ECB violations
35 Avenue, Queens • Block 06185 • Lot 0001
72 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 8, 2026 | 35732845N | ACTIVE | CLASS - 2 | REISSUED ECB#35720063K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED AT CEILING AND WALL INSIDE ELECTRI... | $3,125 | $0 | Jun 4, 2026 |
| May 8, 2026 | 35732846P | ACTIVE | CLASS - 2 | REISSUED ECB#35655406P FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6,FGC APPENDIX E.NOTED:AT GAS METER ... | $3,125 | $0 | Jun 4, 2026 |
| Sep 12, 2025 | 39160194N | ACTIVE | CLASS - 2 | FOUND HYDROTHERM GAS FIRED BOILER MISSING RATING TAG, RELIEF VALVES IN WRONG POSITION CORRECT VIOLATING CONDITION AND... | $6,250 | $6,250 | Nov 25, 2025 |
| Sep 11, 2025 | 39160193L | ACTIVE | CLASS - 2 | FOUND HYDROTHERM GAS FIRED BOILER MISSING RATING TAG RELIEF VALVES IN WRONG POSITION NEEDS SPILL SWITCHES CORRECT VIO... | $6,250 | $6,250 | Nov 25, 2025 |
| Jun 12, 2025 | 35720063K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT CEILING INSIDE ELECTRICAL ROOM WATER PENETRATION(LEA... | $1,250 | $0 | Aug 27, 2025 |
| Jun 15, 2022 | 35655406P | ACTIVE | CLASS - 2 | 28-301.1 REISSUE35561471Y(8/4/21) FAILURE TO PROVIDE VENTILATION TO GAS METER RM PER P115.6(1968CODE),FGC APPEXE(E4)(... | $3,125 | $0 | Sep 20, 2022 |
| Mar 15, 2022 | 39058155J | ACTIVE | CLASS - 2 | MISSING RATING PLATE ON BOILER,RELIEF VALVE NOT VERTICAL,SPILL SWITCHES MISSING,REMOTE SWITCH FOR BOILER NOT AT ARMS ... | $3,125 | $0 | May 3, 2022 |
| Mar 15, 2022 | 39058156L | ACTIVE | CLASS - 2 | MISSING RATING PLATE,ON BOILER,NO SWITCH AT DOOR TO BOILER ROOM,NO CLEAN OUT AT BASE OF CHIMNEY,RELIEF VALVE TO BE VE... | $3,125 | $0 | May 3, 2022 |
| Aug 4, 2021 | 35561471Y | ACTIVE | CLASS - 2 | 28-301.1 REISSUE35498491M NOTED:@BSMT LEVEL GAS&ELECTRICAL METER RM,DOESNT HAVE ANY FRESH AIR OR MECHANICAL VENTILATI... | $3,125 | $0 | Nov 16, 2021 |
| Aug 4, 2021 | 35561469P | RESOLVE | CLASS - 2 | REISSUE35498493X FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES&PUBLIC CORRI... | $1,562 | $0 | Nov 16, 2021 |
| Aug 4, 2021 | 35561470M | RESOLVE | CLASS - 2 | REISSUE35498492Y FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NO FIRESTOPPING PER BC712.3;27-345.NOTED:@BSMT LEVE... | $3,125 | $0 | Nov 16, 2021 |
| Jun 17, 2020 | 35498496L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED:AT THE TIME OF INSPECTION,OBSERVED AT FIRST FLOOR AT VARIO... | $1,250 | $0 | Sep 1, 2020 |
| Jun 17, 2020 | 35498492Y | RESOLVE | CLASS - 2 | REISSUE#35452172L FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345. NOTED: AT ... | $3,125 | $0 | Sep 29, 2020 |
| Jun 17, 2020 | 35498491M | ACTIVE | CLASS - 2 | SEC. 28-301.1 REISSUE#35452173N FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),FGC APPENDIX E... | $3,125 | $0 | Sep 29, 2020 |
| Jun 17, 2020 | 35498494H | RESOLVE | CLASS - 2 | REISSUE#35452170H FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT BASEMENT,WATER PENETRATION AT GAS METE... | $1,562 | $0 | Sep 29, 2020 |
| Jun 17, 2020 | 35498495J | RESOLVE | CLASS - 2 | REISSUE#35452169K FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT BASEMENT,AT GAS METER ROOM & ELECTRICA... | $1,562 | $0 | Sep 29, 2020 |
