ECB violations
101 Street, Queens • Block 09522 • Lot 0032
30 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 3, 2005 | 34482262X | RESOLVE | Non-Hazardous | NOTED: ROOF BULKHEAD DOORS USE OF ILLEGAL HARDWARE-KEYED DOOR ROOF SIDE. REMEDY: REMOVE ILLEGAL HARDWARE. | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482264J | RESOLVE | Non-Hazardous | NOTED: EXIT PASSAGE/CORRIDOR REQUIRED WIDTH DECREASED BY OBSTRUCTIONS:1)AUDITORIUM AISLES,REAR-TABLES,CHAIRS. 2)1ST F... | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482265L | RESOLVE | Non-Hazardous | NOTED:FAILURE TO PROVIDE/MAINTAIN STAIR HANDRAILING. 1)1ST FLR. MEMORIAL HALL VESTIBULE LOWER STAIR SECTION SOUTH END... | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482271H | RESOLVE | Non-Hazardous | NOTED: EXIT DOORS SWING AGAINST THE FLOW OF EGRESS. 1ST FLR. STAIR EXITS "6", "7", & "9". REMEDY: REPAIR/REPAIR DOORS. | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482272J | RESOLVE | Non-Hazardous | NOTED: FAILURE TO PROVIDE/MAINTAIN CROSS CORRIDOR DOORS. 1)3RD FLR. NORTHEAST WING BY EXIT "6" SOUTH SET MISSING NORT... | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482268R | RESOLVE | Non-Hazardous | NOTED: FAILURE TO PROVIDE ADEQUATE VENTILATION WITHIN GAS METER ROOM AS PER NYC BLDG CODE RS16P115.6. REMEDY: PROVIDE... | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482266N | RESOLVE | Non-Hazardous | NOTED: CELLAR (UNDERPOOL) CEILING BEAMS CONCRETE COVER HAVE CRACKED,MISSING SECTIONS & LOOSE THROUGHOUT-EXPOSING CORR... | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482261Y | RESOLVE | Non-Hazardous | NOTED: MID SECTION ALONG EAST ELEVATION OF BLEACHERS ELECTRIC PANEL BOX IS IMPROPERLY SUPPORTED, LEANING AND IN DANGE... | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482263H | RESOLVE | Hazardous | NOTED: WEST WING COURTYARD EAST ELEVATION 3RD FLR. MID WINDOW SET HAS DETERIORATED WOODEN BOX HANGING FROM WINDOW CRE... | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482267P | RESOLVE | Non-Hazardous | NOTED: FAILURE TO PROVIDE/MAINTAIN REQUIRED FIRE STOPPING: 1)1ST FLR.EXIT "1" & "2" PASSAGE-WALL PENETRATIONS. 2)BOIL... | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482269Z | RESOLVE | Non-Hazardous | NOTED: FAILURE TO PROVIDE/MAINTAIN EXTERIOR STEPS HAND RAILINGS: 1)NORTH ELEVATION MAIN ENTRANCE UPPER SECTION MISSIN... | $0 | $0 | Aug 2, 2005 |
| Jun 3, 2005 | 34482270X | RESOLVE | Non-Hazardous | NOTED: EXIT DOORS NOT SELF CLOSING: 1)3RD FLR. STAIR DOORS "14","10","7","6", & "1". 2)2ND FLR. STIAR DOOR "9". 3)1ST... | $0 | $0 | Aug 2, 2005 |
| Dec 23, 2003 | 32043754P | RESOLVE | Non-Hazardous | 50A. 50A-4 SAFETY RELIEF VALVES NEED TO BE PIPED DOWN 8" FROM THE FLOOR WITH NO THREADS ON END AS PER CODE. | $0 | $0 | Feb 10, 2004 |
| Dec 23, 2003 | 32043755R | RESOLVE | Non-Hazardous | 50A. 50A-4 SAFETY RELIEF VALVES NEED TO BE PIPED DOWN 8" FROM FLOOR WITH NO THREADS ON END AS PER CODE. | $0 | $0 | Feb 10, 2004 |
| Dec 23, 2003 | 32043757K | RESOLVE | Non-Hazardous | 50A. 50A-4 SAFETY RELIEF VALVES NEED TO BE PIPED DOWN 8" FROM FLOOR WITH NO THREADS ON END AS PER CODE. | $0 | $0 | Feb 10, 2004 |
