ECB violations

35 Avenue, Queens • Block 06185 • Lot 0001

72 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
May 8, 2026 35732845N ACTIVE CLASS - 2 REISSUED ECB#35720063K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED AT CEILING AND WALL INSIDE ELECTRI... $3,125 $0 Jun 4, 2026
May 8, 2026 35732846P ACTIVE CLASS - 2 REISSUED ECB#35655406P FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6,FGC APPENDIX E.NOTED:AT GAS METER ... $3,125 $0 Jun 4, 2026
Sep 12, 2025 39160194N ACTIVE CLASS - 2 FOUND HYDROTHERM GAS FIRED BOILER MISSING RATING TAG, RELIEF VALVES IN WRONG POSITION CORRECT VIOLATING CONDITION AND... $6,250 $6,250 Nov 25, 2025
Sep 11, 2025 39160193L ACTIVE CLASS - 2 FOUND HYDROTHERM GAS FIRED BOILER MISSING RATING TAG RELIEF VALVES IN WRONG POSITION NEEDS SPILL SWITCHES CORRECT VIO... $6,250 $6,250 Nov 25, 2025
Jun 12, 2025 35720063K ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT CEILING INSIDE ELECTRICAL ROOM WATER PENETRATION(LEA... $1,250 $0 Aug 27, 2025
Jun 15, 2022 35655406P ACTIVE CLASS - 2 28-301.1 REISSUE35561471Y(8/4/21) FAILURE TO PROVIDE VENTILATION TO GAS METER RM PER P115.6(1968CODE),FGC APPEXE(E4)(... $3,125 $0 Sep 20, 2022
Mar 15, 2022 39058155J ACTIVE CLASS - 2 MISSING RATING PLATE ON BOILER,RELIEF VALVE NOT VERTICAL,SPILL SWITCHES MISSING,REMOTE SWITCH FOR BOILER NOT AT ARMS ... $3,125 $0 May 3, 2022
Mar 15, 2022 39058156L ACTIVE CLASS - 2 MISSING RATING PLATE,ON BOILER,NO SWITCH AT DOOR TO BOILER ROOM,NO CLEAN OUT AT BASE OF CHIMNEY,RELIEF VALVE TO BE VE... $3,125 $0 May 3, 2022
Aug 4, 2021 35561471Y ACTIVE CLASS - 2 28-301.1 REISSUE35498491M NOTED:@BSMT LEVEL GAS&ELECTRICAL METER RM,DOESNT HAVE ANY FRESH AIR OR MECHANICAL VENTILATI... $3,125 $0 Nov 16, 2021
Aug 4, 2021 35561469P RESOLVE CLASS - 2 REISSUE35498493X FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES&PUBLIC CORRI... $1,562 $0 Nov 16, 2021
Aug 4, 2021 35561470M RESOLVE CLASS - 2 REISSUE35498492Y FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NO FIRESTOPPING PER BC712.3;27-345.NOTED:@BSMT LEVE... $3,125 $0 Nov 16, 2021
Jun 17, 2020 35498496L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED:AT THE TIME OF INSPECTION,OBSERVED AT FIRST FLOOR AT VARIO... $1,250 $0 Sep 1, 2020
Jun 17, 2020 35498492Y RESOLVE CLASS - 2 REISSUE#35452172L FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345. NOTED: AT ... $3,125 $0 Sep 29, 2020
Jun 17, 2020 35498491M ACTIVE CLASS - 2 SEC. 28-301.1 REISSUE#35452173N FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),FGC APPENDIX E... $3,125 $0 Sep 29, 2020
Jun 17, 2020 35498494H RESOLVE CLASS - 2 REISSUE#35452170H FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT BASEMENT,WATER PENETRATION AT GAS METE... $1,562 $0 Sep 29, 2020
Jun 17, 2020 35498495J RESOLVE CLASS - 2 REISSUE#35452169K FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT BASEMENT,AT GAS METER ROOM & ELECTRICA... $1,562 $0 Sep 29, 2020