| Jun 17, 2020 | 35498493X | RESOLVE | CLASS - 2 | REISSUE#35452171J FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNAR ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC C... | $1,562 | $0 | Sep 29, 2020 |
| Feb 1, 2020 | 39016710Y | ACTIVE | CLASS - 1 | LICENSE MASTER PLUMBER#0909 PULLED EMERGENCY WORK NOTIFICATION (EWN)#Q-00280433 ON 12-12-2019 TO RESTORE HEAT TO THE ... | $2,500 | $0 | Jul 13, 2021 |
| Sep 9, 2019 | 35452172L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NO FIRE STOPPING PER BC 712.3/27-345 NOTED AT BASEMENT GAS AND ... | $0 | $0 | Dec 10, 2019 |
| Sep 9, 2019 | 35452170H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED AT BASEMENT GAS AND ELECTRIC METER ROOMS WATER PENETRATIO... | $0 | $0 | Dec 10, 2019 |
| Sep 9, 2019 | 35452169K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED AT BASEMENT GAS AND ELECTRI METER ROOMS STORAGE OF VARIOU... | $0 | $0 | Dec 10, 2019 |
| Sep 9, 2019 | 35452173N | ACTIVE | CLASS - 2 | 28=301.1:FAILURE O PROVIDE VENTILATION TO GAS METER ROOM PER P 115.6(1968 CODE) FOC APPENXIS E(E4) (2014 CODE0 NOTED ... | $0 | $0 | Dec 10, 2019 |
| Sep 9, 2019 | 35452171J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER ILLUMINATION FOR EXITS EXIT DISCHARGES AND PUBLIC CORRDIROS PER... | $0 | $0 | Dec 10, 2019 |
| Mar 13, 2015 | 35120436P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN.OBSERVED:@ REAR BLDG(#2)WATER PENETRATION INTO CLASS ROOMS FROM ROOF @ ROOMS E,G,H.NOTICEABLE DET... | $0 | $0 | Jul 21, 2015 |
| Mar 13, 2015 | 35120435N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN.OBSERVED:WATER PENETRATION INTO ELECTRICAL & BOILER ROOMS THROUGH FOUNDATION WALL &/OR ELECTRIC C... | $0 | $0 | May 19, 2015 |
| Mar 13, 2015 | 35120434L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN.OBSERVED:@ MAIN BLDG FL 102 LOWER WINDOW OPERATOR BROKEN ON APP 30 WINDOWS,MAKING WINDOWS DIFFICU... | $0 | $0 | May 19, 2015 |
| Mar 13, 2015 | 35120433J | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN.OBSERVED:MAIN ENTRY DOOR IS RACKED,DIFFICT TO CLOSE,DOOR HANGING CAUSING IMPROPER ALIGNMENT.REM:M... | $0 | $0 | May 19, 2015 |
| Mar 13, 2015 | 35120432H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN ADEQUATE FIRE STOPPING OBSERVED:@ BOILER ROOM,MISSING DRYWALL @ INTERIOR OF ROOM ADJACENT ENTRY D... | $0 | $0 | May 19, 2015 |
| May 22, 2014 | 35094503J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG.NOTED EVIDENT SIGNS OF WATER PENETRATION INTO MULTIPLE CLASSROOMS OF REAR BLDG(B)ROOM Y,71,7... | $0 | $0 | Jul 8, 2014 |
| Jul 29, 2013 | 35023897N | RESOLVE | CLASS - 2 | SPALLING CONCRETE AT POOL AREA REAR,SPALLING & CRACKING IN CONCRETE CEILING W/PIECES MISSING EXPOSING REBARS WHICH AR... | $0 | $0 | Dec 17, 2013 |
| Jul 29, 2013 | 35023894H | RESOLVE | CLASS - 2 | SEC. 712.3;27-345 MISSING FIRE STOPPING. AT ELECTRIC METER ROOM IN MAIN BLDG,HOLES & PENETRATIONS IN SHEET ROCK FIRE ... | $0 | $0 | Dec 17, 2013 |
| Jul 29, 2013 | 35023895J | RESOLVE | CLASS - 2 | DOORS NOT CLOSING AT BASEMENT MAIN BLDG,ENTRY & REAR EXIT DOORS ARE NOT CLOSING W/NO CLOSERS ON BASEMENT ENTRY FIRE P... | $0 | $0 | Dec 17, 2013 |
| Jul 29, 2013 | 35023896L | RESOLVE | CLASS - 2 | SEC. 712.3;27-345 MISSING FIRE STOPPING AT ELECTRIC METER ROOM IN POOLBLDG,OPENINGS & PENETRATIONS IN CMU BLOCK FIRE ... | $0 | $0 | Dec 17, 2013 |
