ECB violations
139-01 Jamaica Avenue, Queens • Block 09673 • Lot 0001
27 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 10, 2025 | 39163378L | ACTIVE | CLASS - 2 | OBSERVED ON THE FIRST FLOOR, SPRINKLER HEADS OBSTRUCTED BY CAPS PAINTED TO THE CELLING. ALSO, HOT WATER HEATERS VENTS... | $1,250 | $0 | Aug 18, 2026 |
| Nov 7, 2024 | 39129706M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED PLASTIC ACCESS PANELS. ACCESS PANELS HAVE TO BE FIRE ... | $310 | $0 | Jan 14, 2025 |
| Nov 7, 2024 | 39129694Y | RESOLVE | CLASS - 2 | OBSERVED AT EXPOSURE 1 CAP MISSING FROM FDNY CONNECTION ALSO PAINTED SPRINKLER CAPS THROUGHOUT BUILDING FOR THE CONCE... | $310 | $0 | Jan 14, 2025 |
| Nov 7, 2024 | 39129698L | ACTIVE | CLASS - 2 | I OBSERVED THE INSTALLATION OF BRANCH CIRCUIT WIRING ON ALL FLOORS TO POINTS UNKNOWN, NO PERMIT IN DOB RECORDS COVERS... | $400 | $0 | Mar 18, 2025 |
| Nov 7, 2024 | 39129700L | ACTIVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP EXHAUST DISCONNECT THE FAILURE TO INSTALL THE EQUIPMENT GROUND WITH THE USE OF LIQUID FLEXI... | $1,200 | $0 | Mar 18, 2025 |
| Nov 7, 2024 | 39129699N | ACTIVE | CLASS - 2 | I OBSERVED ON ALL FLOORS THE FAILURE TO PROVIDE A REMOTE SHUT-DOWN AS REQUIRED OF GAS-FIRED SYSTEMS IN MC 1006.8.1 AT... | $1,250 | $0 | Jan 14, 2025 |
| Nov 7, 2024 | 39129695X | RESOLVE | CLASS - 1 | OBSERVED EXCESSIVE COMBUSTIBLE STORAGE IN THE ROOM HOUSING THE GAS METER, WATER METER, SPRINKLER MAIN AND ALSO THE EL... | $312 | $0 | Aug 28, 2025 |
| Nov 7, 2024 | 39129697J | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS THE FAILURE TO PROVIDE TAMPER-RESISTANT OUTLETS IN THE HALLS AS REQUIRED BY LL 39/2015.; LL ... | $625 | $0 | Aug 28, 2025 |
| Nov 7, 2024 | 39129704Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 COD... | $2,500 | $0 | Aug 28, 2025 |
| Nov 7, 2024 | 39129705K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $625 | $0 | Aug 28, 2025 |
| Jan 9, 2020 | 35514670P | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35415320L ISSUED ON 05-23-2019 AND TO FILE... | $2,500 | $0 | Mar 24, 2020 |
| Dec 12, 2019 | 35513844L | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATIN#35415320L ISSUED ON 5/23/19 AND TO FILE... | $6,250 | $0 | Aug 25, 2020 |
| Oct 25, 2019 | 35431511Y | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35415320L ISSUED ON 05/23/19 & TO FILE A C OF C PURSUAN... | $1,265 | -$1,265 | Apr 28, 2020 |
| Sep 26, 2019 | 38271790P | RESOLVE | CLASS - 2 | 1-L-10, 2-L-10. (1,L,10) EMERGENCY STOP SWITCH WORKS BUT NO BUZZER.(2,L,10) ALARM BELL DOES NOT WORK NO BUZZER. | $0 | $0 | Dec 10, 2019 |
| Sep 14, 2019 | 35429082M | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35415320L ISSUED ON 05/23/19 & TO FILE A C OF C PURSUAN... | $2,500 | $0 | Nov 26, 2019 |
| Aug 10, 2019 | 35427231H | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION# 35415320L ISSUED ON 05/23/19 AND TO F... | $6,250 | $0 | Dec 3, 2019 |
| May 23, 2019 | 35423450J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT IN CODE COMPLAINT MANNER NO FIRE STOPPING PER BC 712.3;27-345 NOTED: O... | $0 | $0 | Aug 1, 2019 |
| May 23, 2019 | 35415320L | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT.OBSERVED ON 5-23-19 AT ABOVE ADDRESS 4 GAS FIRED WATER HEATERS INSTALLED ON FLOORS 2-5 WITHOUT ... | $2,500 | $0 | Jul 31, 2019 |
| May 23, 2019 | 35293824M | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING NOTED:OBSERVED AT ROOF BULKHEADS A AND B ROOF EXIT DOORS DO NOT SELF CLOSE DOOR REMAIN IN ... | $312 | $0 | Aug 1, 2019 |
| Nov 15, 2016 | 38251105J | RESOLVE | CLASS - 2 | 67X10,46X10 67X10 COMMUNICATION IS NOT OPERATIVE 46X10 VENTILATION IN MOTOROOM IS NOT OPERATIVE. | $500 | $0 | Jan 3, 2017 |
| Sep 15, 2003 | 34399094Z | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING WALL.HAZARDOUS.NOTE:DEMOLITION DONE(PARTIAL)LEAVING EAST MASONARY WALL INPLACE WHICH IS ... | $800 | $0 | Jan 6, 2004 |
| Jun 6, 2003 | 34395377K | RESOLVE | Hazardous | FAILURE TO SAFEGUARD PUBLIC PROPERTY VIOLATION NOTED AT TIME OF INSPECTION BUILDING WAS DEMOLISHED MOST OF DEBRIS REM... | $1,500 | $0 | Sep 21, 2004 |
| Jun 2, 2003 | 34394908X | RESOLVE | Hazardous | FAILURE TO SAFEGUARD PUBLIC, HAZARD NOTE 4'X 8' SECTION OF PLYWOOD CONSTRUCTION FENCE DOWN ON GROUND, LEAVING DEMOLIT... | $1,500 | $0 | Sep 21, 2004 |
| May 12, 2003 | 34382142N | RESOLVE | Hazardous | FAILURE TO SAFEGUARD PROPERTY CONSTRUCTION DEMO OPERATIONS EAST PERIMETER BNOCK WALL PELL SITE AND DESIGNER PLYWOOD S... | $0 | $0 | Sep 21, 2004 |
| May 7, 2003 | 34394902P | RESOLVE | Hazardous | WORK WITHOUT A PERMIT WORK NOTED EXTERIOR MASONARY BARING WALL BEING PULLED DOWN BY MATERIAL BACK WALLET FIRST OBTAIN... | $800 | $0 | Jun 24, 2003 |
| Dec 2, 2002 | 34369146Y | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECTS IS : A 8' SECTION OF MASONRY BLOCK WALL AT NORTH WEST CORNER OF PR... | $0 | $0 | Aug 23, 2005 |
| Sep 23, 2002 | 34338655K | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING DEFECT ISL 1 PART OF BRICK FENCE APPRX. 20'LONG AND 6'HIGH FACING ON89 AVE IS OUT OF PLU... | $2,500 | $0 | Jan 18, 2005 |