Jun 17, 2020 35498493X RESOLVE CLASS - 2 REISSUE#35452171J FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNAR ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC C... $1,562 $0 Sep 29, 2020
Feb 1, 2020 39016710Y ACTIVE CLASS - 1 LICENSE MASTER PLUMBER#0909 PULLED EMERGENCY WORK NOTIFICATION (EWN)#Q-00280433 ON 12-12-2019 TO RESTORE HEAT TO THE ... $2,500 $0 Jul 13, 2021
Sep 9, 2019 35452172L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NO FIRE STOPPING PER BC 712.3/27-345 NOTED AT BASEMENT GAS AND ... $0 $0 Dec 10, 2019
Sep 9, 2019 35452170H RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED AT BASEMENT GAS AND ELECTRIC METER ROOMS WATER PENETRATIO... $0 $0 Dec 10, 2019
Sep 9, 2019 35452169K RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED AT BASEMENT GAS AND ELECTRI METER ROOMS STORAGE OF VARIOU... $0 $0 Dec 10, 2019
Sep 9, 2019 35452173N ACTIVE CLASS - 2 28=301.1:FAILURE O PROVIDE VENTILATION TO GAS METER ROOM PER P 115.6(1968 CODE) FOC APPENXIS E(E4) (2014 CODE0 NOTED ... $0 $0 Dec 10, 2019
Sep 9, 2019 35452171J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER ILLUMINATION FOR EXITS EXIT DISCHARGES AND PUBLIC CORRDIROS PER... $0 $0 Dec 10, 2019
Mar 13, 2015 35120436P RESOLVE CLASS - 2 FAILURE TO MAINTAIN.OBSERVED:@ REAR BLDG(#2)WATER PENETRATION INTO CLASS ROOMS FROM ROOF @ ROOMS E,G,H.NOTICEABLE DET... $0 $0 Jul 21, 2015
Mar 13, 2015 35120435N RESOLVE CLASS - 2 FAILURE TO MAINTAIN.OBSERVED:WATER PENETRATION INTO ELECTRICAL & BOILER ROOMS THROUGH FOUNDATION WALL &/OR ELECTRIC C... $0 $0 May 19, 2015
Mar 13, 2015 35120434L RESOLVE CLASS - 2 FAILURE TO MAINTAIN.OBSERVED:@ MAIN BLDG FL 102 LOWER WINDOW OPERATOR BROKEN ON APP 30 WINDOWS,MAKING WINDOWS DIFFICU... $0 $0 May 19, 2015
Mar 13, 2015 35120433J RESOLVE CLASS - 3 FAILURE TO MAINTAIN.OBSERVED:MAIN ENTRY DOOR IS RACKED,DIFFICT TO CLOSE,DOOR HANGING CAUSING IMPROPER ALIGNMENT.REM:M... $0 $0 May 19, 2015
Mar 13, 2015 35120432H RESOLVE CLASS - 2 FAILURE TO MAINTAIN ADEQUATE FIRE STOPPING OBSERVED:@ BOILER ROOM,MISSING DRYWALL @ INTERIOR OF ROOM ADJACENT ENTRY D... $0 $0 May 19, 2015
May 22, 2014 35094503J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG.NOTED EVIDENT SIGNS OF WATER PENETRATION INTO MULTIPLE CLASSROOMS OF REAR BLDG(B)ROOM Y,71,7... $0 $0 Jul 8, 2014
Jul 29, 2013 35023897N RESOLVE CLASS - 2 SPALLING CONCRETE AT POOL AREA REAR,SPALLING & CRACKING IN CONCRETE CEILING W/PIECES MISSING EXPOSING REBARS WHICH AR... $0 $0 Dec 17, 2013
Jul 29, 2013 35023894H RESOLVE CLASS - 2 SEC. 712.3;27-345 MISSING FIRE STOPPING. AT ELECTRIC METER ROOM IN MAIN BLDG,HOLES & PENETRATIONS IN SHEET ROCK FIRE ... $0 $0 Dec 17, 2013
Jul 29, 2013 35023895J RESOLVE CLASS - 2 DOORS NOT CLOSING AT BASEMENT MAIN BLDG,ENTRY & REAR EXIT DOORS ARE NOT CLOSING W/NO CLOSERS ON BASEMENT ENTRY FIRE P... $0 $0 Dec 17, 2013
Jul 29, 2013 35023896L RESOLVE CLASS - 2 SEC. 712.3;27-345 MISSING FIRE STOPPING AT ELECTRIC METER ROOM IN POOLBLDG,OPENINGS & PENETRATIONS IN CMU BLOCK FIRE ... $0 $0 Dec 17, 2013