| Jul 10, 2012 | 34980828H | RESOLVE | CLASS - 2 | REISSUE: 34922577R STAIRS LEADING TO THE POOL LEVEL IS MISSING GUARD RAILING FROM THE 1ST FLOOR LEVEL. NOTED: GUARD R... | $0 | $0 | Aug 15, 2012 |
| Jul 10, 2012 | 34980830R | RESOLVE | CLASS - 2 | REISSUE: 34922576P REAR CONCRETE STEP ARE BEING UNDER MINED & SLOPING TOWARDS 1 SIDE LOCATED BEHIND THE POOL AREA AT ... | $0 | $0 | Aug 15, 2012 |
| Jul 10, 2012 | 34980829J | RESOLVE | CLASS - 2 | REISSUE: 34922578Z THE ELECTRICAL ROOM IS LACKING FIRE - STOPPING AT THE BUILDING #1 ADJACENT TO THE MULTI - PURPOSE ... | $0 | $0 | Aug 15, 2012 |
| Jun 24, 2011 | 34922575N | RESOLVE | CLASS - 2 | REISSUE #34830789K DROP CEILING TILES IN THE CAFETERIA IS LOOSE & MISSING AT THE BSMT LVL REM: REPAIR &/OR REPLACE DR... | $0 | $0 | Aug 2, 2011 |
| Jun 24, 2011 | 34922576P | RESOLVE | CLASS - 2 | REISSUE 334830787R EXTERIOR REAR CONCRETE STEPS ARE BEING UNDER MINDED ON THE 1ST FL LVL REM: FILL IN OPEN GAPS UNDER... | $0 | $0 | Aug 2, 2011 |
| Jun 24, 2011 | 34922577R | RESOLVE | CLASS - 2 | REISSUE #34830786P FL OPENING ON 1ST FL LVL INSIDE CLOSET IS MISSING GUARD RAILS LEADING TO BSMT LVL REM: PROVIDE MAI... | $0 | $0 | Aug 2, 2011 |
| Jun 4, 2011 | 34922578Z | RESOLVE | CLASS - 2 | REISSUE 34830784L THE ELECTRICAL ROOM IS LACKING FIRE STOPPING LOCATEDAT THE BSMT LVL REM: PROVIDE MAINTAIN FIRE STOP... | $0 | $0 | Aug 2, 2011 |
| Mar 8, 2010 | 34830786P | RESOLVE | CLASS - 2 | REISSUE: 34780075X. THE OPENING LEADING DOWNSTAIR (STEP LADDER) TO THEBASEMENT DOES NOT HAVE GUARD RAIL TO PREVENT SO... | $0 | $0 | May 18, 2010 |
| Mar 8, 2010 | 34830788Z | RESOLVE | CLASS - 2 | REISSUE: 34793273J. INTERIOR FLR TILES AROUND DRAIN AREA IS SINKING ATPOOL ROOM AT BASEMENT LEVEL CAUSING A TRIPPING ... | $0 | $0 | May 18, 2010 |
| Mar 8, 2010 | 34830789K | RESOLVE | CLASS - 3 | REISSUE: 34793272H. INTERIOR CAFETERIA CEILING TILES ARE LOOSE & MISSING AT THE LOWER LEVEL. REMEDY: REPAIR/REPLACE M... | $0 | $0 | May 18, 2010 |
| Mar 8, 2010 | 34830787R | RESOLVE | CLASS - 2 | REISSUE: 34793274L. EXTERIOR CONCRETE SIDEWALK/STEPS AT REAR OF SCHOOLIS BEING UNDER MINED ON 1ST FLR LEVEL. REMEDY: ... | $0 | $0 | May 18, 2010 |
| Mar 8, 2010 | 34830785N | RESOLVE | CLASS - 2 | REISSUE: 34780078L EXTERIOR ROOF HAS BECOME POROUS AND LEAKING RAIN WATER INTO CLASSROOMS E,H,G, AT 1ST FLR LEVEL CAU... | $0 | $0 | May 18, 2010 |
| Mar 8, 2010 | 34830784L | RESOLVE | CLASS - 2 | REISSUE: THE ELECTRICAL ROOM IS LACKING FIRE STOPPING AT THE BASEMENT LEVEL. REMEDY: PROVIDE/MAINTAIN FIRE-STOPPING. | $0 | $0 | May 18, 2010 |
| Jun 29, 2009 | 34793273J | RESOLVE | CLASS - 2 | REISSUE: 34698833N THE FL TILES IN THE POOL ROOM IS SINKING MISSING LOCATED IN THE BSMT LVL CAUSING A TRIPPING HAZARD... | $0 | $0 | Sep 15, 2009 |
| Jun 29, 2009 | 34780077J | RESOLVE | CLASS - 2 | THE ELECTRICAL RM IS LACKING FIRESTOPPING AT THE BSMT LVL REM: PROVIDEFIRESTOPPING IN THE ELECTRICAL ROOM | $0 | $0 | Sep 15, 2009 |
| Jun 29, 2009 | 34780078L | RESOLVE | CLASS - 2 | EXTERIOR ROOF HAS BECOME POROUS AND ALLOWING RAIN INTO THE CLASSROOM A CAUSING INTERIOR DAMAGES ON THE 1ST FL LVL REM... | $0 | $0 | Sep 15, 2009 |
| Jun 29, 2009 | 34793274L | RESOLVE | CLASS - 2 | THE CONCRETE SIDEWALK AT THE REAR OF THE PREMISES IS BEING ORDER MINE ON THE 1ST FL LVL REM: REPAIR REPLACE SIDEWALK | $0 | $0 | Sep 15, 2009 |