | 38063526J | RESOLVE | Non-Hazardous | 50Y54G74M 50-MACHINE LEAKS 54-MAIN LINE IMPROPERLY FUSED 74-PROPERLY STORE OIL, RACS, PARTS OR REMOVE. | $0 | $0 | Dec 16, 1997 |
| Aug 29, 1997 | 38063527L | RESOLVE | Non-Hazardous | 50Y74D56G74AY74BM 50-MACHINE OIL LEAK 74-SMOKE HOLE GRATING 54-MAIN LINE IMPROPERLY FUSED. 74A OIL TOP OF CAR. 74B PR... | $0 | $0 | Dec 16, 1997 |
| Aug 29, 1997 | 38062100H | RESOLVE | Non-Hazardous | 50Y74M74DAD 50-MACHINE LEAKS 74 OIL, RAGS, GREASE, & PARTS IN M. ROOM 74 A SMOKE HOLE GRATING. | $0 | $0 | Dec 16, 1997 |
| Aug 29, 1997 | 38062099J | RESOLVE | Non-Hazardous | 15I50Y74M74AY51L 15-ROLLER LOBBY DOOR 50-HOIST MAHINE LEAKS 74-OIL & RAGS IN M. ROOM 74A OIL & RAGS TOP OF CAR. 51 TH... | $0 | $0 | Dec 16, 1997 |
| Dec 15, 1994 | 38046058N | RESOLVE | Non-Hazardous | 05J. | $0 | $0 | Mar 7, 1995 |
| Dec 15, 1994 | 38046059P | RESOLVE | Non-Hazardous | 05J, 50F. | $0 | $0 | Mar 7, 1995 |
| Jul 19, 1991 | 38014186L | RESOLVE | Non-Hazardous | 22A,35M,74AM,74BM,74CM,(35) MACHINE ROOM VENT FAN. (74A) INSPECTION CERTIFICATE. (74B) SELECTOR TAPE GUARD. (74C) DUS... | $0 | $0 | Dec 10, 1991 |
| Jul 19, 1991 | 38014188P | RESOLVE | Non-Hazardous | 31Q;74AM;74BM; 74A.INSPECTION CERTIFICATE. 74B.DUST COVERS. | $0 | $0 | Dec 10, 1991 |
| Sep 18, 1990 | 38000672J | RESOLVE | Non-Hazardous | 14L, 15M, 31M, (15)6FLR DUST COVER. (31)PROVIDE BOX COVERS ON TOP OF CAR. | $150 | $0 | Mar 5, 1991 |
| Sep 18, 1990 | 38000670X | RESOLVE | Non-Hazardous | 46K, 37G, 03M, (03)CAPACITY PLATE. | $150 | $0 | Mar 5, 1991 |
| Sep 17, 1990 | 38000665L | RESOLVE | Non-Hazardous | 14L, 18M, 37D, 46L, 55L, (18)LOBBY LOCK COVER (37)TIMER TO CONTROLL BOARD. | $150 | $0 | Mar 5, 1991 |