| Dec 23, 2003 | 32043756Z | RESOLVE | Non-Hazardous | 50A. 50A-4 SAFETY RELIEF VALVE NEED TO BE PIPED DOWN 8" FROM FLOOR WITH NO THREADS ON END AS PER CODE | $0 | $0 | Feb 10, 2004 |
| Mar 14, 2002 | 34303096N | RESOLVE | Non-Hazardous | FAILURE OT PROVIDE 10" X 12" ELEVATOR LANDING SIGNS ON ALL FLOORS. FAILURE TO PROVIDE 3" FLOOR NUMBER SIGNS AT STIR L... | $0 | $0 | May 14, 2002 |
| Aug 10, 2001 | 34297631H | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE PANIC HARDWARE WHERE REQUIRED BY LAW. LOCATION. CAFETERIA, BOYS AND GIRLS LOCKER ROOMS. REMEDY: PR... | $0 | $0 | Oct 23, 2001 |
| Mar 5, 2001 | 34281784M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN.UPON INSPECTION OF THE ABOVE ADDRESS(1)RUNNING TRACK ON SECOND FLOOR, HAS FLOOR MISSING IN SEVERA... | $0 | $0 | Jul 3, 2001 |
| Mar 5, 2001 | 34281782Z | RESOLVE | Non-Hazardous | NO PANIC HARDWARE IN PLACE OF ASSEMBLY.UPON INSPECTION OF THE ABOVE ADDRESS(1)TEACHERS CAFETERIA-2 EXITS(2)MUSIC ROOM... | $0 | $0 | Jul 3, 2001 |
| Mar 5, 2001 | 34281787H | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN.UPON INSPECTION OF THE ABOVE ADDRESS(1)GEOMETRIC CONE FRAME IN CEILING AT POOL AREA IS CRACKED W/... | $0 | $0 | Jul 3, 2001 |
| Mar 5, 2001 | 34281783K | RESOLVE | Hazardous | EXIT DOOR OBSTRUCTED.UPON INSPECTION OF THE ABOVE ADDRESS.LIBRARY EXIT #5DOOR IS INOPERABLE.I COULD NOT OPEN THIS DOO... | $0 | $0 | Jun 26, 2001 |
| Mar 5, 2001 | 34281785Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTIAN.UPON INSPECTION OF THE ABOVE ADRESS.THE FOLLOWING AREAS ARE MISSING RADIATOR COVERS.THE STUDENTS ... | $0 | $0 | Jun 26, 2001 |
| Mar 5, 2001 | 34281786X | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE FIRE SEGREGATIKON OF OCCUIPANCIES.UPON INSPECTION OF THE ABOVE ADRESS.FIRE DOORS WERE MISSING AT E... | $0 | $0 | Jun 26, 2001 |
| Mar 5, 2001 | 34281781R | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN.UPON INSPECTION OF THE ABOVE ADDRESS.THE FOLLOWING AREAS HAVE SPALLING PLASTER ON WALLS OR CEILIN... | $0 | $0 | Jul 3, 2001 |
| Apr 14, 2000 | 34240655P | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING :DEFECTS ARE: NO COVER ON HEAT RADIATORS IN RM,346,348,350. CRACK ON WALL /CEILING IN RM... | $0 | $0 | Jun 13, 2000 |
| Apr 14, 2000 | 34240656R | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BLDG.NOTE:OPEN SEATING IN ATHELEHI FIELD IS ROTTEDAND DAMAGED HOLES IN FENCE.REMEDY:DO ALL REPAIRS. | $0 | $0 | Jun 13, 2000 |
| Feb 16, 1999 | 34198715L | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. DEFECT: PLAYFIELD SETTLED & CRACKED CAUSING TRIPHAZARDS, INCLUDED TENNIS COURTS. REMEDY: REPAVE ... | $0 | $0 | May 25, 1999 |
| Feb 16, 1999 | 34198717P | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. DEFECT: AUDITORIUM HAS SPALLING PLASTER, PEELINGPAINT, CAFETERIA CEILING FALLEN TILES, BOYS GYM ... | $0 | $0 | May 25, 1999 |
| Feb 16, 1999 | 34198716N | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. DEFECT: NO EMERGENCY LIGHTING IN STAIRWAYS. REMEDY: INSTALL ALL EMERGENCY LIGHTING. | $0 | $0 | May 25, 1999 |