Jul 10, 2012 34980828H RESOLVE CLASS - 2 REISSUE: 34922577R STAIRS LEADING TO THE POOL LEVEL IS MISSING GUARD RAILING FROM THE 1ST FLOOR LEVEL. NOTED: GUARD R... $0 $0 Aug 15, 2012
Jul 10, 2012 34980830R RESOLVE CLASS - 2 REISSUE: 34922576P REAR CONCRETE STEP ARE BEING UNDER MINED & SLOPING TOWARDS 1 SIDE LOCATED BEHIND THE POOL AREA AT ... $0 $0 Aug 15, 2012
Jul 10, 2012 34980829J RESOLVE CLASS - 2 REISSUE: 34922578Z THE ELECTRICAL ROOM IS LACKING FIRE - STOPPING AT THE BUILDING #1 ADJACENT TO THE MULTI - PURPOSE ... $0 $0 Aug 15, 2012
Jun 24, 2011 34922575N RESOLVE CLASS - 2 REISSUE #34830789K DROP CEILING TILES IN THE CAFETERIA IS LOOSE & MISSING AT THE BSMT LVL REM: REPAIR &/OR REPLACE DR... $0 $0 Aug 2, 2011
Jun 24, 2011 34922576P RESOLVE CLASS - 2 REISSUE 334830787R EXTERIOR REAR CONCRETE STEPS ARE BEING UNDER MINDED ON THE 1ST FL LVL REM: FILL IN OPEN GAPS UNDER... $0 $0 Aug 2, 2011
Jun 24, 2011 34922577R RESOLVE CLASS - 2 REISSUE #34830786P FL OPENING ON 1ST FL LVL INSIDE CLOSET IS MISSING GUARD RAILS LEADING TO BSMT LVL REM: PROVIDE MAI... $0 $0 Aug 2, 2011
Jun 4, 2011 34922578Z RESOLVE CLASS - 2 REISSUE 34830784L THE ELECTRICAL ROOM IS LACKING FIRE STOPPING LOCATEDAT THE BSMT LVL REM: PROVIDE MAINTAIN FIRE STOP... $0 $0 Aug 2, 2011
Mar 8, 2010 34830786P RESOLVE CLASS - 2 REISSUE: 34780075X. THE OPENING LEADING DOWNSTAIR (STEP LADDER) TO THEBASEMENT DOES NOT HAVE GUARD RAIL TO PREVENT SO... $0 $0 May 18, 2010
Mar 8, 2010 34830788Z RESOLVE CLASS - 2 REISSUE: 34793273J. INTERIOR FLR TILES AROUND DRAIN AREA IS SINKING ATPOOL ROOM AT BASEMENT LEVEL CAUSING A TRIPPING ... $0 $0 May 18, 2010
Mar 8, 2010 34830789K RESOLVE CLASS - 3 REISSUE: 34793272H. INTERIOR CAFETERIA CEILING TILES ARE LOOSE & MISSING AT THE LOWER LEVEL. REMEDY: REPAIR/REPLACE M... $0 $0 May 18, 2010
Mar 8, 2010 34830787R RESOLVE CLASS - 2 REISSUE: 34793274L. EXTERIOR CONCRETE SIDEWALK/STEPS AT REAR OF SCHOOLIS BEING UNDER MINED ON 1ST FLR LEVEL. REMEDY: ... $0 $0 May 18, 2010
Mar 8, 2010 34830785N RESOLVE CLASS - 2 REISSUE: 34780078L EXTERIOR ROOF HAS BECOME POROUS AND LEAKING RAIN WATER INTO CLASSROOMS E,H,G, AT 1ST FLR LEVEL CAU... $0 $0 May 18, 2010
Mar 8, 2010 34830784L RESOLVE CLASS - 2 REISSUE: THE ELECTRICAL ROOM IS LACKING FIRE STOPPING AT THE BASEMENT LEVEL. REMEDY: PROVIDE/MAINTAIN FIRE-STOPPING. $0 $0 May 18, 2010
Jun 29, 2009 34793273J RESOLVE CLASS - 2 REISSUE: 34698833N THE FL TILES IN THE POOL ROOM IS SINKING MISSING LOCATED IN THE BSMT LVL CAUSING A TRIPPING HAZARD... $0 $0 Sep 15, 2009
Jun 29, 2009 34780077J RESOLVE CLASS - 2 THE ELECTRICAL RM IS LACKING FIRESTOPPING AT THE BSMT LVL REM: PROVIDEFIRESTOPPING IN THE ELECTRICAL ROOM $0 $0 Sep 15, 2009
Jun 29, 2009 34780078L RESOLVE CLASS - 2 EXTERIOR ROOF HAS BECOME POROUS AND ALLOWING RAIN INTO THE CLASSROOM A CAUSING INTERIOR DAMAGES ON THE 1ST FL LVL REM... $0 $0 Sep 15, 2009
Jun 29, 2009 34793274L RESOLVE CLASS - 2 THE CONCRETE SIDEWALK AT THE REAR OF THE PREMISES IS BEING ORDER MINE ON THE 1ST FL LVL REM: REPAIR REPLACE SIDEWALK $0 $0 Sep 15, 2009